Consultant Specification Power Xpert CXHTM IEC low voltage motor control and power distribution center Version 1.0 June 2015 INDEX 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. Scope Service conditions Codes and standards Supply system and fault level General requirements and arrangements Safety requirements for operation and maintenance Main busbar and dropper bar system Incoming units Bus section units Motor starter units Outgoing feeder units Networked functionality Internal wiring and terminals Cable entry and termination Earthing Labeling Painting Spares and maintenance requirements Inspection and testing Off-loading and site storage Erection and commissioning 1. SCOPE 1.1. This standard covers the requirements for indoor low voltage, high performance industrial type motor control center and switchgear, comprising busbars and functional units, such as incoming, bus section, motor starter and outgoing feeder units. 1.2. This standard shall be read in conjunction with the requisition. 2. SERVICE CONDITIONS 2.1. The equipment shall be suitable for operating indoors in a safe location for use in a pollution degree 3 environment (IEC 61439-1, par. 7.1.3). 2.2. The degree of protection of the system shall be IP42 2.2. The ambient temperature inside the substation / switch room is maximum 40°C, with a maximum average of 35°C, over 24 hours. The lower limit of ambient air temperature is 5°C. 2.3. The installation location altitude is less than 2000 meters. If altitude is greater than 2000 meters, de-rating of the assembly may be considered. 3. CODES AND STANDARDS 3.1. The equipment offered shall comply with the latest editions of: This specification The applicable national regulations The following international standards = IEC 60038 – IEC Standard voltages IEC 60051 – Direct acting indicating analogue electrical measuring instruments and their accessories – Part 1: Definitions and general requirements common to all parts IEC 60059 - Standard curent ratings IEC 60044-1 – Instrument Transformers – Part 1 : Current Transformers IEC 60044-2 – Instrument Transformers – Part 2 : Inductive voltage Transformers IEC 60112 - Method for determining the comparative and the proof tracking indices of solid insulation materials under moist conditions IEC 60269 - Low voltage fuses IEC 60529 - Degrees of protection provided by enclosures (IP Code) IEC 60947-1 - Low Voltage Switchgear and Control gear – Part 1: General rules IEC 60947-2 - Low Voltage Switchgear and Control gear – Part 2: Circuit Breakers IEC 60947-3 - Low Voltage Switchgear and Control gear – Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units IEC 60947-4-1 - Low Voltage Switchgear and Control gear – Part 4-1: Contactors and motor-starters – Electromechanical contactors and motor-starters IEC 61439-1 - Low voltage switchgear and controlgear assemblies, Part 1: General rules IEC 61439-2 - Low voltage switchgear and controlgear assemblies, Part 2: Power switchgear and control gear assemblies. IEC TR 61641 - Enclosed low-voltage switchgear and controlgear assemblies. Guide for testing under conditions of arcing due to internal fault. Technical Report. 4. SUPPLY SYSTEM AND SHORT CIRCUIT LEVEL 4.1. The system characteristics shall be as specified on the requisition. 4.2. The prospective short circuit current (rms and peak value) at the incoming terminals of the switchgear shall be as specified on the requisition. 4.3. The switchgear supplier shall submit, at quotation stage, a test report (design verification in accordance with 61439-2) from an independent authority to prove the capability to withstand the specified prospective short circuit fault current, at the required voltage level as specified on the requisition. 4.4. For determining the fault level of functional units, i.e. its wiring and components, the current limiting effect of protection devices may be taken in account when they are assembled into the final configuration into the panel. 5. GENERAL REQUIREMENTS AND ARRANGEMENTS 5.1. CONSTRUCTION 5.1.1. The switchgear shall be of a modular design, flush fronted, floor mounting and selfsupporting. The complete system shall be designed to have front and/or rear access, depending on the requisition. 5.1.2. The switchgear shall comply with form ‘4b’ according IEC 61439-2, appendix AA. 5.1.3. The maximum height shall not exceed 2300 mm., excluding a possible separate foundation frame and / or ventilation cowl, possible cable and bus duct connections on top, or mounting on elevated floors. 5.1.4. The general construction shall be sufficiently rigid to accept the weight of a man (nominally 100 kg.) on the top without harmful distortion. 5.1.5. A suitable lifting facility shall be available for each shipping section. 5.1.6. The switchgear enclosure protection degree shall be IP42 minimum according to IEC-60529. 5.1.7. The design of the switchgear shall permit the erection of extension cubicles at either end without disconnecting power to the switchgear until it is required to connect the busbars together and without the need for metal cutting equipment or drilling busbars. 5.1.8. The switchgear / MCC shall be designed for a diversity factor of 0.8 (80%) for vertical sections with two or more functional units. The switchgear/MCC supplier shall submit, at quotation stage, test reports to prove these factors, taking in account the temperature rise limits according to the IEC standards. 5.1.9. All withdrawable units shall be so designed, that disconnection of any terminated mainor auxiliary wiring / cables is not necessary. 5.1.10. All structure dimensions shall be according to DIN 41-488. 5.2. FUNCTIONAL UNITS 5.2.1. Incoming and outgoing bus section unit circuit breakers shall be of the withdrawable type. 5.2.2. Motor starters up to 132 kW and outgoing feeders up to 630 A shall be of the fully withdrawable type. All higher rated units shall be of the fixed mounting type. 5.2.3. Motor starters up to 18.5 kW, and/or feeders up to 63A, must have the capability of being supplied in a half-size width drawer, in order to reach an optimized footprint. 5.2.4. All withdrawable units must have a closed-door racking mechanism that allows the safe and easy procedure of rack-in and rack-out of the unit while keeping the unit door closed, while maintaining the IP rating of each respective unit. 5.2.5. The system must allow for and indicate 3 states: Connected, Test, Disconnected 5.2.6. The withdrawable units must be tested for a minimum of 1000 mechanical operations. 5.2.7. All withdrawable units (chassis) shall have continuous earth connections while inserted in the MCC compartments, in all functional positions: Connected-Test-Disconnected. 5.2.8. The racking mechanism of each functional unit must have a clear mechanical position indication for each functional position: Connected-Test-Disconnected. This will ensure the user has clear knowledge of the unit’s position and to help prevent the user from over-torqueing the unit’s racking mechanism. 5.2.9. Withdrawable unit must have fully segregated phases and ‘arc free’ connectors to the vertical busbars. 5.2.10 The racking mechanism of withdrawable units must be easily operated by a crank to be supplied by the panel manufacturer. 5.3. SPARE AND SPACE COMPARTMENTS 5.3.1. "Spare" compartments, or “provisions”, shall be fully equipped for easy insertion and function of properly rated units in the future as specified. 5.3.2. "Space" compartments shall be suitable to be equipped / upgraded at a future date without de-energizing the switchgear/MCC or parts of it. 5.4. COMPONENTS 5.4.1. Circuit breakers (ACBs) shall have a stored-energy closing and breaking mechanism. They shall be rated according to IEC 60947-2 category B. Circuit breakers shall have a mechanical ON / OFF indication on the front as well as mechanical indication of the charged/discharged state of the stored energy mechanism. 5.4.2. Contactors shall have a making / breaking capacity according to IEC 60947, as AC21 for incomers and outgoing feeders and AC23 for motor starters. The ON/OFF indications shall clearly be indicated on the front by means of the handle or a mechanical indicator. 5.4.3. Current transformers shall be of the epoxy enclosed type and provided with a removable short circuit link. The accuracy shall be 1M5 (incomers and outgoing feeders), resp. 3M5 (motorstarters) for measuring and 5P10 for protection purposes. The secondary side shall be 5A for incomers and outgoing feeders and 1A for motor starters. 5.4.4. Measuring devices shall be flush mounted and shall have an enclosure with a degree of protection of at least IP42. Meters used for incoming units shall be 96 x 96 mm. and for outgoing feeders and motor starters 48 x 48 mm. Number and type of required meters shall be specified. 5.4.5 The trip class of the motor overload protection in the circuit breaker shall be electronic and adjustable, at least of trip class 10 in accordance with IEC 60947-4-1. 5.5. ARRANGEMENTS 5.5.1. Unless otherwise specified, the manufacturer is free to arrange the items in the best engineered manner into a common line-up. 5.5.2. The functional (withdrawable) units are to be rated such, that they can be placed at any height, into each section. 5.5.3. Large (fixed) starters are preferred to be mounted in lower positions in their respective 5.5.4. panels . Each switchgear / MCC shall include if shown in the requisition documents: - 10% spare of the installed outgoing feeder units, with a minimum of one per each compartment size installed. - 10% space of the installed motorstarter units, with a minimum of one per each compartment size installed. 6. SAFETY REQUIREMENTS FOR OPERATION AND MAINTENANCE 6.1. INTERNAL ARC RESISTANCE 6.1.1. The switchgear shall be so designed, that the development of internal arcs, under normal operating conditions, is prevented by providing ‘arc-free’ or ‘arc-proof’ areas, inside the LV switchgear/ MCC. The concept of ‘arc-free’ or ‘arc-proof’ areas must be in full accordance with the IEC TR 61641. 6.1.2. The functional units shall be so designed that a possible internal arc will be restricted to the affected unit’s compartment, without damage to any adjacent compartments and danger to persons in the proximity of the switchgear. 6.1.3. The main busbar of the system must be located at the top of each panel and fully insulated, including connections and busbar holders, copper joints and covered bolts 6.1.4. The vertical (dropper) busbar, for the sections of the withdrawable units, must be fully segregated and insulated. 6.1.5 During the racking procedure of the drawers, an “arc-free” area must be created by the physical features insulating and isolating all power connections of the withdrawable unit prior to electrical contact with the dropper busbar. 6.1.6. The switchgear shall be tested to confirm successful assessment of criteria 1 through 7 inclusively of IEC TR 61641.The switchgear supplier shall submit, at quotation stage, a test report from an independent authority to prove conformity with IEC TR 61641 criteria 1 – 7. 6.2. INTERNAL SEPARATION 6.2.1. The segregation between the horizontal main busbar compartment and any other compartment shall be IP2X minimum. 6.2.2. The segregation between any functional units with relation to other functional units shall be IP2X at minimum. 6.2.3. Horizontal segregation barriers shall be so designed that falling of metal parts (e.g. nuts, bolts, etc.) from one compartment to another is prevented. 6.3. ACCESSIBILITY 6.3.1. A mechanical interlock shall be provided on all "switching" enclosures to prevent the cover or door being opened unless the component is in the "off" position. 6.3.2. With any door open or with unit withdrawn it shall not be possible to insert an IP2X test finger (IEC 60529) on to live parts. 6.3.3. To comply with item 6.3.2. Shrouding is mandatory; shutters shall not be used to achieve the IP2X rating. 6.4. MECHANICAL INTERLOCKS 6.4.1. The mechanism operating handles of all air circuit breakers, switches and fusedswitches shall allow padlocking in the "off" position only. 6.4.2. On withdrawable units, a mechanical interlock function and safety concept shall be utilized that: Prevents racking and un-racking functions while the handle position of the switching device is in the ON position (padlock). The functional unit door will not open while handle of the switching device (like a MCCB) is in the ON position. There shall be no means of bypassing this safety feature. The door is interlocked with the “disconnected” position. Racking functions shall not be possible while the functional unit door is open independent of the handle position. Will maintain its correct operation over the lifetime of the assembly (minimum 25 years) Provide a positive visual indication that the interlock system is engaged. It shall not be possible to close the functional unit door (or the isolating device) with the unit in a partly withdrawn position. The functional units shall be fully withdrawable and the different positions of withdrawable parts (connected, test, isolated and removed) shall be achieved in accordance with table 103 of the IEC 61439-2. The degree of protection in the test and isolation position shall be at least / IP4. On the incoming feeders of switchgear / MCC's, coupled by means of a bus coupler, key interlocks of the “Ronis” type shall be provided to allow only safe manual transfer operations when opening and closing the appropriate circuit breakers. As optional, it can be required an automatic transfer schemes, to be detailed into the data sheet of the project. 6.4.3. 7. MAIN BUSBAR AND DROPPER BAR SYSTEMS 7.1. All current-carrying parts shall be of hard drawn, high conductivity copper. 7.2. Main busbars, including neutral and earth, shall be located in the busbar compartment of the switchgear at the top of each panel. 7.3. The main busbar of the system must be fully insulated, including connections and busbar supports, copper joints and covered bolts. 7.4. The vertical (dropper) busbar, for the sections of the withdrawable units, must be fully segregated and insulated. 7.5. When using the compact half-width functional units, for motor starters up to 18.5 kW, and/or feeders up to 63A, the dropper busbar in their associated panel must be of the double configuration, with a maximum rating up to 2000A with double droppers. 7.6. Busbars and dropper bars shall be fully rated to meet or exceed the fault levels as specified. 7.7. Busbars shall be fully rated to the current carrying capacity as specified. Neutral bars shall be rated at 100% of the current rating and dimension of the phase bars. 7.8. Busbar joints and tee-offs shall be clamped connections. For all electrical main connections the correct torque shall be applied for fixing bolts. The switchgear supplier shall indicate the applicable torques in the maintenance manual. 7.9. Main busbars shall be readily suitable for future extension at both ends of the assembly. 7.10. Main busbars shall be of the same current ratings and dimensions throughout their entire length. Bus tapering shall not be permitted. 7.11. The vertical (dropper) busbar system shall be virtually ‘Maintenance Free’, and its connections can be easily maintained if necessary with front access, without the need for rear access to the panel. The type of connection between the withdrawable functional units and the dropper busbar shall be of the “scissor-connection” type. 8. INCOMING UNITS 8.1. Incoming units shall be provided with an independent manually operated air circuit breaker as specified. If specified in the data sheet, an electrically operated ACB can be required. Depending on the ratings, for instance if less than 800A / 40kA, the incoming unit can also be an independent MCCB section. 8.2. Air circuit breakers shall be of the draw-out type. They shall be provided with a direct working short circuit protection and time delayed overcurrent protection of the electronic type. The time of selectivity between the circuit breakers must be achieved with a ZSI – Zone Selective Interlocking system - according described into IEC 61912-2 – Low 8.3 8.4 voltage switchgear and control gear. The ZSI system must not require any auxiliary power to its operation, and it may be applied for faults between phases, earth-faults or both. Each incoming unit shall be mounted in a separate compartment and shall not be mounted in the same panel as outgoing feeder/ starter units. Each incoming unit shall be provided with a separate metering compartment. The type and number of required meters shall be as specified in the requisition. 9. BUS SECTION UNITS 9.1. Bus section units shall be provided with independent manually-operated fuse-switches or isolating switches as specified. 9.2. Each bus section unit shall be housed in a separate compartment. 10. MOTOR STARTER UNITS 10.1. The standard motor starter configuration is: DOL (contactor + MCCB) + intelligent relay + CTs and meter, with all components mounted into the withdrawable unit, up to 132 kW. 10.2. The motor starter coordination shall be type "2" according to IEC 60947-4-1 10.3. Each motor starter unit shall be provided with an independent manually operated circuit breaker, operable from the front and, capable of breaking the stalled motor current of the largest motor, which that unit is allowed to feed. 10.4. Current transformers for remote ammeters shall be provided if specified. If local ammeters are specified they shall have a compressed overload scale (6 times FLC). 10.5. The control voltage shall be up to 230V AC, according to the technical data sheet, and derived from the auxiliary busbar located in the cable compartment. The auxiliary busbar shall be at least IP2X. 10.6. One red “run” and one green “stop” pilot light shall be provided on the front of each unit. On 2-speed and reversing starters additional pilot lights shall be provided as specified. 10.7. The use of resistors shall not be allowed. 10.8. Unless otherwise specified, all motor starter units shall be of the "direct-on-line" type for use with 3-phase induction motors. 10.9. Reversing and 2-speed contactors shall be electrically interlocked to prevent contactors closing at the same time. 10.10. Starters of the same size and starting type shall be completely interchangeable. 11. OUTGOING FEEDER UNITS 11.1. Outgoing feeder units shall be circuit breakers, such as ACB or MCCB types, depending on the voltage ratings. For voltage > 800A, ACB types must be used. For voltage <= 800A, MCCB types can be used. Metering instruments shall be provided if specified. 11.3. The standard feeder configuration is: MCCB type + CTs and meter, all mounted into the withdrawable unit, up to 630A. CT’s shall not be mounted in the outgoing cable connections compartment. 12. NETWORKED FUNCTIONALITY 12.1 Internal network containing network cable drops for all loads and future spares as outlined in the approved requisition documents. 12.2. Network components to be pre-installed (i.e. Profibus Repeaters, Power supplies etc.) within each Vertical section as required. 12.3 Network cabling system with be internally connected and provided as a single point access cable that is available to the outside network master. 12.4 Network system will meet or exceed operating temperature requirements for the MCC. 12.5 All Network slaves will be provided with appropriate network communication cards 12.6 12.7 12.8 12.9 12.10 12.11 12.12 12.14 13. 13.1. 13.2. 13.3. 13.4. 13.5. 13.6. 13.7. 13.8. suitable for use on the installed network and as specified and approved. Network slaves will be provided with default settings, used for factory testing, or as approved. Wiring diagrams will show all network connections Network configuration drawing will be supplied showing location and wiring of all network components including repeaters and power supplies. Networking mapping information will be provided for all slave devices. Repeaters will be supplied pre-configured, as tested, with all documentation. Network system will be supplied such that all components are suitable for use at the designated design speed / baudrate (e.g. 125K) As required, certain network protocols maybe supported by use of a communication Gateway that will be pre-installed and configured. 12.13 All devices that require a unique network identification address or tag for their associated communication protocol, such as IP address or other addressing types, shall have these identifiers preset at the factory and will be recorded in the project documentation. Profibus cable will be suitable and approved for Profibus DP. Cable will have an ACM rating of 600V 75 degrees C (or equivalent). INTERNAL WIRING AND TERMINALS All internal wiring shall be suitable sized in accordance with the applicable standards and / or manufacturer’s instructions for the used components, with a minimum of 1.5 sq. mm. Secondary wiring from current transformers shall be at least 2,5 sq. mm, and flexibility class V (minimum) or VI (preferable). Auxiliary wiring is identified with markings in black letters / figures onto the insulation or by means of white clip-on code markers with black letters / figures. The marking shall be in accordance with the related wiring diagrams. No more than one wire shall be connected to each terminal, unless the terminal is fit to connect more than one conductor. Where common connections are required, terminal jumper strips shall be used. All internal wiring shall be connected to the same side of the terminal block; the other side shall only be used for external wiring. Main cable terminals allowing the conductors to be connected without the use of cable lugs of any type is strongly preferred. They shall guarantee sufficient contact pressure without damaging the cable conductors. Terminals for auxiliary wiring and cables shall be of the self-clamping type. Terminals shall be identified in accordance with the related wiring diagram. It shall be possible to safely carry out any work on the main and auxiliary wiring of a unit, when de-energized with all other units remaining energized 14. CABLE ENTRY AND TERMINATION 14.1. For incomers it shall be specified if cable(s) or busduct(s) are used. The direction of busduct(s) will be as specified. All outgoing cables will be as specified. 14.2. Switchgear shall have facilities for the entry of cables from either top or bottom on incoming feeders and top and/or bottom on outgoing units with a cable compartment. 14.3. Vertical sections with two or more functional units shall be provided with a separate vertical cable compartment to run the full height of the equipment. The width of this compartment shall be at least 400 mm. Facilities for fixing the cables shall be provided within this compartment. 14.4. Unless otherwise specified, the purchaser shall provide the necessary cable glands, clamps and -lugs. 14.5. It shall be possible to terminate cable at any outgoing unit in complete safety with all other outgoing units energized. 14.6. Cable way doors shall be equipped with a three-point locking system. 15. EARTHING 15.1. The switchgear shall be provided with a continuous main earth bar along the whole length, located in the busbar compartment. The minimum size shall be 40x10 mm. 15.2. A vertical earth bar shall be provided in each vertical section along the whole height of the equipment. The minimum size shall be 30x10 mm. It shall have provisions for termination of an earth conductor per specified cable. 15.3. The earth bars shall be copper and suitably sized to withstand the fault current level and fault clearing time under the prospective short circuit conditions for a solidly earthed system. 15.4. The switchgear’s enclosures shall be bonded to these earth bars, including all individual vertical sections, all fixed and withdrawable-type equipment when in service position and all metal cable sheets. When earth continuity of removable or withdrawable parts is arranged via metal support surfaces, the switchgear / MCC supplier shall provide type test certificates, indicating fulfillment of the requirements of effective conductivity and the precautions necessary to guarantee permanent good conductivity. 15.5. Doors mounted with voltage carrying equipment shall be earthed by means of a suitable sized flexible copper conductor. 15.6. When racking the functional units into service, the first electrical connection to be made will be the earth connection. When racking the functional unit out of service, the last electrical connection to be broken will be the earth connection. 16. LABELING 16.1. Labels shall be "resopal" or similar, with black letters on a white background. They shall be fixed to the switchgear by means of proven durable self-threading screws or rivets or by insertion into the appropriate mounting slot. 16.2. One label per compartment, indicating the compartment number (A, B, C, etc.) and the connected equipment and/or equipment number, shall be provided. Minimum label dimension 63 x 21.7 mm. Letter heights shall be at least 4 mm. 16.3. Each removable or withdrawable unit shall contain the same equipment as indicated on the front door. 16.4. Safety shutters for ACB’s shall be clearly labeled with 25 mm high white letters on a red background, as follows: - Busbar shutters marked "BUS-BAR" - Incoming circuit shutters marked "INCOMING SUPPLY" 16.5. Removable safety shrouds shall be fitted with "DANGER" warning labels. 17. PAINTING 17.1. The standard painting method is: - pre-treatment (degreased, phosphate coating, made passive) - powder coating (thermosetting powder with epoxy resin as base, applied electrostatically in average layer thickness of 60 – 70 micrometers) 17.2. The color of all outer walls (rear wall, top plates, compartment covers and external sidewalls) shall be RAL7035. 17.3. Profiles, support brackets, mounting plates, separations, partitions, etc. inside the enclosure shall be of galvanized sheet steel. 18. 18.1. 18.2. 18.3. SPARES AND MAINTENANCE REQUIREMENTS The manufacturer shall submit a recommended spare parts list. The manufacturer shall state and price separately in its quotation all necessary special tools and equipment required for proper maintenance and testing at site. The manufacturer shall submit together with the switchgear an erection, operating and maintenance manual. 19. 19.1. 19.2. 19.3. 19.4. INSPECTION AND TESTING The purchaser will specify whether a factory acceptance test, witnessed by purchaser or their representative, will be required for each switchgear. Factory acceptance tests shall be carried out on the complete assembled switchgear, as follows: visual inspection to verify whether the composition of the assembly is in accordance with the approved order documents Measurement of the insulating resistance High-voltage test in accordance with IEC 61439, item 11.9 Check of electrically operated switchgear Functional test of mechanical interlocks Check on interchangeability of equal components Complete records of the above inspection and tests shall be compiled into one inspection document by the manufacturer. A copy shall be sent to the purchaser. The purchaser may, at their option, request special testing requirements. When this is the case, the special requirements should be issued to the manufacturer so any additional costs or charges will be identified and quoted as necessary. 20. OFF-LOADING AND SITE STORAGE 20.1. The equipment shall not be dispatched from the manufacturer's production facility until a date of arrival at the site is agreed with the purchaser. This is to ensure that proper arrangements are made for receipt and off-loading. The purchaser can also waive for this right, since the manufacturer was formally informed about this option. 20.2. The manufacturer shall indicate in its quotation whether facilities for off-loading should be arranged by purchaser. 20.3. The manufacturer shall indicate in its quotation the minimum conditions for temporary storage at site. 21. ERECTION AND COMMISSIONING 21.1. The term "erection" shall be interpreted as “fixing and leveling on prepared foundations and the bolting together of sections, busbars, and other loose items, to form a complete unit”. 21.2. The purchaser will specify whether erection, supervision of erection, or no erection is required from the manufacturer. 21.3. The purchaser will specify whether commissioning is required from the manufacturer. EXAMPLE LVS SPECIFICATION – MCC: [Default Spec] ; [Optional Spec] ; [2nd Optional Spec] STANDARDS AND REGULATIONS: - IEC 61439-1 / IEC 61439/2 / IEC TR 61641 - Standard specification LV Switchgear and Motor Control Centre INSTALLATION ENVIRONMENT: - Location : Indoor - Altitude : <= 2000 m - Ambient temperature (24 hr average) : 35 degrees C - Pollution degree : 3 - Degree of protection : IP42 SUPPLY DETAILS: - Earthing system : [TN-S] ; [TN-C-S] - External connection : L1, L2, L3, N, PE - Rated Voltage (Un) : [415V] ; [440V] ; [480V] - Rated frequency (fn) : [50 Hz] ; [60 Hz] - Rated short-term withstand current (Icw) : [50 kA] ; [65 kA] ; [80 kA] ASSEMBLY AND ERECTION: - Incoming cables : Bottom - Outgoing cables : Bottom - Type of access : [Front] ; [Rear] - Max. height : 2300 mm - Internal form of separation : [3B] ; [4B] MAIN BUSBAR SYSTEM: - Position : Top - Rated current (In) : [1600 A] ; [2500 A] ; [3200 A] - Rated short time withstand current (Icw) : 50 kA / 1s - Rated peak withstand current (Ipk) : 110 kA - Number of bars : L1, L2, L3, N, PE - Neutral rating : N = 100 % VERTICAL BUSBAR SYSTEM: - Rated current (In) : 800 A - Rated short time withstand current (Icw) : 50 kA / 1s - Insulation : phase to phase, phase to neutral and phases / neutral to ground insulated - Number of bars : L1, L2, L3, N - Neutral rating : N = 100 % INCOMING FEEDERS AND BUSCOUPLERS - Air circuit breaker, type Eaton NRX, 4 pole 1600 A, 50 kA Withdrawable design Mechanical ON and OFF pushbutton Pushbutton padlocking facility Trip unit, type Eaton Digitrip 520LSI Auxiliary Switch local / remote Auxiliary Switch open / close Signal lamps open / close / trip OUTGOING MOTOR STARTER UNITS (DOL) ≤ 15 kW Motor Circuit Protection, type Eaton series G Contactor, type Eaton DILM Electronic Overload, type Eaton C400 Series - Withdrawable design, with racking system to allowed for racking behind closed door. - MCP interlocked with the door so the door can only be opened in OFF-position of the switch. - All withdrawable units must have a closed-door racking mechanism that allows the safe and easy procedure of rack-in and rack-out of the unit while keeping the unit door closed, while maintaining the IP rating of each respective unit. - The door must be interlocked with the “disconnect” position. No racking functions shall be possible while the door is open independent of the handle position. - The degree of protection in the test and isolation position shall be at least IP42. - Padlock facility in the appropriate positions. - Signal lamps (on / off ), Eaton type M22-series. OUTGOING MOTOR STARTER UNITS (DOL) ≥ 15 kW Motor Circuit Protection, type Eaton series NZM Contactor, type Eaton DILM - Electronic Overload, type Eaton C400 SeriesWithdrawable design up to 132kW - MCP interlocked with the door which can only be opened in OFF-position of the switch. - All withdrawable units must have a closed-door racking mechanism that allows the safe and easy procedure of rack-in and rack-out of the unit while keeping the unit door closed, while maintaining the IP rating of each respective unit. - The door must be interlocked with the “disconnect” position. No racking functions shall be possible while the door is open independent of the handle position. - The degree of protection in the test and isolation position shall be at least IP42. - Padlock facility in all appropriate positions - 3 Signal lamps (on / off / trip), Eaton type M22-series - Auxiliary protection by Miniature Circuit Breaker, type Eaton PLSM-C2 - 1 CT for Amp-metering (for motor starters ≥ 4 kW) - DIN48 Amp Meter in front compartment - 1 Core Balance CT, type Eaton ELRCT and protection device, type Eaton ELR1ADJ for earth leakage protection (for motor starters ≥ 30 kW) OUTGOING FEEDER UNITS (OF) ≤ 630 A Moulded Case Circuit Breaker, type Eaton NZM - Withdrawable design - Moulded Case Circuit Breaker interlocked with the door which can only be opened in OFF-position of the switch. - All withdrawable units must have a closed-door racking mechanism that allows the safe and easy procedure of rack-in and rack-out of the unit while keeping the unit door closed, while maintaining the IP rating of each respective unit. - The door must be interlocked with the “disconnect” position. No racking functions shall be possible while the door is open independent of the handle position. - The degree of protection in the test and isolation position shall be at least IP42. - Padlock facility in all appropriate positions
© Copyright 2025 Paperzz