DEESYS TOTAL PRODUCTS GUIDE - WESTERNSINO.COM

DEESYS TOTAL PRODUCTS GUIDE
디지털
전력보호
계전기기
Digital
Power
Protective
Relay
Venture Company
KEPCO Venture
Nuclear electrical
Manufacturer’
s
ISO9001
KSA9001
KSC 1303: Panel Meter
KSC1706 : C.T/P.T
Korea Fire Equipment
Inspection Corp.
Germanischer
Lloyd
TUV Product Service GMBH
JIS C 1102
Korean Agency for
Technology and Standards
Digital Multi-Power Protective Relay
Power Quality Meter
Communication for Electrical protection System
- Digital Protective Relay
Digital Type Protective Relay
Marine Type Protective Relay
Digital Earth Leakage Detector and Relay
Earth Leakage Ground Fault Relay
Low Voltage Zero Phase Sequence Current Transformer
Motor Protective Relay
Induction Type Protective Relay
Panel Board Meter
Current and Voltage Transformer
Insulator
DEESYS
TOTAL PRODUCTS GUIDE
Digital Power Protective Relay
Digital Multi-Power Protective Relay
Power Quality Meter
Communication for Electrical Protection System
- Digital Protective Relay
Digital Type Protective Relay
Marine Type Protective Relay
Digital Earth Leakage Detector and Relay
Earth Leakage Ground Fault Relay
Low Voltage Zero Phase Sequence Current Transformer
Motor Protective Relay
Induction Type Protective Relay
Panel Board Meter
Current and Voltage Transformer
Insulator
Digital Electric &Electronic system
인사말
Introduction
디이시스(주)는 전력보호계전기기 전문 생산업체로 D2K Series 라는 각종 Digital 계전기 및 집합형 누전경보기를 국내 최초로 개발 완료하여 특허출원을
완료하였습니다. 최근 전기 누전으로 인한 화재 및 인명, 재산의 피해를 사전에 예방하여 주는 소방법을 근거로 개발된 Digital 계전기 및 누전경보기 제품
은, 산업발전에 따라 전기 사용량이 증대되고 전력계통이 복잡 다양화 됨에 따라 전기로 인한 재해가 증가되고 있는 시점에 전력보호계전기기의 기능을
Up-grade하여 기기 한 대로 8회로에서 32회로까지의 다양한 모델을 선택함으로서 설치 면적을 최소화 하였으며, 기존의 기기와도 호환이 가능하여 개
보수 비용이 절감될 수 있는 획기적인 제품입니다. 기능, 설치, 운영면에서 보면, 현재 변전소의 무인화 및 원격 감시 시스템에 적용되고 있으며, 고기능
화 및 정보 전송의 간소화 등의 기술적 발전을 이룬 차세대형 배전감시 Digital 보호계전기기로서 최근의 수요, 공급의 확대로 많은 건축물의 전기사고로
인한 피해로 부터 인명, 재산을 보호하는 큰 역활을 담당하고 있습니다.
History
연혁
79.
79.
82.
86.
88
91.
92.
3
7
6
9
10
4
5
대연전자 주식회사 창립
소방용 기계기구 제조허가 취득
제조업 허가
유망 중소기업 선정
한국 전기공업 협동조합 가입
한국 전기공업 진흥회 가입
계량기 제조업 허가 취득
한국 산업기술진흥회 가입
94. 1 계전기 말레이시아 및 동남아시아 수출
4 일본 Mitsubishi(주) 부품 공급계약 체결
10 김포공장 신축 준공-본사 및 공장
96. 3 기업부설연구소 설치
97. 3 복합형 전력용 변환기 개발 (한국전기연구소)
97. 12 DIGITAL 과전류 및 지락과전류 계전기 개발
99. 7 대한전기학회 특별회원 (대한전기학회)
00. 4 상호변경 대연전자(주)→디이시스(주)
01. 1 NPTC 한학연 회원사
5 변성기 공장 신축
02. 5 일본 KAWAMURA 전기(주) 수출공급
03. 4 대한전기협회 회원 가입
04. 4 대표이사 변경 (대표이사 유병국)
07. 2 디지털 계전기 개발 출시
Awards
수상실적
86.
92.
96.
97.
98.
98.
98.
99.
00.
00.
01.
02.
9
2
5
2
3
5
9
1
5
11
10
7
유망 중소기업 선정
신기술개발표창
품질관리대상수상
우수 수출업체 표창
조세의 날 표창
수출 및 신기술 개발표창
유망 VENTURE 기업 선정
기술경쟁력 우수기업 선정
유망 전력 VENTURE기업 선정
2000년 전기공업 수출부문 수상
2001년 전기공업 수상
수출 및 신제품 개발표창
제일은행
한국전기공업협동조합
한국소방검정공사
한국전기공업협동조합
경인지방국세청장
산업자원부장관
경기지방 중소기업청
중소기업청
한국전력공사
국무총리
산업자원부장관
행정자치부장관
Certificate
인증현황
80.
93.
95.
97.
98.
98.
99.
99.
00.
01.
02.
인증서
3
3
4
6
7
9
9
1
5
6
3
누전경보기(ELD, ELR) 형식승인
KS C 1303 지시전기계기인증
ISO 9002인증
ISO 9001인증
ELD, ELR 신제품 형식승인
원자력 (KEPIC-EN) 자격인증
KS C 1706 계기용 변성기 인증
GL선급협회 PFR인증
CE 인증(디지탈 계전기)
디지털 누전경보기 형식승인
JIS C 1102 지시전기계기인증
Certification
한국소방검정공사
한국표준협회
한국품질인증원
한국생산성본부
한국소방검정공사
대한전기협회
한국표준협회
GL선급협회(독일)
TUV(독일)
한국소방검정공사
본공업규격
02. 5 EM우수품질인증
03. 11 CE 인증(디지탈 복합형계전기 EMC)
04. 3 CE 인증(디지탈 복합형계전기 안전
기술표준원
TUV(독일)
TUV(독일)
Digital Electric & Electronic system
디지털 전자화 배전반 종합보호 계전기 RS-232, 485 통신제어
Intelligent Elctronic Device[IED]
종합메터 MNET
종합보호계전기 MPRO
디지털 전력보호 계전기 (통신제어)
Digital Power protective Relay
과전압 및 부족전압 계전기 OVR & UVR
디지털 누전경보기[ELD]/RS-485 통신제어
Digital Earth Leakage Relay
누전경보기 ELD 8회로
누전경보기 ELD 16, 24, 32회로
MICOM 누전경보기, 지락계전기
MICOM Type ELD, GFR
누전경보기 ELD 5, 10회로
지락계전기 GFR 5, 10회로
누전경보기, 지락계전기
Analog Type ELR, GFR
지락계전기(매입형)GFR
지락계전기(소켓형)GFR
누전경보기(매입형)ELR
디지털 전력보호 계전기
Digital Power Protective Relay
과전류 및 지락과전류 계전기 OCR & OCGR
재폐로 계전기 Reclosing Relay
Digital Electric & Electronic system
유도형 전력보호계전기
Induction Protective Relay
과전류 계전기
OCR
부족전압 계전기
UVR
지시계기 메터
Panel Board Meter
DIN 48, 72 각형메터
Square Type
상절체형 메터
각형메터(Square Type)
광각형 메터
Wide Type
모터 보호 계전기
Motor Protective Relay
4E 모터보호계전기
3E 모터보호계전기
디지털형 전력보호 계전기
Digital Type Power Protective Relay
과전류 및 지락과전류 계전기
OCR & OCGR
과전류 계전기
OCR
과/부족 전압 계전기
OVR & UVR
지락방향 계전기
DGR(SGR)
전력용 직류 / 교류 변환기
Power transducer
단품형 변환기
Single Type Transducer
변압기 및 변류기 (저압, 고압, 특고압)
Epoxy Molded voltage & Current Transformer
영상 변류기
ZCT
저압변성기
Low Voltage CT,VT
고압변성기
High Voltage CT,VT
절연애자
(0.6kV~36kV)
Insulator
안전을 위해 반드시 지켜야할 사항
본 제품을 사용함에 있어서, 아래 사항을 반드시 지켜 주시기 바랍니다.
또한 안전상의 주의가 필요한 사항에 대해서는 해당 제품의 취급설명서를 잘 읽어 주신 후 사용하여 주십시오.
■사용환경과 사용조건에 관한 사항사항
■접속에 관한 사항
●다음과 같은 장소에서 사용하지 말아 주십시오.
●단자 접속은 다음 사항을 지켜주시기 바랍니다.
오동작 및 수명이 단축될수 있습니다.
�주위온도가 -10~60℃ 의 범위를 넘는 장소.
또한 안전을 위해 전기공사, 전기배선등의 전문기술을
가진 사람이 실행하십시오.
�일평균 온도가 35℃를 넘는 장소.
�습도가 30~70% RH의 범위를 넘는 장소.
�먼지, 부식성가스, 염분, 연기가 많은 장소.
�접속은 카다로그등의 접속그림과 같이 바르게 실행해주세요.
※부식성 가스는 아황산가스, 암모니아 가스, 유화수소가스 등 금속이나 플라
�부적절한 접속이나 공사는 제품의 파손 및 누전의 원이 됩니다.
�접속에는 전기량과 단자크기에 따라 알맞는 입착단자를 사용하
스틱등을 부식시키는 가스를 말함.
십시오.
�진동, 충격이 많은 경우.
�단자BOLT는 적절한 공구에 의한 적합한 토크로 단단히 죄어
※진동이 많은 장소에서 사용되는 경우 제품의 일부 부품이 공진이 발생되어
주세요.
소손될 우려가 있으며, 또한 오차나 기기변동이 발생할 경우가 있으므로, 방
진처리를 하거나 설치장소를 변경하시기 바랍니다.
�비, 물, 자외선, 일광이 직접 닿는 장소.
�노이즈 전파가 많은 장소, 정전기 발생이 많은 장소, 고조
파, 사이리스터회로 등의 파형왜곡이나 고조파가 많은 장소.
●다음의 설비에 사용되는 경우는 자사에 상담 하십시오.
�원자력 프랜트, 의료장치, 군사설비, 비행기, 차량.
M4나사 : 0.98~1.47N/m
주의
M5나사:1.47~1.96N/m
�단자COVER는 안전을 위해 반드시 설치해주세요
�계기용변성기와의 접속은 2차측 극성에 유의하시기 바랍니다.
�특히CT의 오접속 또는 CT 2차측의 개방은 고전압이 발생하여,
CT의 고장 및 화재의 원인이 되며, 취급자들의 감전의 위험도
있습니다.
�단자BOLT 에 윤활유 사용을 하지 마십시오.
■설치에 관한 사항
●유통과정에서 과대한 충격등이 가해져 이상 상태가 되는
■사용방법에 관한 사항
경우가 있으니, 외관등의 이상이 없는지를 확인해 주십시오.
●설치는 다음과 같은 사항을 지켜주시기 바랍니다. 또한 안
전을 위해 설치는 전문기술을 보유한 사람이 해 주십시오.
�함에 제품을 설치할 때에 무리한 힘을 가해서 끼워넣거나,
제품이 스트레스를 받지 않도록 주의하시기 바랍니다.
●정격범위내에서 사용해 주세요
정격범위와의 사용은 오동작이나 고장의 원인이 됩니다.
※상세한 것은 카다로그 및 취급설명서를 참고 하십시오
■고장시 수리 이상시 처리에 관한 사항
�또한, 볼트 및 너트를 이용하여 함에 설치할때에는 SIZE에
적합한 공구를 사용하여 단단히 죄어 주십시오.
※체결조임 토르크 M3 ; 0.48~0.98N/m
M4 : 0.98~1.47N/m
M5 : 1.47~1.96N/m
�이상음, 이상발열 또는 고장이 생길 경우 즉시 입력차단
등의 응급조치를 행한후, 가장 가가운 대리점 및 본사
A/S 부서로 연락하시기 바랍니다.
■보수 점검에 관한 사항
■ 보관에 관한 사항
●제작을 오랜기간 바르게 사용하기 위해서는 일상점검을 하십시오
�제품에 손상이 없는가?
�동작이나 지시에 이상(입력에 대응하지 않는 동작이나 지시)
이 없는가?
�설치 또는 단자대의 결선에 느슨함이 없는가?
●장시간 보관하는 경우는 다음과 같은 장소를 피해주십시오.
고장 및 명단축의 원인이 될수 있습니다.
�주의 온도가 -20~60℃의 범위를 넘는 장소.
�일평균 온도가 35℃를 넘는 장소.
�습도가 90% RH 이상으로 결로하는 장소.
�먼지, 폐식성가스, 염분, 연기가 많은 장소.
�진동, 충격이 많은 장소.
�비, 수분, 자외선, 일광이 직접 닿는 장소.
※감전을 방지하기 위해서는 반드시 정전상태에서 행해주십시오.
●COVER는 대전방지처리를 했으므로 청결유지는 다음 사항을
지켜주세요.(특히 지시전기계기)
�덮개표면의 더러운 것은 부드러운 헝겊으로
가볍게 두들겨 제거하십시오. 또, 심하게
더러울 경우는 교환을 하는 것이 좋습니다.
●관리는 전원을 끄고, 배선을 빼고, 비닐 봉투나 상자등에 넣
어서 보관하시기 바랍니다.
■ 폐기에 관한 사항
●일반 산업용 폐기물로 처리해 주세요.
�화학걸레등을 오랜기간 접촉시키거나
벤젠, 신나 등에 부식되지 않게 해주십
시오. 변형, 변색하거나 장식이 벗겨지는
등의 원인이 됩니다.
�지시전기계기는 정전기에 의한 지침이 불안정한
동작을 하는 경우가 있습니다. 그 경우는 시판되
는 대전 방지제를 COVER에 도포하여 주십시오.
●절연시험에서 제품에 파손되는 경우가 있으므로 다음 사항을
지켜주시기 바랍니다.
�전압 시험 시의 인가 전압은 기종및 단자에 따라 다르므로
카다로그에 기재된 전압을 지켜주십시오.
�인가개소에 주의하십시오. VT입력 단자간의 동일전위에 인
가하면 고장의 원인이 됩니다.
●사용할 때에는 제품이 정상동작을 하는가를 확인하십시오.
�제품의 수명은 사용상태에 따라 틀리지만 대략 10년을 추정
하고 있습니다.
Contents
Digital Multi-Power Protective Relay
Motor Protective Relay
■D2K-MPRO Digital Multi-Power Protective Relay
2
■Motor Protective Relay
■3E, 4E Motor Protective Relay
14
Power Transducer
Power Quality Meter
■D2K-MNET Quality Power Meter
Communication for Electrical Protection
System- Digital Protective Relay
■3 Phase Digital Over Current and Earth Fault Relay
[50/51, 50N/51N]
20
Digital Protective Relay
■Reclosing Relay [79]
32
Digital Type Protective Relay
■Digital Over Current and Earth Fault Relay
[50/51x3, 50/51N]
■Digital Over and Under Voltage Relay [59/27]3∅
■Multi Function Over Current and Earth Fault Relay
[50/51x3, 50/51N]
■Over Current Relay [50/51x2] [50/51x3]
■Ground Over Current Relay(Earth Fault Relay)
[50/51N]
■Multi Function Over and Under Voltage Relay [59/27]
■Over and Under Voltage Relay [59/27]1∅
■Ground Over Voltage Relay [64]
■Directional Ground Relay [67]
■High Voltage Zero-Phase Current Transformer
[ZCT]HZR-Series
■Static Phase Open Relay [47]
■High Voltage Ground Relay [51G]
36
42
50
57
63
67
73
77
81
84
85
88
Marine Type Protective Relay
■선박용
■선박용
■선박용
■선박용
■선박용
3 Phase Voltage and Frequency Relay
3 Phase Phase Fail Relay
3 Phase Phase Sequence Indicator Relay
Single or 3Phase Synchroscope
Dimension
96
97
98
99
100
Digital Earth Leakage Detactor and Relay
■D2K-ED Series Earth Leakage Detector and Relay
102
Earth Leakage Ground Fault Relay
■Multi Function Earth Leakage Detector and Fire Alarm
■Earth Leakage Fire Alarm and Relay [ELR]
1C, 5C, 10C
■Earth Leakage Relay [ELR] 1C
■Multi Function Ground Relay [GFR] 5C, 10C
■Aux Relay Board [Isolation] 5C, 10C
■Ground Fault Relay 1C
112
122
124
125
132
133
Low Voltage Zero Phase Sequence
Current Transformer
■Zero Phase Sequence Current Transformer
[ZR, ZS, ZB, SZR-Series]
■Zero Phase Sequence Current Transformer
[ZB-Series]
■Cable & Busbar Through Type
[ZR, ZS, ZB, SZR-Series]
■Busbar Mold Type Zero Phase Sequence Current
Transformer [3∅ 3W]
■Busbar Mold Type Zero Phase Sequence Current
Transformer [3∅ 4W]
■How to Installation and Inspection
138
140
141
142
143
144
■Power Transducer
■Voltage Transducer
■Current Transducer
■Watt Transducer
■Var Transducer
■Watt/Watt Hour Transducer
■Var/Var Hour Transducer
■Power Factor/Phase Angle Transducer
■Frequency Transducer
■Analog to Pulse Transducer
■Zero Sequence Voltage Transducer(V0)
■DC mV/DC V Transduce
■Isolator/Temperature Transducer
146
151
162
163
165
167
171
173
175
177
179
181
182
183
184
Induction Type Protective Relay
■Induction Protective Relay
■Induction Type Over Current Relay [OCR] 50/51
■Induction Type Ground Over Current Relay
[50N/51N]
■Induction Type Over, Under Voltage Relay
[59] [27] [64]
■Induction Type Directional(Selective) Ground Relay
[67]
■How to Drawout
■Dimension
186
188
193
195
198
200
201
Panel Board Meter
■Panel Board Meter
■Panel Board Meter [DIN Type]
■Panel Board Amper Meter
■Panel Board Volt Meter
■Panel Board Watt Meter
■Panel Board Var Meter
■Panel Board Factor Meter [cosφ
]
■Panel Board Frequency Meter [Vo]
■Panel Board Maximum Demand Meter [Vo]
■Panel Board Maximum Demand Meter [Ao]
■Panel Board Meter Dimension
■3상 절환형 각형 지시전기계기 [교류전압전류계]
■Digital Panel Board Meter
204
206
207
208
209
211
214
216
217
218
219
221
223
Current and Voltage Transformer
■Round Type Current Transformer [1.15kV]
■Winding Type Current Transformer [1.15kV]
■Square Type Current Transformer [1.15kV]
Busbar 취부용
■Square Type Current Transformer [1.15kV]
Panel 취부용
■Voltage Type Transformer [0.72kV]
■Busbar Type Current Transformer [3.45-7.2kV]
■Square Window Type Current Transformer
[3.45-7.2kV]
■Voltaget Transformer [3.45-7.2kV]
■Ground Type Voltage Transformer [3.45-7.2kV]
■Round Type Zero Phase Current Transformer
[3.45-7.2kV]
■Epoxy Resin Insulator [0.6kV]
■Epoxy Resin Insulator [7.2, 12kV]
■Epoxy Resin Insulator [24kV]
■Epoxy Resin Insulator [24, 36kV]
■Shunt [Voltage Drop 50mV]
■Current Limit Resister [CLR]
230
232
233
234
235
236
237
238
239
240
241
243
246
247
248
249
한국전기연구원 개발시험합격품
D2K-MPRO
Digital Multi-Power
Protective Relay
■ Intelligent Electronic Device
[OCR 50/51, OCGR(50/51N), UVR(21), OVR(59)
OVGR(64G), SGR(67G), DOCR/DOCGR(67N)]
D2K-MPRO
전자화 배전반 종합 보호 계전기
D2K-MPRO Digital Multi-Power Protective Relay
MODEL D2K-MPRO
특징
Features
MPRO는 고신뢰성의 디지털 보호계전기능, 정밀한 계측기능 및 차단
기 제어기능을 수행하고, 중앙감시시스템과의 다양한 인터페이스를 통
한 원방감시제어가 가능하며 고기능의 전자식 배전반 Solution을 가능
하게 하는 IED(Intelligent Electronic Device)입니다. 또한 직접접지
또는 비접지 계통에서도 적용되며 중소용량의 발전소가 연계된 계통에
서 방향성(Directional OCR) 선택/동작시도 적용할 수 있습니다.
MPRO is a IED(Inteligent Electronic Device) that provides a
solution for high reliable multi purpose digital protective relay,
precise measurement and circuit breaker controls, remote
controls interfacing with a central detective system, and a high
performance distributing board. This works with or without
grounding, or directional OCR in a small power plant.
Specificatain
50/60(Hz)
사용주파수
정격 전류
CT
5(A)
ZCT(1차/2차)
200/1.5(mA)
PT
100(V)
GPT
190(V)
CB 제어용
30(A) 250VAC, 0.5sec
신호용
5(A) 250VAC
정격 전압
정
격
사용온도및 습도
출력접점
상 태입력
AC/DC 110~250(V)
2.5VA 이하
제어전원
AC/DC 86~250(V)
사용 온도
습
사용온도
-20~60℃
보관온도
-25~70℃
일평균30~80%
도
절연 저항
IEC60255-5규격 적용
상용주파 내전압
뇌 임펄스 내전압
IEC60255-6규격 적용
과부하 내량
1MHz Burst
내환경 성능
Electrostatic Discharge
EMC
Fast Transient
IEC60255-22, IEC61000-4
규격 적용
Sureg
RF Interface
2
DEESYS TOTAL PRODUCTS GUIDE
EMI
IEC60255-22-3규격 적용
진동 및 충격
EC60255-22-3규격 적용
D2K-MPRO Digital Multi-Power Protective Relay
특징
Features
● 다기능 디지털보호 계전기능
OCR, DOCR(Option), OCGR, UVR, OVR, OVGR,
DOCGR(Option), SGR
● Multi purpose digital protective relay
OCR, DO(Option), OCGR, UVR,
DOCGR(Option), SGR
● 정밀급(1.0급)의 각종 전기량 계측기능
- 전류, 전압, 유 . 무효전력, 유 . 무효전력량, 역률 및 주파수
- 각 계측 데이터별 Pick Demand
- 시간대별 각종 Demand의 3개월간 데이터를 저장 관리하는
Load Profile 기능
● Precision voltammeter:
- current, voltage, effective, reactive power, power factor,
and frequency
- pick demand on each measured data
- load profile function that store data in time for 3 months
● 다양한 표준 통신 Protocol 수용
(별도의 Protocol 변환기 불필요) 주문시 선택
- DNP 3.0
- ModBus
- IEC 60870-5
- LonWorks
- BACnet
● compatible with various standard communication Protocol
● 고장정보 기록기능
- 최근 32개의 고장정보 저장. 관리기능
- 최근 4개의 고장파형 저장. 관리기능
● Store system error
- store 32 errors from the most recent data
- store 4 frequency errors from the most recent data
● 사용자 인터페이스
터미널 포트를 통하여 각종 설정 및 계측데이터,
보호 특성커브, 고장파형 등을 확인
● User interface
- Able to check the setting, measured data, protective
curve, and frequency error by communication port.
● 다양한 제어전원
Free Voltage : AC/DC86~250[V]
Option : DC24/48[V]
● Various control
- free voltage: AC/DC 86~250V
- option: DC 24/48 V
● 전원 상실 시
- Time-Keeping 기능
- Event 기록 및 로그 정보유지
● Power off
- save time function
- save log information and event
● 구조
- 인출형 [Drow out type]
● Type
- draw out
OVR,
OVGR,
(protocol converters are optional)
- DNP 3.0
- ModBus
- IEC60870-5
- LonWorks
- BACnet
Front plate
Display Panel
- High quality LED
- 20 characters with 4 lines
Relay Operation
- Display operation relay LED
- Pick up status LED
- Reset button
Operation status
- Run
- System fail
System reset button
Local/Remote mode
- LED or button
User interface(Terminal Port)
- RS-232C
- Optical port(option)
Communication status
- display communication
status with mater (refer
to the back)
- Tx(green)/Rx(red)
User function key
- measured data display
- relay setting
- communication parameter setting
- event setting
- addition function setting
Power On/Off button
- On(red)
- Off(green)
DEESYS TOTAL PRODUCTS GUIDE
3
D2K-MPRO Digital Multi-Power Protective Relay
Operating Characteristic Curve
한시 동작 특성(Time delay characteristics IEC-60255)
� I -1K �+ C ×
T=
a
tp
10
a
K
C
반한시 Normal Inverse(NI)
0.02
0.14
0
강반한시 Very Inverse(VI)
1
13.5
0
초반한시E xtreme Inverse(EI)
2
80
0
I: 과전류에 대한 배율(%)
tp: 동작시간(Lever)
정한시 동작 특성 Definite time operation
T = tp (0.1~10sec)
Specificatain
계전기능
동작구분
순시
동착치
동작시간
설정범위
설정단위(Step)
설정범위(Lever)
5~80A, Block
�
1 A�
40ms 이하
설정단위(Step)
OCR
(50/51)
특성
반한시, 강반한시
한시
0.2~16A. OFF
0.1
�A�
0.2~50.0
0.2
초반한시
*정한시
순시
3~40A. OFF
0.5
�A�
40ms 이하
한시
0.2~5A. OFF
0.1
�A�
0.1~50.0
순시
반한시, 강반한시
OCGR
(50/51N)
0.2
초반한시
*정한시
순시
5~80A. OFF
�
1 A�
40ms 이하
한시
0.2~16A. OFF
0.1
�A�
0.2~50.0
순시
반한시, 강반한시
DOCR
동작위상각
한시
0~90(1。
단위 설정)
±60~±90(1。
단위 설정)
(0.1~1)×110
�V�
1.0
�%�
0.2~50.0
0.2
반한시, 정한시
OVR(59)
한시
(1.1~1.4)×110
�V�
1.0
�%�
0.2~50.0
0.2
반한시, 정한시
OVGR(64)
한시
(0.05~0.4)×190
�V�
1.0
�%�
0.2~50.0
0.2
반한시, 정한시
전류
1~10
�mA�
0.1
�mA�
SGR
전압
(0.05~0.4)×190
�V�
1.0
�%�
0.2~50.0
0.2
정한시
(67G)
기준위상각
0~90(1。
단위 설정)
동작위상각
±60~90(1。
단위 설정)
0.2
초반한시 *정한시
순시
3~40A. OFF
DOCGR
한시
(67N)
기준위상각
0~90(1。
단위 설정)
0.2~5A. OFF
동작위상각
±60~90(1。
단위 설정)
*정한시 설정은 공통으로 0.1sec~10sec(0.2sec step)임
4
초반한시
*정한시
기준위상각
UVR(27)
0.2
DEESYS TOTAL PRODUCTS GUIDE
0.5
�A�
0.1
�A�
40ms 이하
0.1~50.0
반한시, 강반한시
D2K-MPRO Digital Multi-Power Protective Relay
Characteristic Curves
반한시 보호특성(Normal Inverse)
강반한시 보호특성(Very Inverse))
초반한시 보호특성(Extremely Inverse)
정한시 보호특성(Definite Time)
DEESYS TOTAL PRODUCTS GUIDE
5
D2K-MPRO Digital Multi-Power Protective Relay
Control
상태입력
Optional Analog입력
제어출력
Event 관리
입력구성
Photo-Isolated Binary Input
Remote Fault Reset
1 Port
CB Remote ON/OFF
2 Port
Programmable Contact
3 Port (DI)
입력회로
AC220V/DC250V,AC110V/DC125V
�4~20[mA] 아날로그 입력
�전기적 절연으로 외부 Surge에 안전한 구조
�온도 및 가스압력 등의 감시를 위한 별도의 RTU불필요
출력단자
용량
비고
TRIP(1Port)
30A/250VAC(0.5sec)
*Programmable
CB ON/OFF(2Port)
30A/250VAC(0.5sec)
Contact Output
경보용(6Port)
5A/250VAC
(설정에 따라 재구성 가능)
�1ms SOE처리
�전원 상실시에도 데이터 백업유지
�차단기 ON/OFF(현장/원방 구분)제어
�설정치 변경(현장/원방 구분)
�현장/원방 선택변경
�IED Restart
(Power On/Watchdog Restart구분)
�자기진단에 의한 시스템 Failure
�Binary Input Change
�사고발생 및 Fault Reset
Communication
다양한 표준 Protocol을 탑재, 유연한 감시 시스템 구성 가능
(감시반 구성을 위한 별도의 Protocol 변환 장치 불필요)
통신 Port
전력 감시시스템 구성예
∙Port 1 : RS-232C
∙Port 2 : Isolated RS-485
통신 Protocol
∙DNP3.0
∙ModBus
∙IEC60870-5
∙LonWorks
∙BACnet
- 통신채널당 최대 64대의 IED 접속가능
- 통신거리 최대 1.2km(RS-485 구성시)
6
DEESYS TOTAL PRODUCTS GUIDE
Eather-net (TCP/IP)
D2K-MPRO Digital Multi-Power Protective Relay
Metering
계측사양
표 시
오 차
3상 전류(A)
0~10,000(A)
±0.5%
3상전압(V)
0~200,000(V)
±0.5%
영상 전압(V0)
0~10,000(A)
±1.0%
영상 전류(I0)
0~200,000(V)
±1.0%
유효 전력(WATT)
0~9,999(MW)
±0.5%
무효 전력(var)
0~9,999(Mvar)
±0.5%
유효 전력량(W/H)
0~999,999(MWH
±1.0%
무효 전력량(var/H)
0~999,999(MvarH)
±1.0%
역률(P.F)
Lead/Lag 0~100(%)
±0.1%
주파수(Hz)
45.0~65.0(Hz)
±0.01Hz
비 고
선간 전압 및 상전압
Load Profile
항목
Pick Demand
관리 전기량
전류, 전압
기록용량
월간 Pick 발생 시각 및 Pick 값
유효전력, 무효전력
유효전력량, 무효전력량
역률
주파수
시간대별 Demand
최근 3개월 Data
유효전력, 무효전력
유효전력량, 무효전력량
역률
주파수
Fault Memory
운전정보기록
∙IED 운전관련 종합이력정보 저장 . 관리
∙실시간 SOE처리 기능 (1ms 해상도)
∙Event 정보 Back Up (최대 128개)
∙Fault 정보(최대 128개)
항목
고장 정보
관리데이터
고장시 3상 전류, 전압 및 영상전압의 크기 및 위상각
기록용량
최근 128개 고장 데이터
고장 발생 시각
고장 상 표시
동작 계전기 및 형태 표시
총 고장 횟수
고장 파형 데이터
고장 발생 시각
최근 고장 파형 4회
각 상전류, 전압 파형
(128Cycle 샘플 데이터/1회)
영상전류, 영상전압 파형
DEESYS TOTAL PRODUCTS GUIDE
7
D2K-MPRO Digital Multi-Power Protective Relay
Menu Specification
Front Panel에는 LCD와 LED 및 Function Key에 의해고장 상태 표시, 설정치 변경 및
표시, IED 동작이상 및 통신상태, 각종 계측량 Fault Reset등을 수행 할 수 있습니다.
또한 별도의 터미널 포트를 구비하여 편리한 User Interface 기능을 수행할 수 있으며
보호 특성 커브나 고장 파형을 확인 할 수 있으며 모든 Data는 PC에 저장하여 사후
분석할 수 있습니다.
표준 RS-232C 사용
통신속도 : 9,600 - 38,400bps 설정가능
Terminal Port를 이용한 User용 Local Interface구성
● 계측치 / DI 상태표시
● 차단기 상태표시
● Polling주기 조절에 의한
자동 갱신기능
● 에러 및 통신상황 표시
● 통신 Transaction View
8
DEESYS TOTAL PRODUCTS GUIDE
D2K-MPRO Digital Multi-Power Protective Relay
●
●
●
●
설정
입력
동작
동작
계전기 동작 특성 확인
신호에 따른 동작시간 계산확인
시간 배수 변경
특성 변경
● 계전요소별 설정값 표시
● 설정치 자동 갱신
● 설정치 변경 화면 활성
● 계전요소별 설정값 변경 기능
● 기본 설정값 복원 기능
● 설정 최대 및 최소값 준수
DEESYS TOTAL PRODUCTS GUIDE
9
D2K-MPRO Digital Multi-Power Protective Relay
Menu Specification
● 최근 고장의 상세 정보 표시
● 실시간 자동 갱신 기능
● 고장파형 선택
● 파형 읽기/삭제
● 고장파형 파일 저장 기능
●
●
●
●
●
●
●
10
고장파형 분석
고장정보 표시
영역별 탐색/확대 기능
파형별 컬러 지정
파형 복합 기능
채널 선택 기능
2개 이상의 파형 비교 기능
DEESYS TOTAL PRODUCTS GUIDE
D2K-MPRO Digital Multi-Power Protective Relay
Wiring
EXternal Wiring(3P4W)
EXternal Wiring(3P3W)
● UVR ACTIVE로 설정할 경우 P.T 전압이 없으면 TRIP접점이 항상 출력되고 있습니다.
● UVR이 동작하고 있으면 CB제어가 안됩니다.
DEESYS TOTAL PRODUCTS GUIDE
11
D2K-MPRO Digital Multi-Power Protective Relay
Dimension
Front View
Side View
Cutting View
Rear View
12
DEESYS TOTAL PRODUCTS GUIDE
한국전기연구원 개발시험합격품
D2K-MNET
Power Quality Meter
■D2K-MNET Power Quality Meter
D2K-MNET
원격 감시제어용 종합메터
D2K-MNET Power Quality Meter
Introduction
D2K MNET
D2K MNET은 전형적인 Power Meter를 뛰어넘어 혁신적으로 디자인 되었으며, 컨셉화 되어졌습니다. 또한 D2K MNET은 작아지고, 전자적으로
진보했으며, 프로그램이 가능한 종합 측정 장비입니다. D2K MNETⅢ는 미래의 전기적 측정방법의 여러가지 요구에 대한 해답이 될 것입니다.
D2K MNET의 Concept은 몇가지 아래와 같은 원칙을 기본으로 디자인 되었습니다.
Environmental Impact & Cost Saving
D2K MNET은 많은 아날로그 혹은 디지털 장비를 대체할 수 있고, 그에 필요한 배선 및 컨트롤스위치를 줄임으로서 많은 비용을 절감 할 수 있으
며, 컨트롤 판넬외 전면부를 간소화 시킬수 있습니다.
Increase Productivity &Efficency
D2K MNET은 설치시 발생하는 많은 케이블과 작업시간을 대폭적으로 줄일 수 있으며, 1p2w/1p3w/3p3w/3p4w 결선을 사용할 수 있습니다.
Improved Tecnical Superiority and Reliablity
D2K MNET은 기존 장비보다 훨씬 앞선 기술적 능력을 갖고 있습니다.(Overload capabilities, accuracy levels, long term stability, readout
dependability, etc) D2K MNET은 전면 표시창의 VFD(Vacuum Fluorescent Display) 사용으로 기존의 녹색 표시장치에서 발생되었던 원거리
에서 읽기 어려웠던 문제점을 극복하였으며, 안개와 같은 악조건 속에서도 표시창을 통하여 30가지가 넘는 정보를 순차적으로 자동 스크롤 혹은
수동 스크롤 기능을 통하여 읽어들일 수 있습니다. 또한, 범용 Modbus� protocol의 RS232/485 통신 포트를 내장하여 PC를 통해 각종 정보를
읽어들일 수 있으며 장치를 관리할 수 있습니다.
Parameters Conversion
Microprocessor가 내장된 D2K MNET은 modicon사의 Modbus� 시스텀을 기본으로 제공합니다. 이는 제품의 정보 표시창으로부터 읽어들일
수 있는 30가지 이상의 정보보다 더 많은 90가지 이상의 정보를 PC를 통하여 감시 제어 할 수 있는 기능을 제공합니다.
Features
● 90가지 이상의 전력 및 에너지 정보표시
● 공장과 건물의 자동화
● Modbus protocol 탑재
● 최대 600V 사용가능
● True RMS 변화가능
● 순시 최대값, 최소값 표시기능
● 선명하고 긴 수명의 VFD채용
● RTC 내장(Real Time Clock)
● P.T / C.T 비율 설정가능
■
■
■
■
■
■
■
■
■
● Factory & Building Automation (FA & BA)
D2K MNET은 AC Switch-gear 혹은 공장 전력분배 시스템에 광
범위하고 쉽게 적용이 가능하여 공장과 건물의 자동화로의 발전을
도와줍니다.
● Memory for all setup and energy data
전원공급이 중단되어도 D2K MNET은 측정된 Wall-Hopur, 최대
수요전력, 날짜와 시간, PT/CT비, 시스템설정값, 표시설정값, 통신
관련 데이터등의 모든 값을 메모리에 저장하여 안전하게 보관합니
다.
● PLC Modbus Compatible
Modbus communications protocol 은 D2K MNET과
Programmable Logic Controller(PLC) 혹은 다른 thirdparty 의
Modbus 호환 모니터링 프로그램, 컨트롤 시스템간의 데이터를 효
율적으로 변환합니다. 또한 IPC-based centralized master
display software 를 쉽게 채용할 수 있는 모니터링 시스템을 채용
하였습니다.
● Built-in Real Time Clock
D2K MNET은 실시간 타이머(Real Time Clock)를 내장하여 최대/
최소 에너지값을 기록할 수 있으며, 수요전력 Sampling(Display)
Time을 설정 할 수 있습니다. (15/30Minute)
14
DEESYS TOTAL PRODUCTS GUIDE
0.15% 이내의 오차
최대 수요전력의 통제
모든 셋팅값과 데이터의 저장
광범위한 Selftest
Low input burden 0.1VA (5A /120V)
폭넓은 제어전원 사용 (80~260V AC/DC)
간략화된 제품의 구성
DIN & ANSI 에 적합한 Cutout
2kV RMS input / output / power 의 절연
● Field Programmability
D2K MNET은 CT/PT비, Modbus @ address, 통신속도, parity,
display등을 전면의 버튼을 이용하거나 통신포트를 이용하여 PC에
서 현장의 조건에 맞도록 설정이 가능합니다.
● Accuracy up to 0.15%
더욱 발전된 conversion,“ sampling 그리고 software 보상기술
로 전압과 전류는 0.15% 이하, 전력은 0.25%이하의 오차율을 실현
하였습니다. PC를 통하여 감시 제어할 수 있는 기능을 제공합니다.
D2K-MNET Power Quality Meter
Model & Ordering Number
Model : D2K MNET
-5.0A
DMM
- H - 1 - 1
Current Input
1.0A
5.0A
Wiring
1 : 1P2W
2 : 1P3W
3 : 3P3W
4: 3P4W
Power
H: AC 80-260V, DC 80-330V
L: DC 20-60V
Communcation Port
1: RS-485
2: RS-232
Specification
Programmable measurements / Accuracy / Display readouts
Param.
Digits
Accuracy
Phase1
Phase2
Phase3
Vx3
5 (or 4)
9.9.9.9.9. V / KV
Display(maximum)
0.15% fs
V1
V2
V3
Ax3
5 (or 4)
9.9.9.9.9. A / KA
0.15% fs
A1
A2
A3
Watts
5 (or 4)
9.9.9.9.9. W / KW / MW / GW
0.25% fs
W1
W2
W3
Vars
5 (or 4)
9.9.9.9.9. Var / KVar / MVar / GVar
0.25% fs
Var1
Var2
Var3
Var
VA
5 (or 4)
9.9.9.9.9. VA / KVA / MVA / GVA
0.25% fs
VA1
VA2
VA3
VAE
PF
4
0.9999
0.25% fs
PF1
PF2
PF3
WH
8
9.9.9.9.9.9.9.9.9. WH / KWH /MWH
0.8% rd
WH
VarH
VarH
8
9.9.9.9.9.9.9.9.9. VarH / KVarH / MVarH
1% rd
IO
5 (or 4)
9.9.9.9.9. A / KA
0.5% fs
Hz
5 (or 4)
70.000
0.03% rd
● Accuracy : Corresponding to each auto-range scale
● VL1 / VL2 / VL3 : Line to line voltage
VP1 / VP2 / VP3 : Line to neutral voltage
● PF1 / PF2 / PF3 : Related conversion elements
● IO (neutral current, only for 3 phase 4 wires)
Total
Average
VE
AE
W
PF
● Accuracy performance range for WH / VarH / PF
Cos Θ : 1-0.5 for WH / PF
Sin Θ : 1-0.5 for VarH
Voltage � 75V, Current � 0.5A
● Phase rotation
SEQ POST : positive sequence
SEQ NEG : negative sequence
DEESYS TOTAL PRODUCTS GUIDE
15
D2K-MNET Power Quality Meter
input
● Range
Voltage : 10 - 600V
Current : suitable for CT secondary rating(optional)
Maximum 6A for 5A rating
Maximum 1.2A for 1A rating
Frequency 40 -70 Hz
● Burden
Voltage < 0.4VA at 600V
< 0.04VA at 150V
Current < 0.1VA at 5A
Overload rating
Current
2 X rated continuous
10 X rated 30 seconds
25 X rated 2 seconds
50 X rated 1 sceonds
voltage
750V continuous
1000V 10 seconds
1200V 3 seconds
Measured system
● Suitable for 3 phase 4 wires / 3 phase 3 wires/ single
phase 2 & 3 wires / 3 phase balance
● Select by input wiring & software configuration
Programmability
● Software accessible / password lock
● System selection :
3 phase 4 wires/ 3 phase 3 wires /
1 phase 2 & 3 wires / 3 phase balance
● PT: 1 - 5000.0 ; CT : 1 - 2000.0
● Readout display control
5 or 4 digit / auto scan or manual selection / scanning
time
● Maximum demand 1 - 60 min
● Maximum and minimum of instant measurement
● Communication
baud rate 1200/ 2400/ 4800/ 9600/ 19200
parity (even or odd) / None
Address setting 1 -254
● Calibration
software with password lock
● Memory
all of energy date and status setting
16
DEESYS TOTAL PRODUCTS GUIDE
Communication port
RS485 ( standard) : RS232 (option)
Moobus RTUprotocol
Display
VFD / 0.28”/ blue color, 3 rows of 9 alphanumerics
RTC
Maximun deviation 5 sec in 24 hours
Time for year / month / date / hour/ minute / sec
Dielectric strength
IEC 255-5
2KV AC rms 1 minute between input / output /power
Impulse and surge test
ANSI / IEEE C37.90.1-1989(3KV) SWC test
IEC 255-22-1 class III SWC test
IEC 255-22-4 class Ⅳ (IEC 801-4) SWC test
IEC 255-5 1.2 50us (5KV) impulse test
Stability
Temperature range - 24 to +55 ?C
Maximum 100 ppm / ?C
Long term stability 0.15% drift maximum per year
Operation condition
Temperature range - 25 to + 60 ?C,
RH 20 - 95% non-condensed
Power supply
AC 80-260V, 40-70 Hz, DC 80 - 330V
DC 20-60v (option)
Dissipation maximum 12VA for AC and 6 watts for DC
D2K-MNET Power Quality Meter
Applications
The D2K-MNET PC TOOL a utility program that can help user to connect to“D2K-MNET Power Meter”rapidly. The D2K-MNET PC
TOOL, provided with every D2K-MNET meter , allows easy access to all meter setup information and actual values via a personal
computer running Windows 95/98 and one of the PC’s communication ports-COM1 or COM2. The user can:
●
●
●
●
Program/ Modity setup information
Load/save setup information files from/to disk
Read actual“Basic”value (current/voltage/power/frequency)
Read actual“statistics”value (maximum/minimum/time of maximum/time of minimum)
The “D2K-MNET PC TOOL”can be used“stand-alone”
, without a D2K-MNET meter, to create or edit D2K-MNET meter setup
information files.
SCADA
System
RTU
DCS System
HC 6000
PC Tool
PLC
Test set
RS-485 ModBus Communication Bus (RTU Mode)
Communication Wiring
Computer
RS485
D- D+
Up to 32 devices,
maximum 4000 feet
Ground shield at SCADA/
PLC/Computer only
(one end grounding)
Shield
Twisted pair Shielded cable
ZT(*)
R = 120 ohm
C C = 1000pF
R
Com D- D+
Com D- D+
Com D- D+
METER
METER
METER
DEESYS TOTAL PRODUCTS GUIDE
17
D2K-MNET Power Quality Meter
Wiring
3 Phase 3 Wires Unbalance Load
AS AL BS
BL
CS CL
PA PB
1 Phase 2 Wires / 3 Phase 4 Wire balance Load
PC PN
FG
Power
AS AL
BS
BL
CS CL
PA PB
PC PN
FG
_
+~ -
_
+~ -
L1
L1
L2
L2
L3
Source
Load
Source
BL
CS CL
PA PB
PC PN
Load
3 Phase 3 Wires Unbalance Load (3CT)
3 Phase 4 Wires Unbalance Load
AS AL BS
FG
Power
AS AL
BS
BL
CS CL
PA PB
PC PN
FG
_
+~ L1
L2
L3
N
BL
CS CL
PA PB
PC PN
Source
Load
�Setting system : 3 phase 4 wires
Load
3 Phase 3 Wires Unbalance Load (3CT)
3 Phase 3 Wires Balance Load (1)
AS AL BS
FG
AS AL
Power
BS
BL
CS CL
PA PB
PC PN
FG
L1
L2
L3
L1
L2
Source
Source
Load
AS AL BS
BL
CS CL
PA PB
PC PN
FG
Power
_
+~ -
18
Standard
RS485
L1
L2
Load
Source
DEESYS TOTAL PRODUCTS GUIDE
Load
Communication Port
3 Phase 3 Wires Unbalance Load
L3
Power
_
+~ -
_
+~ -
L3
Power
_
+~ L1
L2
L3
Source
Power
Option
D+ D- Com
X Y Z
RS232
RxD TxD SG
X Y Z
한국전기연구원 개발시험합격품
Communication for
Electrical Protection system
-Digital Protective Relay
■3 Phase Digital Over Current and Earth Fault Relay [50/51, 50N/51N]
D2K-OG50
과전류 & 지락과전류계전기
D2K-OG50 Series 3-Phase Over Current and Earth Relay[50/51,50/51N]
MODEL D2K-MOG50
System and Protection
디지털 과전류 계전기는 32bit DSP(Digital Signal Processor)를 내장
하고 1Cycle을 24Sampling 하며 A/D Converter로 변환, Sampling
값을 연산 처리한 고속 Digital Relay 입니다.
Apply
이 계전기는 154kV 또는 22.9kV 직접 접지 또는 저항 접지 계통에 사
용 할 수 있으며, 다기능 다특성을 내장하고 있어 설계 초기에 계전기
선택이 용이합니다. 특히 장강반한시(LT-VI)특성을 추가하여 강반한시
특성의 상위 Lever를 확대했으며, 동작특성 Lever도 정정가능 범위를
세분화 확대하였습니다.
Features
Display Mode
각 상의 현재 상태전류를 기준으로 하여 A, B, C, N상의 전류상태
를 실시간으로 LCD(Liquid Cristal Display)표시창에 표시합니다.
Keypad and Communication
모든 정정치 및 Data는 전면부의 Keypad 또는 RS 232 Port로 PC
와 연결하여 Control 할수 있으며, 후면의 RS485 Port를 이용하여
중앙 Control system에서도 릴레이의 모든 기능을 점검 할 수 있
습니다.
Fault Memory [Memory view]
사고 Data의 횟수는 10회까지 Memory한다.
∙Fault current
∙Fault time
∙Fault phase
∙Fault date
∙Fault type
20
DEESYS TOTAL PRODUCTS GUIDE
Monitoring and Protocol
사고파형을 저장함으로서 Event Monitoring이 실시간 가능합니다.
Digital Relay는 Setting Range가 광범위하여 어떠한 상황에서도
정정이 가능하고, 자동화 설비를 위하여 DNP3.0 또는 호환 및 신
뢰성이 높은 Modbus 프로토콜을 적용 하였으며 수용가 요구시 제
공됩니다. 이 계전기는 수용가의 목적에 따라 기능 및 정정 범위를
변경하여 공급 할 수도 있습니다.
Fault Event Monitoring
Fault Event 파형을 72Cycle까지 저장 할 수 있어 사고 분석을 용
이하게 하고 특히 무인화 시스템에 적용됩니다.
D2K-OG50 Series 3-Phase Over Current and Earth Relay[50/51,50/51N]
Typical substation architecture
Eather-net (TCP/IP)
Communication for Specification
통신사양
통신속도(Comm Speed) : 19,200bps
통신거리(Comm Length) : 1.2km
통신방식(Comm Port) : RS232/485
최대노드수(Max. node) : 64Set
Read
Write
�Current display(pr.se)
�Setting position
�Fault current(se)
�Fault time
�Fault phase
�System state check
�Date and time
�Current set
�Time Lever set
�CT ratio(pri/sed)set
�Frequency set
�Operatung curve set
�Communication set
DEESYS TOTAL PRODUCTS GUIDE
21
D2K-OG50 Series 3-Phase Over Current and Earth Relay[50/51,50/51N]
Specification
Model ▶D2K-OG50
Part Name
Model
Standard code
Element
Aux. power
Rating
OCEF
Three Phase - Over Current and Earth Fault Relay
D2K-OG50
IEC 255, KEMC 1120, and KEPCO
Overcurrent (50/51) 3Phase, Earth Fault(50N/51N)
AC 110/120V and DC 110/125V ±30%, 9W(Non oper) 16W(Oper)
AC 5A, 50/60㎐
Burden OC/EF 0.3VA
Overcurrent : 0.2~15A(0.1A step)
OC
Instantaneous : 5~80A (1A step)
Time lever : 0.1~15(0.1 step)
Setting range
Inst Time
Overcurrent : 0.1~5A(0.1A step)
EF
Instantaneous : 3~40A (1A step)
Time lever : 0.1~15(0.1 step)
Time curve
장강반한시(LT-VI), 반한시(N-IN), 강반한시(V-IN), 초반한시(E-IN) IEC std.
반한시(NIES), 강반한시(VIES) KEPCO std.
Resetting value
Set of > 95%
Reset time
50ms±25ms
Degree protection
IP52
Short current
80 In
Communication
Key-pad
RS232(Front view), RS485(Reare view)
Mode, ESC, Enter, Direction Key(�,�,�,�)
RUN(Green) : C.P.U Error 동작상태 감시 및 전원감시
COMM(Yellow) : 깜박일때 신호 출력 중
Indicator
Pick-up(Red) : Pick-up 과부하 동작시 점등
ERR(Red) : 내부회로 및 소자 불량시 점등
R.S.T.N : 동작 상표시 INST : 단락상태 표시등
Fault Memory
Reset
Temperature
Mounting
Contact capacity
10회 Memory 기능 및 사고선로별 회로표시 (선입선출방법,“1”
이 최근 사고를 뜻함
Memory event recording time 1.2sec
Auto Reset, Indicator(Manual Reset)
Operating temperature -10~60℃
Storage temperature -20~70℃
Flush mounted type
Make AC 250V 15A 0.5sec(L/R=0), DC 125V 30A 0.5sec
Break AC 250V 3A 0.5sec(L/R=0), DC 125V 30A 0.5sec
Main trip 2a CPU Error : SCADA 1a, alarm 1a
Output capacity
OC과부하 : SCADA 1a, alarm 1a OC단락 : SCADA 1a, alarm 1a
EF과부하 : SCADA 1a, alarm 1a EF단락 : SCADA 1a, alarm 1a
Life time
Withstand voltage
Lightning impulse withstand voltage
Surge transient
Electromagnetic fild
2㎸ for 1minute between all terminal
1.2㎲/50㎲ 5㎸ Positive/Negative electrodes, 3times
2.5㎸/1㎒ (IEC255-4)
5W transceiver 150㎒-400㎒/0.3m (IEC 1000-4-3 c1.2)
Transient Bust immunity
Aux. power. contacts. current-4㎸ (IEC 255-22-4)
Electrostatic discharge
8㎸ in air, 6㎸ by contacting
Vibration
Shock
22
기계적 수명 : 10×106 / 전기적 수명 : 2×105
DEESYS TOTAL PRODUCTS GUIDE
Vibration frequency : 16.7㎐ Double amplitude:0.4㎜ Direction:horizontal, vertical, transverse
Shock acceleration : 50G Shock application direction:horizontal, vertical, transverse
Shock times : 3 times
40ms
D2K-OG50 Series 3-Phase Over Current and Earth Relay[50/51,50/51N]
Front View
LED Indicator
Display
General Setting
Level Setting point
Fault check
Communication
Self test mode
CPU(RUN)Error check & Aux.
Power
Pick-up indicator
System Error indicator
Fault indicator
Comm. conection indicator
Key Part
Key part
Top menu mode key
Escape Key menu
Cursor menu key
Up�Down menu
Right�Left menu
Communication Part
Reset
RS232 Serial Part
Lamp and CPU reset
Menu Specification
Start on display
�CPU RESET S/W를 입력하거나 전원을 ON/OFF 하면 초기상태가
됩니다.
Fault Check Mode
Fault current, time, phase
�[MEMORY VIEW] Mode가 나올때까지 MODE Key를 입력합니다.
Line on Display Mode
�각상 전류(Line Check)확인은 정상 운전시에는 항상 각 상의 전류
를 인식하여 LCD 창에 1차 및 2차 전류값을 표시합니다.
�방향 Key를 입력하면 최종 사고 횟수, 사고 상, 사고 TYPE, 사고전류,
사고 Cycle, 사고 시간, 사고 날짜등을 확인 할 수 있습니다. 최종
10회까지 사고치를 기억하고 있으며 그 이상의 값은 최종 Date가
새로 입력되면 제일 먼저 입력된 Date부터 지워집니다. 이 기억
된 값은 EEPROM에 기억되므로 전원 상실시에도 유지됩니다. 먼저
입력된 사고 Date를 확인 하고자 할 때에는 위 Display Mode에서
좌, 우 방향 Key를 입력하면 됩니다.
�사고 Memory는 최대 10회까지 기억됩니다.
Setting View
�[Setting view] Mode가 나올때까지 Mode Key를 입력합니다.
�방향 Key를 입력하여 현재의 계전기 Setting 상태를 확인 할 수
있습니다.
DEESYS TOTAL PRODUCTS GUIDE
23
D2K-OG50 Series 3-Phase Over Current and Earth Relay[50/51,50/51N]
General Setup
CT ratio setup
System setup
System의 날짜, 입력 주파수, C/T Ratio Ini Display 상태등을 변경 할
수 있습니다.
�MODE Key를 이용하여 [GENERAL SETUP] 상태가 되도록 입력
합니다.
�MODE Key를 이용하여 [GENERAL SETUP] 상태가 되도록 입력합
니다.
�위 Display 상태에서 1 .SYSTEM SET에 Cursor를 위치하고 Enter
Key를 입력합니다.
�위 Display 상태에서 1 .SYSTEM SET에 Cursor를 위치하고
Enter Key를 입력합니다.
Frequency setup
�MODE Key를 이용하여 [GENERAL SETUP] 상태가 되도록 입력
합니다.
�위 Display 상태에서 1 .SYSTEM SET에 Cursor를 위치하고
Enter Key를 입력합니다.
�위 Display 상태에서 C/T Ratio에 Cursor를 위치하고 Enter Key를
입력합니다.
�위 Display 상태에서 방향 Key를 이용하여 변경 하고자 하는 C/T
Ratio를 입력 하고 Enter Key를 입력하면 변경된 값이 저장 됩니다.
최대 9999A까지 입력 가능합니다.
�위 Display 상태에서 Line Freq에 Cursor를 위치하고 Enter Key를
입력합니다.
�위 Display 상태에서 방향 Key를 이용하여 변경 하고자 하는 주파
수를 입력하고 Enter Key를 입력하면 변경된 값이 저장됩니다.
Auto test setup
Start on MODE 가기
�위 Display 상태에서 Auto Test에 Cursor를 위치하고 Enter Key를
입력합니다.
�전면판에 있는 ESC Key를 입력하면 초기 MODE로 전환됩니다.
�위 Display 상태에서 Auto Test에 Setting값을 변경 하고자 할때에
는 Up/Down Key를 입력하여 값을 변경하고 Enter Key를 입력하
면 자동으로 System을 Test 합니다.
24
DEESYS TOTAL PRODUCTS GUIDE
D2K-OG50 Series 3-Phase Over Current and Earth Relay[50/51,50/51N]
표시기능
Pickup LED
OC 또는 EF 요소중 전류치가 정정값에 접근하면 이 PICKUP LED가
깜박거리고 지속으로 켜지면 아래와 같이 Display합니다.
(OC-A Phase)
RUN LED
AUX, Power가 정상적이면 녹색 LED가 점등됩니다.
ERR LED
SYSTEM에 이상이 있거나 CPU ERROR가 발생하면 점등됩니다.
COMM LED
외부 기기와 접속하여 통신중 일때 점등됩니다.
Operating Characteristic Curves
이 계전기는 7가지의 반한시 요소, 정한시 요소를 내장한 계전기로 특성 선택시 다음과 같이 선택 할 수 있으며 국제규격 IEC표준과
KEPCO 사양을 채택 하였습니다.
DEESYS TOTAL PRODUCTS GUIDE
25
D2K-OG50 Series 3-Phase Over Current and Earth Relay[50/51,50/51N]
26
DEESYS TOTAL PRODUCTS GUIDE
D2K-OG50 Series 3-Phase Over Current and Earth Relay[50/51,50/51N]
Characteristic Curves - IEC & ESB6
×Tap (IEC)
I
(
)-1
Ip
A
∙LT-VI(장강반한시)=
B
∙N-IN(반한시)= (
C
∙V-IN(강반한시)= (
D
∙N-IN반한시)= (
E
∙V-IN(강반한시)= (
F
∙E-IN(초반한시)=
G
∙DT(정한시) = Tap(IEC)
Tap:Time lever, I:Fault current(CT 2’
ry), Ip:Current set. value
0.11
Tap
+ 0.42 )×
(KEPCO)
I 0.02
10
(
) -1
Ip
39.85
Tap
+1.084 )×
(KEPCO)
I 1.95
10
(
) -1
Ip
0.24
I 0.4
(
) -1
Ip
+0.12 )×Tap(IEC)
1.6
+0.04 )×Tap(IEC)
I
(
)-1
Ip
8
×Tap(IEC)
I
(
)-1
Ip
DEESYS TOTAL PRODUCTS GUIDE
27
D2K-OG50 Series 3-Phase Over Current and Earth Relay[50/51,50/51N]
Operating time table
�Normal inverse -IECLever Time
0.5
1
2
3
4
5
6
7
8
9
10
�Very inverse -IEC-
T2
T3`
T5
0.44
0.87
1.74
2.62
3.48
4.36
5.23
6.10
6.97
7.84
8.71
0.28
0.55
1.11
1.67
2.22
2.78
3.33
3.88
4.44
4.99
5.55
0.19
0.39
0.77
1.16
1.54
1.93
2.31
2.70
3.09
3.47
3.86
T10
0.14
0.28
0.56
0.84
1.12
1.40
1.67
1.96
2.23
2.51
2.79
Lever Time
0.5
1
2
3
4
5
6
7
8
9
10
T20
0.11
0.22
0.45
0.67
0.90
1.12
1.34
1.57
1.79
2.01
2.24
�Extremery inverse -IECLever Time
0.5
1
2
3
4
5
6
7
8
9
10
T2
T3`
T5
1.33
2.67
5.33
8.00
10.67
13.33
16.00
18.67
21.33
24.00
26.67
0.50
1.00
2.00
3.00
4.00
5.00
6.00
7.00
8.00
9.00
10.00
0.17
0.33
0.67
1.00
1.33
1.67
2.00
2.33
2.67
3.00
3.33
T10
T20
0.04
0.08
0.16
0.24
0.32
0.40
0.49
0.57
0.65
0.73
0.81
0.03
0.03
0.04
0.06
0.08
0.10
0.12
0.14
0.16
0.18
0.20
Lever Time
0.5
1
2
3
4
5
6
7
8
9
10
T2
T3`
T5
0.42
0.83
1.66
2.49
3.32
4.15
4.98
5.81
6.64
7.47
8.30
0.27
0.54
1.07
1.61
2.15
2.69
3.22
3.76
4.30
4.83
5.37
0.19
0.38
0.76
1.14
1.51
1.89
2.27
2.65
3.03
3.40
3.78
Part
Indicator
T10
0.14
0.28
0.55
0.83
1.10
1.37
1.65
1.93
2.20
2.48
2.75
Lever Time
0.5
1
2
3
4
5
6
7
8
9
10
T20
0.11
0.22
0.44
0.66
0.88
1.10
1.32
1.54
1.76
1.98
2.20
Phase
A-B
Phase
B-C
Fault
C-A
A-B-C
A-N
B-N
C-N
Ground
A-B-N
Fault
B-C-N
C-A-N
A-B-C-N
28
Operating Indicator(LED)
Time Over
A
B
●
●
●
●
●
●
●
●
●
●
●
DEESYS TOTAL PRODUCTS GUIDE
●
●
●
T5
0.22
0.44
0.88
1.32
1.76
2.20
2.64
3.08
3.52
3.96
4.40
T10
T20
0.11
0.22
0.44
0.65
0.87
1.09
1.31
1.52
1.74
1.96
2.18
0.06
0.12
0.25
0.37
0.50
0.62
0.75
0.87
0.99
1.12
1.24
T2
T3`
T5
3.00
6.00
12.00
18.00
24.00
30.00
36.00
42.00
48.00
54.00
60.00
1.50
3.00
6.00
9.00
12.00
15.00
18.00
21.00
24.00
27.00
30.00
0.75
1.50
3.00
4.50
6.00
7.50
9.00
10.50
12.00
13.50
15.00
T10
T20
0.33
0.67
1.33
2.00
2.67
3.33
4.00
4.67
5.33
6.00
6.67
0.16
0.32
0.63
0.95
1.26
1.58
1.90
2.21
2.53
2.84
3.16
T10
T20
0.08
0.15
0.31
0.46
0.61
0.77
0.92
1.08
1.23
1.38
1.54
0.06
0.12
0.24
0.36
0.48
0.60
0.72
0.84
0.96
1.08
1.20
�Very inverse -KEPCO-
Fault indicator LED
F.T Part
T3`
0.42
0.84
1.68
2.52
3.36
4.20
5.04
5.88
6.72
7.56
8.40
�Long-Very inverse -IEC-
�Normal inverse -KEPCOLever Time
0.5
1
2
3
4
5
6
7
8
9
10
T2
0.82
1.64
3.28
4.92
6.56
8.20
9.84
11.48
13.12
14.76
16.40
current Inst.Over Current
C
EF
A
B
C
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
EF
●
●
●
●
●
●
●LED ON
T2
T3`
T5
0.75
0.50
3.00
4.50
6.00
7.50
9.00
10.50
12.00
13.50
15.00
0.32
0.64
1.28
1.92
2.55
3.19
3.83
4.47
5.11
5.75
6.38
0.14
0.29
0.58
0.87
1.16
1.045
1.73
2.02
2.31
2.60
2.89
D2K-OG50 Series 3-Phase Over Current and Earth Relay[50/51,50/51N]
Wiring
Terminal arrangement
DEESYS TOTAL PRODUCTS GUIDE
29
D2K-OG50 Series 3-Phase Over Current and Earth Relay[50/51,50/51N]
Dimension
30
DEESYS TOTAL PRODUCTS GUIDE
한국전기연구원 개발시험합격품
Digital Protective
Relay
■Reclosing Relay [79]
D RC-O41
자동재폐로계전기
Reclosing Relay[79]
MODEL DRC-041(Draw out type)
Funtion
�Test
�Counter erase
�Set Checking (Pt, Rt, Wt, T1, T2, T3, Counter)
�Reset (Lock out)
�CPU Reset
Permissible ambinet Temperature
�-10℃ to +50℃ (Guaranted Performance)
�-20℃ to +60℃ (Storage)
Feature
The auto-reclosing relay is designed with micro processor
based electronic CPU. Which can be applied for any
distribution line either coordinating with synchronizing relay or
bus voltage supervising relay. As setting range is wide, the
reclosing relay may coordinate with other protective relay or
system easily. Since the relay has a self checking funtion. It
can be shown the error message on the front plate of the
relay as soon as detected. There is a delay timer with which
discrepancy time between main and aux. contact of circuit
breaker can be adjusted.
Specification
Application
The relay is applied for 3 phase reclosing system up to
154kV transmission network. The relay has input for
synchronizing relay or bus voltage relay where need for
network operation or bus voltage supervision.
Model
�DRC-041(Draw out type)
Rating
�Aux. Power : DC110/125V(+100%, -20%)
Setting Range
�Prepare Time : 30+(5, 10, 20, 40, 75) ∑ (5Sec step,
30~180Sec)
�Reclaim Time : 20+(10, 20, 40, 80, 130) ∑ (10Sec step,
20~300Sec)
�Waiting Time : 1, 2, 3, 4, 5, 8, +∑ (1Sec step, 1~20Sec)
�T1 Time : 0.1, 0.2, 0.4, 0.8, 1.5, +∑ (0.1Sec step, 0~3.0Sec)
�T2 Time : 1, 2, 3, 4, 8, 15 +∑ (1Sec step, 0~30Sec)
�T3 Time : 5, 10, 15, 30, 60 +∑ (5Sec step, 0~120Sec)
Input Contact
�25-a : Synchro Relay (Normal "a")
�M/L : Manual Locking
�63CB : Circuit breaker Pressure
�50/51-a : Relay Contact
�43RC : Reclosing switch ON/OFF
�CB-a : Circuit breaker“a”Contact
Output Contact
�79B : OTLC Blocking
�79M : Reclosing signal (During Reclosing pulse with)
�79S : 50 Relay Blocking (During Reclosing pulse with)
�79C : Relay Error (C.P.U, Power)
�79F : Lock out (Fail) Continuous
Counter Indicator
�Cumulative number of reclosing Commands, up to 999
Reclosing pulse with
32
DEESYS TOTAL PRODUCTS GUIDE
500ms
Insulation
�2kV, 50/60Hz for 1Min
�Between all terminals Connected for together and Earth
Impulse Withstand
�5kV, 1.2/50㎲
�Between all terminals Connected for together and Earth
Time Chart(four times reclaim success)
Reclosing Relay[79]
특징
Feature
이 자동 재폐로 계전기는 마이크로 프로세스 칩을 사용하여 선로사고
차단시 3상 일괄, 3회까지 자동 재투입 할 수 있는 계전기 입니다. 마
이크로 프로세스 칩을 사용하므로써 재폐로의 정확성을 확보하고 시간
설정범위의 폭을 넓혔으므로 어떠한 계통에서도 사용이 가능합니다.
자가 진단 기능을 내장하고 있어 CPU가 정상이 아닐 경우 에러 표시
가 나타납니다. 또한 차단기 보조 접점 시간차를 보정 할 수 있는
Time delay 요소가있습니다.
The Auto-reclosing relay based on microprocessor
technology is for 3phase reclosing distribution system. While
Line fault occurs and circuit breaker(CB) is tripped by OCR,
the Auto-reclosing relay makes the CB reclosed for three
times at a time. By appling advanced technology, the relay
has not only advanced reliable operation, but also wide
range of time set and various function, interval failure of the
relay like DC fail or CPU error etc. is shown by LED on the
front plate. For the interval fault, a output contact is provided
for remote control supervision. For adjusting purpose with
aux. contact from CB, the relay is provide a time delay
element.
적용
Application
이 3상 일괄 투입형 자동 재폐로 계전기는 154급 이하 방사상 선로에
사용할 수 있으며, 동기 계전기와 조합하여 동기 조건이 맞을 경우 투
입 할수 있는 기능도 내장되어 있습니다. 동기 조건이 필요 없는 선로
에서는 모선전압 감시 계전기와 조합하여 모선이 이상 없을 시 투입
조건을 만족하도록 하는 기능으로 사용됩니다.
The three phase auto-reclosing relay is for radial
transmission line below 160kv system. It can be
coordinated with synchronizing relay for check live-line
and live-bus or voltage detecting relay for main bus
voltage.
명판
Front plate
-기능 다이얼 : 정상 운전시 이 다이얼은 COUNT에 놓습니다. 릴레이
가 동작하면 동작 횟수에 따라 1st LED/ 2nd LED/ 3rd LED 순으
로 켜집니다. 이 LED는 RESET을 누르면 꺼집니다. Pt-Rt-Wt-T1T2-T3 순으로 돌리면 그 위치에서 Setting 값을 확인 할 수 있습니다.
-디스플레이 기능 : 기능 다이얼을 COUNT에 놓아두면 재폐로 총 누
계 횟수를 지시합니다.
-COUNT ERASE Button을 누르면 디스플레이의 누계 횟수가 지워집
니다.
-POWER LED(Green) : Aux power가 정상이면 항시 켜져 있습니다.
만약 CPU 에러에 의한 꺼짐 상태라면, RESET를 누르면 복귀합니다.
만약 복귀되지 않을 경우 전문가에 의한 내부점검이 필요합니다.
-SUCCESS LED(Green) : 재폐로가 성공적으로 완료되면 커집니다.
이 LED는 다음 재폐로 신호가 들어 올 때까지 켜져 있습니다.
-FAIL LED(Red) : 재폐로를 실패하면 켜집니다.
-PREPARE LED(Yellow) : 재폐로를 수행 중에 켜집니다.
-25-a LED(Green) : 동기 조건이 맞았을 시 켜집니다.
-Pt dip swith : 초기 준비 시간을 설정합니다.
-Rt dip swith : 리클레임 타임을 설정합니다.
-Wt dip swith : 웨이팅 타임을 설정합니다.
-T1/T2/T3 dip swith : 1,2,3차 재폐로 시간을 설정합니다. Dips with
의 타임 정정값을 0(off)으로 놓으면 PASS기능을 합니다. 예를 들면
T3의 모든 swith 를 off로 놓으면 3회 재폐로는 수행되지 않습니다.
-NORMAL/LOCK Switch : NORMAL측으로 놓으면 재폐로 기능 적
용이며 LOCK측으로 놓으면 재폐로 기능을 off합니다.
-RESET : 재폐로 실패시 이 Button을 눌러 주어야 다음 사고시 재폐
로 기능을 수행합니다.
-CPU RESET : CPU에러 발생시도 POWER LED가 DC전원 상실시
와 같이 꺼집니다. 이때 이Button 을 누르면 복귀됩니다. 만일 전원
이 정상이면서 복귀되지 않는다면 릴레이의 자체를 점검해야 합니다.
- Menu Dial : The dial pointer will be set at COUNT for
normal use. Accumulated reclosed times are summed on
the display While reclosing is performing. 1st LED-2nd
LED-3rd LED is/are lighted in order whenever succeeding.
The LEDs are off by RESET Button. By turning the dial, PtRt-Wt-T1-T2-T3. Preset value is shown on the display.
- COUNT ERASE : The button is for erasing of cumulated
recolsed times.
- POWER LED(Green) : The LED is lighted during Aux. power
ON. If the LED is off caused by CPU Error, press RESET,
The POWER LED will be ON. If not, the relay have to be
checked in detail by specialist.
- SUCCESS LED(Green) : If reclosing is performed
successfully, the LED is lighted. The LED is ON, until next
performing.
- FAIL LED(Green) : The LED is lighted when auto reclosing
is failed.
- PREPARE LED(Yellow) : The LED is lighted under
performing reclosing funtion.
- 25-a LED(Green) : The LED is lighted when synchronizing
condition is OK.
- Pt : Preparing time set switch
- Rt : Reclaim time set switch
- Wt : Waiting time set switch
- T1/T2/T3 : reclosing time set switches. If set value is 0,
then the Tx will be passed.
- NORMAL/LOCK : NORMAL means reclosing function in ON,
while LOCK is off for the reclosing function.
- RESET : After reclosing fail or one cycle of reclosing
function, the RESET will return all initial condition of the
reclosing relay for next performance.
- CPU RESET : If CPU Error occurs, the POWER LED is off,
the LED is on by pressing the CPU RESET. If the LED is
not ON, the relay have to be checked in detail by a
specialist.
- TEST : Pressing one time, Performing 1st reclosing function.
Pressing second(third) time with in reclaim time set,
performing 2nd(3rd) time reclosing function. After three
times performing. FAIL LED will be lighted by pressing one
more time(4th). For initial condition, press RESET.
※ 자체 재폐로 시험 방법
재폐로 연동시험을 가상적으로 수행할시 과전류부(OC)는 순시로 설정하고 지락요소(EF)의 순시를
Lock 시킨후 한시로 동작할 수 있도록 설정한 후 재폐로 계전기와 연동시험을 하면됩니다.
1회 재폐로 OCR부의 순시로 동작
2회 재폐로GR부의 한시동작(시간 : 정한시-DEF- / 동작시간Lever : 최소
DEESYS TOTAL PRODUCTS GUIDE
33
Reclosing Relay[79]
Terminal block
Dimension
DRC-041
DRC-041
Connection
FEEDER PROTECTION & RECLOSING
NOTEl
① : 재폐로 신호(100mS)
② : Trip Signal
1. LPS - 모선 LINE 전압활선 및 Synchro Relay Contact-Nomal Close
2. 43RC - 재폐로 사용 및 잠금 Switch(Normal Close)
3. 79SX - 순시 Blocking용 Aux, Relay, 79FX-Lock Out용 Aux, Relay, 79PX - Preparing Completed, 28RX - OCR System Error,
79CX - Red System Error
4. 외부신호중 사용하지 않는 다음의 신호는 (+)에 연결한다.〔 20-a(Terminal- 1번 단자), 60CB-a(Terminal- 3번 단자)〕
34
DEESYS TOTAL PRODUCTS GUIDE
한국전기연구원 개발시험합격품
Digital type Protective Relay
■Digital Over Current and Earth Fault Relay [50/51x3, 50/51N]
■Digital Over and Under Voltage Relay [59/27]3∅
■Multifunction Over Current and Earth Fault Relay [50/51x3, 50/51N]
■Over Current Relay [50/51x2] [50/51x3]
■Ground Over Current Relay(Earth Fault Relay) [50/51N]
■Multifunction Over and Under Voltage Relay [59/27]
■Over and Under Voltage Relay [59/27]1∅
■Ground Over Voltage Relay [64]
■Directional Ground Relay [67]
■High Voltage Zero-Phase Current Transformer [ZCT]HZR-Series
■Static Phase Open Relay [47]
■High Voltage Ground Relay [51G]
디지털형 계전기
Digital Over Current and Earth Fault Relay [50/51X3, 50/51N]
Front View
1. 4X20 DISPLAY LCD
- State and information
Display
2. L.E.D INDICATOR
- Trip phase and state
indication
3. CONTROL KEY
- Use to setting and
check the state
4. CLEAR / VIEW
- LAMP CLEAR &
LCD BACKLIGHT
5. CPU RESET
- Use to CPU rest
Menu Specification
1. 4X20 LCD DISPLAY WINDOW
특징
� 각 상의 전류값을 표시하며 상태 및 셋팅을 확인 할 수 있는 정
� 이 디지털 과전류 계전기는 마이크로 프로세서 기술을 적용한
계전기로서 3상과전류 요소와 접지과전류 요소를 가진 계전기
입니다. OCR과 OCGR는 독립적으로 정정 가능합니다. 보호협
조는 (1)반한시, 강반한시, 초강반한시 이중 1개 요소와 순시 요소
또는 (2)정한시 적용할 수 있습니다. 본 릴레이는 마이크로 프로
세서 칩 및 A/D 컨버터등 최첨단 기술의 적용으로 기존의 기계
식이나 정지형 보다 월등히 정밀하고 정확히 동작합니다.
적용
� 이 디지털 계전기는 직접접지 또는 저항접지 개통인 배전선로
보호 및 수용가의 수전 변전소의 feeder 보호용에 적용할 수 있
습니다. 이 릴레이는 다기능 / 광범위의 정정이 가능하므로 설계
단계에서 정확하게 정정치를 계산하지 않아도 되므로, 릴레이 선
택이 용이합니다.
보로 표시해준다.
2. L.E.D INDICATOR
� 제품의 동작상태를 표시해준다.
- RUN : MAIN CPU의 동작여부를 확인할 수 있다.
- PICKUP : 과전류 입력시 점등
- COMM : RS 485 통신의 동작상태를 표시
- R.S.T.N : 동작된 상을 표시
- INST : 순시동작을 하였을시 점등
- POWER : 전원의 동작상태를 확인할 수 있다.
3. 조작부
� 셋팅 및 상태를 확인하기위한 조작시 사용되는 버튼
- MODE : MAIN SETUP을 진입하기위해 사용된다.
- ENTER : SETTING된 값을 확정할 때 사용된다.
- ESC : 설정값을 취소하거나 상위메뉴로 빠져나오기위해 사용
된다.
- ▲, ▼, ◀, ▶버튼 : MENU를 스크롤하거나 선정값을 조정, 커서
의 위치변경에 사용된다.
4. CPU RESET
� CPU를 RESET할 때 사용한다. 단, 설정된값과 저장된 데이터는
지워지지 않는다.
5. CLEAR / VIEW
� LAMP의 RESET 및 LCD의 BACKLIGHT를 동작시킬때 사용된다.
- 1회 누름 : LCD의 BACKLIGHT 동작
- 2회 누름 : BACKLIGHT동작후 LAMP CLEAR
36
DEESYS TOTAL PRODUCTS GUIDE
Digital Over Current and Earth Fault Relay [50/51X3, 50/51N]
Menu Specification
Main Menu
4. C/T RATIO
- 사용 CT의 1차와 2차의 비율을 설정한다.
▶ 방향키 (▲, ▼, ◀, ▶)를 이용하여 CT의 1차측 값을 설정한다.
설정된 CT비율은 입력된 값이 계산되어 전면 LCD에 DISPLAY
된다.
� 전원 투입시 초기화면
O V E R
E A R T H
C U R R E N T
&
F A U L T
R E L A Y
v . X X
OPERATING SETUP
� 전원 투입시 초기화면
� MODE 버튼을 누른후 나타나는 MENU 화면
[
1 . S Y S
2 . O P E
3 . F A U
M
T
R
L
A I N
M E N U ]
E M
S E T U P
A T I N G
S E T U P
T
M E M O R Y
[
1
2
3
O P E
. T O
. L E
. T O
R
C
V
C
A T I N G
S E T U P ]
/ I O C
( O C )
E R / C U R V E ( O C )
/ I O C ( O G )
4 . L E V E R / C U R V E ( O G )
[ M A I N
M E N U ]
4 . S E L F
T E S T
5 . S E C U R I T Y
S E T
1. TOC/IOC(OC)
1. SYSTEM SETUP
- RELAY의 통신 및 CT비 등의 설정을 할 수 있다.
[ T O C / I O C ] [ O C ]
T O C [
X . X ]
L O C K ?
[ N ]
I O C [
X ]
L O C K ?
[ N ]
2. OPERATING SETUP
- OC 및 OG관련 동작치 및 동작시간(커브)를 설정 할 수 있다.
TOC : 과전류 설정항목이며 방향키(▲, ▼)를 이용하여 원하는
값을 설정한다.
▶ LOCK : 방항키(▲, ▼)를 이용하여 Y, N 값을 설정할 수 있다.
Y로 설정시 TOC는 동작 하지 않는다.
▶ IOC: 순시전류 설정항목이며 방향키(▲, ▼)를 이용하여 원하는
값을 설정한다.
▶ LOCK : 방항키(▲, ▼)를 이용하여 Y, N 값을 설정할 수 있다.
Y로 설정시 IOC는 동작 하지 않는다.
▶
3. FAULT MEMORY
- 최근 사고기록을 10개까지 확인할 수 있다.
4. SELF TEST
- LAMP 및 RELAY 의 동작을 TEST할 수 있다.
5. SECURITY
- PASSWORD 를 설정할 수 있다.
2. LEVER / CURVE(OC)
System Setup
[ L E V E R / C U R V E ] [ O C ]
L E V E R
[
X . X ]
C U R V E
[ N I ]
� SYSTEM SETUP 상세 메뉴
F
D
C
C
R
E
O
/
E Q U E N C Y
V I C E
I D
M M
S P E E D
T
R A T I O
[
[
[
[
X
X
1
X
X
X
9
X
] H z
]
2 0 0 ]
X X ] / 5 A
1. FREQUENCY
- 입력 전류의 주파수를 조정한다.
▶ 방향키 (▲, ▼)를 이용하여 50 / 60Hz로 조정 할 수 있다.
2. DEVICE ID
▶ 방향키 (▲, ▼, ◀, ▶)를 이용하여 원하는 설정값을 입력한다.
LEVER : OC에서 설정된 이상의 값이 입력시에 동작시간을 설
정하는 항목이며 방향키(▲, ▼, ◀, ▶)를 이용하여 원
하는 값을 설정한다.
▶ CURVE : 방향키(▲, ▼)를 이용하여 DT, NI, VI, EI 값을 설정할
수 있다.
- DT : Definite Time
- NI : Normal Inverse
- VI : Very Inverse
- EI : Extremely Inverse
▶
3. TOC/IOC(OG)
3. COMM SPEED
- RS 485 통신 사용시, 통신의 속도를 조정한다.
▶ 방향키 (▲, ▼)를 이용하여 9600bps / 19200bps 설정이
가능하다.
[ T O C / I O C ] [ O G ]
T O C [
X . X ]
L O C K ?
[ N ]
I O C [
X ]
L O C K ?
[ N ]
▶
TOC : 지락과전류 설정항목이며 방향키(▲, ▼)를 이용하여 원
하는 값을 설정하다.
DEESYS TOTAL PRODUCTS GUIDE
37
Digital Over Current and Earth Fault Relay [50/51X3, 50/51N]
Menu Specification
LOCK : 방항키(▲, ▼)를 이용하여 Y, N 값을 설정할 수 있다.
Y로 설정시 TOC는 동작 하지 않는다.
▶ IOC: 지락순시전류 설정항목이며 방향키(▲, ▼)를 이용하여
원하는 값을 설정한다.
▶ LOCK : 방항키(▲, ▼)를 이용하여 Y, N 값을 설정할 수 있다.
Y로 설정시 IOC는 동작 하지 않는다.
▶
SELF TEST
� SELF TEST 상세메뉴
[ T O C / I O C ] [
I O C [
X ]
1 . T
2 . T
3 . T
O C ]
E S T
E S T
E S T
L A M P
R E L A Y
S W I T C H
4. LEVER / CURVE(OG)
1. TEST LAMP
▶ 전면부의 L.E.D 불량여부를 검사하는 메뉴이다.
[ L E V E R / C U R V E ] [ O C ]
L E V E R
[
X . X ]
C U R V E
[ N I ]
LEVER : TOC에서 설정된 이상의 값이 입력시에 동작시간을
설정하는 항목이며 방향키(▲, ▼, ◀, ▶)를 이용하여
원하는 값을 설정한다.
▶ CURVE : 방향키(▲, ▼)를 이용하여 DT, NI, VI, EI 값을 설정할
수 있다.
- DT : Definite Time
- NI : Normal Inverse
- VI : Very Inverse
- EI : Extremely Inverse
▶
FAULT MEMOY
[ L E M P
T E S T ]
[ E N T E R ]
T O
A L L
L A M P
[ E S C ]
T O
Q U I T
L E S T
- 위의 메뉴상태에서 ENTER KEY를 누르면 전면부의 모든
L.E.D가 점등하며, ESC KEY를 누르면 상위메뉴로 빠져나온다.
2. TEST RELAY
[ R
[ L E F T ]
[ R I G H T
[ E S C ]
t
E L A Y
T E S T ]
T O
0 C
T R I P
] T O
E F
T R I P
o
Q U I T
T E S T
�FAULT MEMORY 상세 메뉴
- 위의상태에서 LEFT KEY(◀)를 누르면 OC RELAY가 TRIP하
며, RIGHT KEY(▶)를 누르면 EF RELAY가 TRIP한다.
ESC KEY를 누르면 상위메뉴로 빠져나온다.
[ F A U L T
M E M O R Y ]
1 . F A U L T
R E C O R D
2 . C L E A R
F A U L T
M E M
3. TEST SWITCH
1. FAULT RECORD
[ F A U L T
V I E W ]
N 0 : 0 1
o f
1 0
r e c o r d s
P h a s e : X
A m p : X X X . X
T y p e : x x x x
C y c : x x x x x x
▶
▶
사고전류 입력된후 TRIP이 되면 최고 10회까지 사고내용이
저장된다.
FAULT RECORD 선택시 나타나는 세부설정 항목
- NO : 기록값의 번호, 빠를수록 최근의 사고 기록이며 10개의
데이터 초과시 가장 나중값이 지워지며 다시 기록된다.
- Phase : 사고발생 상을 표시한다. R, S, T상중 가장 먼저
TRIP이 발생한 사고상을 표시해준다.
- Amp : 사고발생시 입력된 사고전류의 크기를 표시해준다.
- Type : 사고의 종류를 표시한다. 한시사고(Time)와 순시사고
(Inst)를 표시해준다.
- Cyc : 사고전류 입력시(Pickup)에서 Relay Trip까지의
시간을 Cycle로 표시해준다.
2. CLEAR FAULT MEM
[ F A U L T
C L E A R ]
C L E A R
F A U L T
R E C ?
▶
38
[ N ]
방향키(▲, ▼)를 이용하여 Y, N을 선택 할 수 있으며 Y선택시 저
장되어진 모든 사고 데이터가 삭제된다.
DEESYS TOTAL PRODUCTS GUIDE
[ S W I T C H
T E S T ]
[
]
<
h e r e
P r e s s & c h e c k
s w i t c h
[ E S C ] t o
Q U I T
T E S T
- 위의 메뉴상태에서 각 Key를 누르면[ ]부분에 눌러진 Key의 값
이 표시된다. CPU RESET과 MODE KEY를 제외한 각 키의 불
량여부를 확인 할 수 있다.
ESC KEY를 누르면 상위메뉴로 빠져나온다.
SECURITY SET
� SECURITY SET 상세메뉴
[ S E C U R I T Y
P A S S W O R D
P A S S W O R D ]
[ * * * * ]
s e t ’ 0 0 0 0 ’ t o
d i s a b l e
1. SECURITY PASSWORD
▶ 제품의 PASSWORD를 설정하는 부분이다.
- 패스워드를 사용하지 않는 경우 :“000”
로 설정한다.
- 패스워드를 사용하는 경우 :“0001”
~”
9999”사이의 숫자를
입력한다.
[패스워드가 활성화 되고하면 MODE번튼을 누를 때 마다 패스
워드를 묻게 된다.]
- 패스워드를 잃어버렸을 경우 :“1183”
을 입력 한다.
[1183을 입력할 경우 패스워드가“0000”
으로 초기화 된다.]
Digital Over Current and Earth Fault Relay [50/51X3, 50/51N]
MODEL ▶ DOG-D51D-N(DRAW OUT)
▶ DOG-D51-N(NON DRAW OUT)
RATING
Rated Current
AC 5A
Frequency
50/60Hz ± 5%
Burden
OC 0.5VA, EF 0.2VA
Element
(50/51) 3PHASE, 50N/51N
Standard Code
IEC 255, KEMC 1120
Auxiliary Voltage
AC/DC 80~260V
Memory
Up to 10 records of Fault data
Communication
RS-485 Mod-bus Protocol(9600/ 19200bps)
Ambient Temperature
-10。~ 60。(with no icing)
CONTACT
AC 240V 10A 0.5sec (R/L=0ms)
Make
DC 1000W 0.5sec (R/L=0ms)
Capacity
AC 240V 3A 0.5sec (R/L=0ms)
Break
DC 30W 0.5sec (R/L=0ms)
INSULATION
Dielectric Withstacd
2KV for 1minute between all terminal
Insulation Resistance
�100MΪ
Lightning Impulse Witihstand
5KV 1.2㎲ /50㎲
Surge Transient
(DC 500V Megger)
Positive/Negative 3Times
2.5KV 1MHz/ 200Ϊ
CURRENT SETTING
Type1
OC
Standard
EF
Over Current : 0.2 ~ 15A (0.1A step)
Insttantaneous : 5.0 ~ 80A (1A step)
Over Current : 0.2 ~ 5A (0.1A step)
Instantaneous : 1.0 ~ 40A (1A step)
OPERATING TIME
Over Current
[LEVER 10]
Earth Fault
[LEVER 5]
NI
300% : 6.30sec / 700% : 3.53sec
VI
300% : 6.75sec / 700% : 2.25se
EI
300% : 10.0sec / 700% : 1.67sec
NI
300% : 3.15sec / 700% : 1.76sec
VI
300% : 3.37sec / 700% : 1.12sec
EI
300% : 5.0sec / 700% : 0.83sec
TIME SETTING & CURVE (IEC 255-3)
OC / EF Lever
0.1 ~ 40 Lever (0.1 step)
Instantaneous Time
Less than 50ms
0.14
tp
t =
�
I 0.02 -1
10
13.5
tp
t =
�
I - 1
10
80
tp
t = 2
�
I - 1
10
Normal inverse Time
Very inverse Time
Extremely Inverse Time
Definite Time
t = tp
Resetting Value
�90%
Reset Time
I:%Current
(80% � 0.8)
(120% � 1.2)
tp : Time Lever
�100ms
DEESYS TOTAL PRODUCTS GUIDE
39
Digital Over Current and Earth Fault Relay [50/51X3, 50/51N]
■ Block diagram
■ Wiring
■ Terminal arrangement
40
DEESYS TOTAL PRODUCTS GUIDE
Digital Over Current and Earth Fault Relay [50/51X3, 50/51N]
Over current and earth fault relay
(%)CURRENT
(%)CURRENT
(%)CURRENT
(%)CURRENT
DEESYS TOTAL PRODUCTS GUIDE
41
Digital Over & Under Voltage Relay [59/27]3
Front View
1. 4X20 DISPLAY LCD
- State and information
Display
2. L.E.D INDICATOR
- Trip phase and state
indication
3. CONTROL KEY
- Use to setting and
check the state
5. CLEAR / VIEW
- LAMP CLEAR &
LCD BACKLIGHT
4. CPU RESET
- Use to CPU rest
Menu Specification
1. 4X20 LCD DISPLAY WINDOW
특징
� 각 상의 전압을 표시하며 상태 및 셋팅을 확인 할 수 있는 정
� 이 다기능 과,부족전압 계전기는 마이크로 프로세서 기술을 적용
한 계전기로서 3상과전압 요소와 저전압 요소를 가진 계전기
입니다. OUVR은 독립적으로 정정 가능합니다.
보호협조는 (1)반한시, 정한시 이중 1개 요소와 순시 요소에 적용
할 수 있습니다.
본 릴레이는 마이크로 프로세서칩 및 A/D 컨버터등 최첨단 기
술의 적용으로 기존의 기계식이나 정지형 보다 월등히 정밀하고
정확히 동작 합니다.
적용
� 이 디지털 전압계전기는 발전기의 고장이나 선로사고시 또는 정
전시의 전압변동에 대응하여 1V 단위의 정밀정정이 가능하며,
동작시의 사고값이 기록되어 수/변전설비 보호용으로 적용할 수
있습니다.
보로 표시해준다.
2. L.E.D INDICATOR
� 제품의 동작상태를 표시해준다.
- RUN : MAIN CPU의 동작여부를 확인할 수 있다.
- PICKUP : 과전압/부족전압 입력시 점등
- COMM : RS 485 통신의 동작상태를 표시
- AB, BC, CA : TRIP이 동작된 상을 표시
- UV, OV : UNDER VOLTAGE 및 OVER VOLTAGE의 동작
상태 표시
- INST : 순시동작을 하였을시 점등
- POWER : 전원의 동작상태를 확인할 수 있다.
3. 조작부
� 셋팅 및 상태를 확인하기위한 조작시 사용되는 버튼
- MODE : MAIN SETUP을 진입하기위해 사용된다.
- ENTER : SETTING된 값을 확정할 때 사용된다.
- ESC : 설정값을 취소하거나 상위메뉴로 빠져나오기위해 사용
된다.
- ▲, ▼, ◀, ▶버튼 : MENU를 스크롤하거나 선정값을 조정, 커서
의 위치변경에 사용된다.
4. CPU RESET
� CPU를 RESET할 때 사용한다. 단, 설정된값과 저장된 데이터는
지워지지 않는다.
5. CLEAR / VIEW
� LAMP의 RESET 및 LCD의 BACKLIGHT를 동작시킬때 사용된
42
다.
- 1회 누름 : LCD의 BACKLIGHT 동작
- 2회 누름 : BACKLIGHT동작후 LAMP CLEAR
DEESYS TOTAL PRODUCTS GUIDE
Digital Over & Under Voltage Relay [59/27]3
Menu Specification
Main Menu
OPERATING SETUP
� 전원 투입시 초기화면
� 전원 투입시 초기화면
3 P H A S E
O V E R
&
U N D E R
V O L T A G E
v . X X
� MODE 버튼을 누른후 나타나는 MENU 화면
[
1 . S Y S
2 . O P E
3 . F A U
M
T
R
L
A I N
M E N U ]
E M
S E T U P
A T I N G
S E T U P
T
M E M O R Y
[ M A I N
M E N U ]
4 . S E L F
T E S T
[
1
2
3
O
.
.
.
E
V
E
N
R
E
V
D
A T I N G
S E
R
V O L T A G
E R / C U R V E
E R
V O L T A
T U P ]
E
( O V )
G E
4 . L E V E R / C U R V E ( U V )
1. OVER VOLTAGE
O V
▶
1. SYSTEM SETUP
- RELAY의 통신 및 PT비 등의 설정을 할 수 있다.
P
O
L
U
▶
[ O V E R
[
X . X ]
V O L T A G E ]
L O C K ?
[ N ]
OV : 과전압 설정항목이며 방향키(▲, ▼)를 이용하여 원하는 값
을 설정한다.
LOCK : 방향키(▲, ▼)를 이용하여 Y, N 값을 설정할 수 있다.
Y로 설정시 OV는 동작 하지 않는다.
2. OPERATING SETUP
- OV 및 UV관련 동작치 및 동작기간(커브)를 설정 할 수 있다.
2. LEVER / CURVE(OV)
3. FAULT MEMORY
- 최근 사고기록을 10개까지 확인할 수 있다.
[ L E V E R / C U R V E ] [ O V ]
L E V E R
[
X . X ]
C U R V E
[ N I ]
4. SELF TEST
- LAMP 및 RELAY 의 동작을 TEST할 수 있다.
System Setup
� SYSTEM SETUP 상세 메뉴
F R E Q U E N C Y
D E V I C E
I D
C O M M
S P E E D
[ X X ] H z
[ X X ]
[ 1 9 2 0 0 ]
1. FREQUENCY
- 입력 전압 및 전류의 주파수를 조정한다.
▶ 방향키 (▲, ▼)를 이용하여 50 / 60Hz로 조정 할 수 있다.
2. DEVICE
▶ 방향키 (▲, ▼, ◀, ▶)를 이용하여 원하는 설정값을 입력한다.
LEVER : OV에서 설정된 이상의 값이 입력시에 동작시간을 설
정하는 항목이며 방향키(▲, ▼, ◀, ▶)를 이용하여 원
하는 값을 설정한다.
▶ CURVE : 방향키(▲, ▼)를 이용하여 DT, NI 값을 설정할 수 있
다.
- DT : Definite Time
- NI : Normal Inverse
▶
3. UNDER VOLTAGE
[ T U V / I U V ] [ U V ]
T U V [
X . X ]
L O C K ?
[ N ]
I U V [
X . X ]
L O C K ?
[ N ]
▶
TUV : 부족전압 설정항목이며 방향키(▲, ▼)를 이용하여 원하
는 값을 설정한다.
▶
LOCK : 방향키 (▲, ▼)를 이용하여 Y, N값을 설정할 수 있다.
Y로 설정시 TUV는 동작 하지 않는다.
3. COMM SPEED
- RS 485 통신 사용시, 통신의 속도를 조정한다.
▶ 방향키 (▲, ▼)를 이용하여 9600bps / 19200bps 설정이
가능하다.
DEESYS TOTAL PRODUCTS GUIDE
43
Digital Over & Under Voltage Relay [59/27]3
Menu Specification
▶
▶
IUV : 순시 부족전압 설정항목이며 방향키(▲, ▼)를 이용
하여 원하는 값을 설정한다.
LOCK : 방향키(▲, ▼)를 이용하여 Y, N 값을 설정할 수 있다.
Y로 설정시 (▲, ▼) IUV는 동작 하지 않는다.
4. LEVER / CURVE(UV)
[ L E V E R / C U R V E ] [ U V ]
L E V E R
[
X . X ]
C U R V E
[ N I ]
SELF TEST
� SELF TEST 상세메뉴
[
1 . T E
2 . T E
3 . T E
S
S
S
S
E L F
T
L A
T
R E
T
S W
T
M
L
I
E S T ]
P
A Y
T C H
1. TEST LAMP
▶ 전면부 L.E.D 불량여부를 검사하는 메뉴이다.
LEVER : TUV에서 설정된 이상의 값이 입력시에 동작시간을
설정하는 항목이며 방향키(▲, ▼, ◀, ▶)를 이용하여
원하는 값을 설정한다.
▶ CURVE : 방향키(▲, ▼)를 이용하여 DT, NI 값을 설정할 수 있
다.
- DT : Definite Time
- NI : Normal Inverse
▶
[ L A M P
T E S T ]
[ E N T E R }
T O
A L L
L A M P
[ E S C ]
T O
Q U I T
T E S T
- 위의 메뉴상태에서 ENTER KEY를 누르면 전면부의 모든
L.E.D가 점등하며, ESC KEY를 누르면 상위메뉴로 빠져나온다.
2. TEST RELATY
FAULT MEMOY
[ R
[ L E F T ]
[ R I G H T
[ E S C ]
t
� FAULT MEMORY 상세 메뉴
[ F A U L T
M E M O R Y ]
1 . F A U L T
R E C O R D
2 . C L E A R
F A U L T
M E M
1. FAULT RECORD
▶ 사고전압이 입력된후 TRIP이 되면 최고 10회까지 사고내용이
저장된다.
▶ FAULT RECORD 선택시 나타나는 세부설정 항목
[ F A U L T
V I E W ]
N 0 : 0 1
o f
1 0
r e c o r d s
P h a s e : X
V O L T : X X X . X
T y p e : x x x x
C y c : x x x x x x
- NO : 기록값의 번호, 빠를수록 최근의 사고 기록이며 10개의
데이터 초과시 가장 나중값이 지워지며 다시 기록된다.
- Phase : 사고발생 상을 표시한다. R, S, T상중 가장 먼저
TRIP이 발생한 사고상을 표시해준다.
- Volt : 사고발생시 입력된 사고 전압의 크기를 표시해준다.
- Type : 사고의 종류를 표시한다. 과전압/ 부족전압을 표시해
준다.
- Cyc : 사고전압 입력시(Pickup)부터 Relay Trip까지의 시간
을 Cycle로 표시해준다.
2. CLEAR FAULT MEM
[ F A U L T
C L E A R ]
C L E A R
F A U L T
R E C ?
▶
44
- 위의상태에서 LEFT KEY(◀)를 누르면 OV RELAY가 TRIP하
며, RIGHT KEY(▶)를 누르면 UV RELAY가 TRIP한다.
ESC KEY를 누르면 상위메뉴로 빠져나온다.
3. TEST SWITCH
[ S W I T C H
T E S T ]
[
]
<
h e r e
P r e s s & c h e c k
s w i t c h
[ E S C ] t o
Q U I T
T E S T
- 위의 메뉴상태에서 각 Key를 누르면[ ]부분에 눌러진 Key의 값
이 표시된다. CPU RESET과 MODE KEY를 제외한 각 키의 불
량 여부를 확인 할 수 있다.
ESC KEY를 누르면 상위메뉴로 빠져나온다.
SECURITY SET
� SECURITY SET 상세메뉴
[ S E C U R I T Y
P A S S W O R D
P A S S W O R D ]
[ * * * * ]
s e t ’ 0 0 0 0 ’ t o
[ N ]
방향키(▲, ▼)를 이용하여 Y, N을 선택 할 수 있으며 Y선택시 저
장되어진 모든 사고 데이터가 삭제된다.
DEESYS TOTAL PRODUCTS GUIDE
E L A Y
T E S T ]
T O
0 V
T R I P
] T O
U V
T R I P
o
Q U I T
T E S T
d i s a b l e
1. SECURITY PASSWORD
▶ 제품의 PASSWORD를 설정하는 부분이다.
- 패스워드를 사용하지 않는 경우 :“0000”
로 설정한다.
- 패스워드를 사용하는 경우 :“0001”
~”
9999”사이의 숫자를
입력한다.
[패스워드가 활성화 되고나면 MODE번튼을 누를 때 마다 패스
워드를 묻게 된다.]
- 패스워드를 잃어버렸을 경우 :“1183”
을 입력 한다.
[1183을 입력할 경우 패스워드가“0000”
으로 초기화 된다.]
Digital Over & Under Voltage Relay [59/27]3
MODEL ▶ DOU-D33-N(NON DRAW OUT)
▶ DOU-D33D-N(DRAW OUT)
RATING
Rated Voltage
AC 110V
Frequency
50/60Hz ± 5%
Burden
OV 2VA, UV 2VA
Element
[59] 3PHASE, [27] 3PHASE
Standard Code
IEC 255, KEMC 1120
Auxiliary Voltage
AC/DC 80~260V
Memory
Up to 10 records of Fault data
Communication
RS-485 Mod-bus Protocol
Ambient Temperature
-10。~ 60。(with no icing)
CONTACT
Output Relay
Trip 2c (OV, UV)
AC 240V 10A 0.5sec (R/L=0ms)
Make
DC 1000W 0.5sec (R/L=0ms)
Capacity
AC 240V 3A 0.5sec (R/L=0ms)
Break
DC 30W 0.5sec (R/L0ms)
INSULATION
Dielectric Withstand
2KV for 1minute between all terminal & case earth
Insulation Resistance
�100MΪ
Lightning Impulse Witihstand
5KV 1.2㎲ /50㎲
Surge Transient
2.5KV 1MHz/200Ϊ
(WithDC 500V Megger)
Positive/Negative 3Times
VOLTAGE SETTING
Over Voltage Range
100~160V (1.0V step)
Under Voltage Range
50~120V (1.0V step)
Instantaneous : 20~90V (1.0V step)
OPERATING TIME
Over Voltage
Inverse Time or Definite Time
Under Voltage
Inverse Time or Definite Time
TIME SETTING & CURVE
OV / UV Lever
0.1 ~ 40 Lever (0.1 step)
Instantaneous Time
Less than 50ms
OV / UV Definite Time
-0.85
� tp
Ⅴ2.4 -1
t = ( 12.15
+ 0.35) �
Ⅴ2 -1
t = tp
Resetting Value
Over Voltage : V�90%, Under Voltage : V�110%
Reset Time
Less than 100ms
UV Inverse Time
OV Inverse Time
V : % Voltage
(80% � 0.8)
(120% �
1.2)
tp : Time lever
t =
tp
10
DEESYS TOTAL PRODUCTS GUIDE
45
Digital Over & Under Voltage Relay [59/27]3
■ Block diagram
■ Wiring
■ Terminal arrangement
46
DEESYS TOTAL PRODUCTS GUIDE
Digital Over & Under Voltage Relay [59/27]3
Operating time curves
Under voltage relay
Over voltage relay
t= (
(Inverse time)
(Definite time)
(Inverse time)
(Definite time)
12.15
tp
+0.35) ×
V 2-1
10
DEESYS TOTAL PRODUCTS GUIDE
47
Digital Over & Under Voltage Relay [59/27]3
보호협조
Protective Coordination
전력 계통에 사용되는 계전기는 상위 계통에서부터 말단 부하에 이르
기까지 Level에 따라 협조가 이루어져야 합니다.
과전류 계전기의 적용시 고려해야 할 사항은 아래와 같습니다.
Protective relays would be coordinated with other relays in
the same system from main trunk line to end loads. Setting
values of each OCR/OCGR according to each protection level
is considered with following items.
1)보호구간 내에서의 단계별 단락 전류 산출.
2)보호구간 내에서의 단계별 과부하 전류 산출.
3)대용량 단위 설비의 열적 특성 확인.
4)전력용 변압기 등의 전압 초기 인가시 돌입전류와 시간특성 확인.
5)Power Fuse, ACB, MCCB등 한시 차단특성을 갖는 차단특성 확인.
6)기타 CT의 선정은 전문가와 협의함.
1) max. and minimum short currents(3 Phase to Ground) for
protection section.
2) Overload level
3) Heat endurance characteristics of large equipments like
Main transformer.
4) In-rush current during initial charge to large transformer.
5) Long time trip characteries of power fuse. ACB. MCCB and
etc.
6) Saturation characteries of CT applied.
상기 1~5 항의 Data를 근거로하여 정정값을 계산합니다.
상위계통에서부터 말단부하 선로에 이르기까지, 자기구간 사고시만 동
작되고, 타 구간 사고시에는 동작되지 않는 범위에서 정정합니다. 정정
을 위한 협조는 아래의 계통도 및 특성 곡선도에서 보호범위를 참조
하십시오.
In accordance with the data from the item 1 to 6, setting
values are calculated. While a relay is working at a line fault
correctly, other sections shall remain without anymaloperation. For protecting coordination, refer to the system
network and characteristic curve, as the below figures.
계전기 적용계통도
One Line Diagram
보호협조 예
Protecting coordination
F
P1
Device No.
ITEM
50/51
50N/51N
27
59
64
67
47
46/47/51/51N
OCEF
(3P4W)
OCGR
(EFR)
UVR
OVR
OVGR
DGR
POR
MPR 3E
MPR 4E
OCR
(2 phase)
(3 phase)
48
50/51,50N/51N
DEESYS TOTAL PRODUCTS GUIDE
Digital Over & Under Voltage Relay [59/27]3
개요
돌입전류
수전단의 차단기를 투입하면 구내 전기설비가 충전되어 과도전류가 흐릅
니다. 그러므로 ① 변압기의 여자돌입전류 ② 고압Condenser의 충전전
류에 대해서 수전단 OCR에 동작 영향을 고려해야 합니다.
변압기 여자돌입전류
변압기가 여자되지 않은 상태에서 1차측에 전압을 급격히 인가하면, 변압
기에는 역기전력이 발생해 있지 않기 때문에 철심의 자속이 일시적으로
포화되어 버립니다. 리액턴스분이 0 이되면, 변압기의 1차측이 단락된 것
과 동일한 상태이고, 과대전류가 과도적으로 흐릅니다.
제1차의 파고치는, 정격전류의 수배에서 수십배의 전류가 흐르기 때문에
peak 시간은 1~2Hz, 정격전류로 환원시까지는 2~3초 가량되는 경우도
있습니다. 이것을 여자돌입전류와 고압 콘덴서 충전전류를 참조하여 계전
기의 오동작 및 CB와의 보호 협조를 정확히 setting하여 주십시오.
In-Rush Current of Transformer(3∅)6,600V
Transformer cap.
type
oil filled transformer
mold transformer
Cap.
(KVA)
20
30
50
75
100
150
200
300
500
750
1,000
1,500
2,000
10
20
30
50
75
100
150
200
300
500
750
1,000
Rated
(A)
1.7
2.6
4.4
6.6
8.7
12.1
17.5
26.2
43.7
65.6
87.5
131
175
0.9
1.7
2.6
4.4
6.6
8.7
13.1
17.5
26.2
43.7
65.6
87.5
IN-Rush current(A)
0.01s
0.05s
0.1s
0.5s
1s
5s
28.3
43.3
64.8
76.0
94.7
117
146
218
308
462
616
755
896
15.6
27.2
41.6
62.0
88.7
111
151
190
252
420
504
616
16.8
25.7
4.05
47.5
59.2
77.0
95.6
146
212
325
433
542
672
9.2
16.2
24.7
38.7
55.4
73.1
99.0
125
169
295
354
443
12.8
19.6
21.4
36.8
45.8
60.5
75.1
119
178
274
366
472
616
7.0
12.3
18.9
30.0
43.0
57.4
77.8
98.2
138
249
299
385
5.7
8.8
14.2
16.6
20.7
27.5
34.1
57.9
86.5
137
183
259
364
3.2
5.5
8.5
13.6
19.4
26.1
35.4
44.6
66.8
125
150
212
4.2
6.4
10.1
11.9
14.8
20.2
25.0
40.0
62.5
101
135
189
252
2.3
4.0
6.2
9.7
13.9
19.1
25.9
32.7
47.2
91.8
110
154
1.9
2.9
4.7
6.6
8.7
13.0
17.5
26.2
43.7
65.6
87.5
131
175
1.0
1.8
2.8
4.5
6.6
8.7
13.0
17.5
26.2
43.7
65.6
87.5
In-Rush Current(A)
Cap. Rated
Cable
(KVA) (A)
Pick
10
0.9
2.6
t=0
149
6% Reactance
Cap.
t=0
Pick
0.9
-
-
0.005s 0.01s 0.02s 0.05s 0.1s
(KVA)
1.3
0.9
0.9
0.9
20
1.7
2.6
249
2.3
1.7
1.7
1.7
1.7
-
-
50
4.4
2.6
336
5.2
4.4
4.4
4.4
4.4
3
5.9
100
6.6
3.2
428
12.5
6.7
6.6
6.6
6.6
4.5
8.9
200
8.7
4
503
38.2
10.5
8.7
8.7
8.7
6
11.7
500
17.5
22
736
146
40.3
18.2
17.5
17.5
12 23.6
750
43.7
50
1,226
544
256
82.0
43.9 43.7
30 58.9
1,000
65.6
80
1,548
919
564
233
72.0 65.6
45 88.3
87.5
100
1,819
12,383
1,057
636
105 92.9
60
In-Rush Current
Once circuit breaker of receiving sector be passed with
power, enclosured facilites get into the state of in-rush.
There fore For
① exciting in-rush current of transformer occurs.
② relating for high voltage condencer charged.
they should be noted that receiving sector is under operating
effect.
Exciting In-Rush Current of Transformer
In the state of which transformer is not excited, once voltage
is suddenly applied to primary, as counter electromotive force
in transformer does not occur, core magnatic flux is
temporarily saturated.
In case that reactance is zero, primary of transformer is as in
the state of short circuit, transient current keeps over flowing.
Because peak value of primary wave passes several times to
several ten times of rated currents, it would, at the peak of
flowing time 1~2Hz, take 2 seconds to 3 seconds for getting
returned to rated currents. This is what we call "excitation inrush currents and currents protective coordination between
wrong-operating and circuit breaker shall be exactly set.
In considering with exciting in-rush currents and current
charged in high voltage condensers.
계산상의 조건
1. 전선길이 1km
2. 주파수 60Hz
3. 전압 6,600V
콘덴서에 선로상수를 통하여 전압의 파고치가 인가되는 경우의 과도전
류와, 정상상태로 흐를 경우의 교류전류를 가산하여 최대치를 표시합
니다.
Over current in case that peak value of voltage is applied by
use of line constant AC passing in normal state the above
overcurrent and altenating current add up to maximam value.
118
DEESYS TOTAL PRODUCTS GUIDE
49
Multi Function Over Current and Earth Fault Relay[50/51 3, 50/51N]
DOG-M51D
특징
Feature
이 다기능 과전류 계전기는 마이크로 프로세서 기술을 적용한 계전기
로서 3상 과전류 요소와 접지 과전류 요소를 가진 계전기입니다.
OCR과 OCGR는 독립적으로 정정 가능합니다. 보호협조는 (1)반한시,
강반한시, 초강반한시, 중 1개 요소와 순시 요소 또는 (2)정한시 적용
할 수 있습니다. 본 릴레이는 마이크로 프로세서 칩 및 A/D 컨버터등
최첨단 기술의 적용으로 기존의 기계식이나 정지형 보다 월등히 정밀
하고 정확히 동작합니다.
The multi-OCR is a microprocessor based digital type
protective relay that has 3 phases overcurrent and ground
overcurrent element which are provided with inverse, very
inverse, extremely inverse, and definite time, curkes. OCR
and GOCR can set the functions independently. The relay
may be supplied in drawout type case or fixed type case
according to customer's requirement. Its protceting
coordination is configured with (1) one of time inverse
curvesand instananuouse setting, or (2) definite time setting.
The relay works more precisely and correctly than
electmechanical type or static type, because of appling
advanced digital converting technology.
적용
Application
이 다기능 계전기는 직접접지 또는 저항접지 계통인 배전선로 보호 및
수용가의 수전 변전소의 feeder 보호용에 적용 할 수 있습니다. 계전
기는 다기능/광범위 정정이 가능하므로, 설계단계에서 정확하게 정정
치를 계산하지 않아도 되므로, 계전기 선택이 용이합니다.
The relay is suitable for solid or resistance grounded
distribution feeder of utility company or cosumer's substation.
Since the relay has multi-funtions and wide range settings. it
is no necessary for engineer to calculate in detail at the
beginning of design.
Front plate
50
DEESYS TOTAL PRODUCTS GUIDE
Multi Function Over Current and Earth Fault Relay[50/51 3, 50/51N]
IEC255 JEC 2500, 2510
DOG-M51(Non Draw out) / DOG-M51D(Draw out)
Specifications
●MODEL
DOG-M51(Non Draw out)
DOG-M51D(Draw out)
●Rating
Rated current
Frequency
Auxiliary Voltage
Ambient temperature
●Current setting
-OCOvercurrent range
Instantaneous
-EFOvercurrent range
Instantaneous
●Operating time
Over Current
Normal inverse time
AC 5A
50/60㎐±5%
AC/DC 110V(86~260V)
-10℃ to 60℃(with no icing)
∙Very inverse time
2~10A/steps of 0.5A
20~80A/steps of 0.5A
0.2~2A/steps of 0.05A
1~40A/steps of 0.5A
NI=
VI=
∙Extremely inverse time EI=
∙Definite time
D=
0.14
tp
10
tp
�
10
tp
�
10
tp ※I:Fault current(%)
10 ※tp:time lever
0.02-1 �
13.5
-1
80
2-1
2�
Resetting Value > 95%
Reset time
< 100㎳
●Burden
Overcurrent
Earth Fault
Aux Voltage
Very inverse time
Extremely inverse time
Instantaneous time
Degree Protection
Thermal Withstand
Capability
●Vibration resistance
Malfunction
●Shock resistance
Destruction;
for 1s 80xIn Continuously 3xIn
10㎐ 5mm double amplitude 30s
each in X and Y directions 16.7㎐
2.5mm double amplitude 600s each
in
X,Y, and Z directions
300㎨(approx. 30G) 3 time each in 3
directions
●Insulation to IEC 255
Dielectric withstand
0.5VA
0.5VA
12VA(AC),6W(DC)
●Contact
Output Relay
Trip 1c, Alarm 1a
Trip & Alam contact capacity
Make
AC 240V 10A(L/R=0ms)
DC 1000W 0.5Sec(L/R=0ms)
Break
AC 240V 3A(L/R=0ms)
DC 30W 0.5Sec(L/R=0ms)
●Indicator
Operating start
CPU RUN
Operating
Extremely inverse time
Earth Fault
Normal inverse time
●Time setting & curve IEC 255-3
-OCOvercurrent time lever
0.25~40(Steps of 0.25 lever)
Instantaneous
Less than 40㎳
∙Normal inverse time
Very inverse time
Lever #10
300% 6.3 sec
700% 3.5 sec
300% 6.75 sec
700% 2.25 sec
300% 10 sec
700% 1.67 sec
Lever #5
300% 3.15sec
700% 1.76sec
300% 3.37sec
700% 1.12sec
300% 5.0sec
700% 0.83sec
Lessthan 0.04sec
IP52
Insulation resistance at 500V
Impluse Voltage Withstand
Surge transient simulator
Weight
2kV for 1 minute between
all terminals and case
earthed.
>100㏁
5kV-1.2/50 ㎲
2.5kV 1MHz/200Ϊ
2.2kg
LED(Red)
LED(Gre)
LED(Red)Manual Reset
DEESYS TOTAL PRODUCTS GUIDE
51
Multi Function Over Current and Earth Fault Relay[50/51 3, 50/51N]
Over current and earth fault relay
52
DEESYS TOTAL PRODUCTS GUIDE
Multi Function Over Current and Earth Fault Relay[50/51 3, 50/51N]
전류 정정방법
Current Setting Mode
한시전류 정정
변류기 비율을 참조하여 계약전력의 150% 부근에 정정합니다.
Time limit Current setting
In consideration of current transformer ratio, setting shall
be conducted some where around contact demand 150%
TAP ≒
1 X 5
CT
X (1.1~1.5)
TAP ≒
TAP = 계전기의 정정 tap
CT = Rated current of primary in transformer
한시시간 정정
전력회사와 협조하여 정정하십시요.
순시전류 정정
변압기의 돌입여자전류로 인하여 오동작하지 않도록 1차, 2차의 보
호협조를 고려하여 정정하십시오. 일반적으로 변압기의 용량으로 계
산하여 전류치의 1,000~1,600에 정정합니다.
1 X 5
CT
X (10~16)
Time limit setting
Required to set current it cooperate with electric
corporation concerned.
Instantaneous current setting
Required to set power in consideration of primary and
secondary protective coordination so that wrong operating
fault can not occur due to exciting rush current of
transformer. Generally measuring capacity, setting shall be
done at 1,000~ 1,600%(current value)
TAP = 계전기의 정정 tap
‘
1
X (1.1~1.5)
= Current value of contact demand
1
CT = 변류기 1차 정격전류
TAP ≒
CT
TAP = Relay setting tap
= 계약전력 전류치(=계약전력(KW)/√
3X6.6(kv))
1
1 X 5
TAP ≒
= 계약전력 전류치(=계약전력(KW)/ 3X6.6(kv))
CT = 변류기 1차 정격전류
1 X 5
CT
X (10~16)
TAP = Setting tap
시험
1. 한시요소 시험시에 OC Test 스위치를 누르면 한시, 모든 순시 기
능을 할 수 있습니다.
2. 지락요소 시험시에도 E.F Test 스위치를 누르면 한시, 순시 기능
을 할 수 있습니다.
3. OC, EF 시험 및 동작표시 LED확인시에는 상시 전원전압을 연결
해야 합니다.
4. Setting Tap 눈금에 있는“Lock”기능은 계전기가 동작하지 않
는 위치이므로 시험후에는 정상위치로 돌려 놓으십시요.
‘
1
= Current value based on KVA
CT = Primary rated current of CT(Secondary Current 5A)
Test
1. When testing of time limit element. one touch of OC test
switch can perform both tests ,of time limit element and
instantaneous element
2. All the test of grounding element with only pushing EF
test switch, you can easily check the function of time limit
and instantaneous element.
3. For OC and EF test and confirmation of operating
indicator LED, you shall keep constant power voltage
connected.
4. "Lock" on setting tap scale is the position where relay
does not operate, after the test you shall get it back to
ordinary position.
Indication
Fault Part
Discription
Operating Indicator
Phase
R-S
Over
Current
Instantaneous
overcurrent
Earth
Fault
Over Current
R
S
●
●
S-T
T-R
●
●
●
●
R-S
●
●
S-T
●
●
R.S.T
●
T
INST
OC
INST
●
●
R.S.T
T-R
Earth Fault
●
●
●
●
●
●
●
●
●
N
●
Instantaneous
●
●
DEESYS TOTAL PRODUCTS GUIDE
53
Multi Function Over Current and Earth Fault Relay[50/51 3, 50/51N]
동작특성 설명
Operating Characteristics
전면판의 모든 S/W는 Dip-Switch로 구성되어 있습니다.
All switchs of front plate for relay are installed dip switdh
Tripping time curve(CO)
DE (Definite time)
NI (Normal inverse)
VI (Very inverse)
EI (Extremely inverse)
Tripping time curve(CO)
DE (Definite time)
NI (Normal inverse)
VI (Very inverse)
EI (Extremely inverse)
Please select each curve as changing over the dip switch
dip switch를 전환하여
각 curve를 선택합니다.
Over current setting
한시전류는 2~10A로 구성되어 있고 0.5 A step으로 정정 가능합니
다. Dip switch는 ON-OFF로 구성되어 있고 ON사용시에 정정범위가
설정됩니다. 정정방법은 전면판에 수록되어 있고 값을 ON하였을 경우
모두 더하면 (∑) setting값을 설정됩니다.
Over current setting
The definitive current tap is limited for 2A to 10A and the
tap is divided 0.5 step.
Dip switch has ON-OFF position and it is able to set the
setting range in case of“on”position
Please refer to front plate how to set.
But if you set setting current, you should plus the value of
on position
Is=2+1.0+2.0=5(A)
※ Lock위치로 ON-setting하면 ON기능이
동작하지 않습니다.
Time lever setting
Time lever는 0.25~40으로 0.25step단위로 setting 가능합니다.
Time lever setting
Time lever is limited from 0.25 to 4.0 sec and the tap is
divided 0.25 step
Ts=0.25+0.25+0.5+1.0+1.5+2.5+4.0
=10 lever
Instantaneous current setting
Inst, current는 20~80A로 정정되며 5A step으로 setting 가능합니
다.
Instantaneous current setting
The tap of instantaneous current is limited from 20A to 80A
and the tap is divided 5A step.
Is=2+1.0+2.0=5(A)
※ Lock위치로 ON-setting하면 ON기능이
동작하지 않습니다.
54
DEESYS TOTAL PRODUCTS GUIDE
If the dip switch is set on lock position, the instantaneous
function is not operated.
Multi Function Over Current and Earth Fault Relay[50/51 3, 50/51N]
Trip indicator
내부의 Relay가 동작하며 아래 각부의 동작상태를 LED Lamp로 확
인 가능합니다.
Trip indicator
when the aux relay is operated, it is able to confirm
operating status of following parts and LED LAMP.
Line check
Line Check Switch를 누르면 각상에(T,EF) 흐르는 부하전류를 알 수
있습니다.
Line check
Push the line check switch, you can see the load current
of each phase (T,EF)
Fault check
사고로 부터의 신호가 발생하면 시간 경과후 CB가 차단하게 됩니다.
이때 사고의 상태(CT2차 전류)를 Display하는 동시에 사고 전류를
Memory합니다. 전원 또는 Line OFF후에도 S-RAM이 동작하기 때
문에 사고의 상태를 전원 재투입 후에도 Memory하고 있습니다.
Momory Reset을 할 경우에는 Line check S/W와 Fault check
S/W를 동시에 누르면 Momory가 소거됩니다.
Fault check
When there are some fault, the circult breaker will be
shutdown after a few second. At that time, the status of
fault(2ry current of CT) will be displayed and the current
value of fault will be memoried due to operating S-RAM.
After aux power turn off, the status of fault is memoried
due to operating S-RAM
In order to reset memory function, please push line check
S/W and fault check S/W at the same time, and value of
memory will be detected.
Pick-up count
동작이 시작되면 count를 display에 표시하여 주기 때문에 동작 시간
상태를(%) 알 수 있습니다.
Pick-up count
On operating pick up count, it is able to see the time of
trip operating(%) due to display the trip time counter
Set check
각 설정한 Tap의 표시가 Display에 나타나기 때문에 각 setting tap
에 대한 설정 확인이 가능합니다.
Set check
It is able to confirm each setting tap value due to display
the setting value an display window.
OC tset & EF test
한시(CO) 기능을 자체 test 할 수 있어 Relay의 동작여부를 알 수 있
습니다.
test시 time lever의 setting시간과 동일하게 동작하므로 동작시간
curve의 상태가 동시에 check됩니다.
OC tset & EF test
It is able to confirm the status of relay operating by the
relay the function(CO.)
The time setting of time lever and the operating time curve
will be checked at the same time on testing
If the run lamp is not operated, please push the reset
button.
Run
Power부의 전원 감시 및 CPU의 동작이상 상태감시를 하고 있습니
다. RUN lamp On시 정상상태. (Run lamp OFF시 Error상태) 만약
RUN표시 lamp가 동작하지 않을 경우에 Reset Button을 눌러 주십
시오.
Run
On run position, it is indicated the status of power source
and the operating status of CPU. (when run lamp turn on, it
is good condition, and when run lamp turn off, it is error
condition)
Block diagram
DEESYS TOTAL PRODUCTS GUIDE
55
Multi Function Over Current and Earth Fault Relay[50/51 3, 50/51N]
Block diagram
Non draw out
Draw out
Terminal arrangment
Non draw out
Draw out
Terminal arrangement
Digital type draw out
56
DEESYS TOTAL PRODUCTS GUIDE
Cutting Size: 165 X 122mm
Over Current Relay [50/51 2] [50/51 3]
DOC-M32D , DOC-M42D
특징
Characteristics
기능
C.P.U를 내장하여 고신뢰도 및 정확도를 만족시키기 위해 MICOM화
하였습니다. Digital방식에 의한 고정밀화로 기능에 안정성을 실현하였
습니다. 자기감시기능을 채택하여 고장유무상태를 보다 신뢰성있게 향
상 시켰습니다. Multi function으로 표시 및 다기능에 충실하였습니다.
Function
Computerized by having C. P. U built-in the function to
high reliability and accuracy and stabilized sopisticated
function through digital system.
Easy detection of malfunction with self-checking set.
Convenient operation, based on multifunction. As target
was installed, overload and short circuit can be clearly
detected phase by phase.
표시선택
상시부하전류가 계측이 되어 Metering의 표시가 가능합니다. 정정치의
식별이 가능하여 setting후 정확한 위치가 표시됩니다. 유도 원판형의
회전표시에 대응하는 동작상태의 time counter가 표시되어 동작상태의
확인이 가능합니다.
구조
EMC에 대응하여 case구조 및 내부회로를 특수설계하여 고신뢰성을
확보하였습니다.
인출, 비인출형 구조로 되어있어 시공 및 현장 시험시 편리합니다.
계전기 인출시 CT회로 개방에 대한 대책이(Short bar)되어있어 CT의
소손을 방지할 수 있습니다.
Front plate
Display
Convenient meter scale indicates the load state of currents
passing all the time. Setting value of operating current is clearly
discernable and correct position, also detectable after setting.
With time counter setting it can surely confirm operating
condition. Based on test SW, easy check-up can be
performed.
Construction
Case construction corresponding to EMC and inner circuit
was specifically designed for ensuring high reliability.
Drawout and non-draw out type was so well constructed
that setting and field test can be conveniently performed.
When drawing out, short bar keeps CT circuits from burning
down.
1. Current Display / Operating Count
2. Curr. Limits Element
3. Time Lever Element
4. Instantaneous Element
5. R-Phase Indicator
6. S-Phase Indicator
7. T-Phase Indicator
8. Over current Start Indicator
9. Power Lamp LED
10. CPU Run Indicator
11. Monitor Selection Switch
12. Time curve Selection Switch
13. Setting Check
14. Test
15. Fault Indicator
16. Draw-out Handle
17. Reset
DEESYS TOTAL PRODUCTS GUIDE
57
Over Current Relay [50/51 2] [50/51 3]
IEC255 JEC 2500, 2510
DOC-M32(Non Draw out)
DOC-M32D(Draw out)
DOC-M42(Non Draw out)
DOC-M42D(Draw out)
2 phase
2 phase
3 phase
3 phase
Specifications
●MODEL
DOC-M32(Non Draw out)
DOC-M32D(Draw out)
DOC-M42(Non Draw out)
DOC-M42D(Draw out)
2
2
3
3
●Rating
Rated current
Frequency
Auxiliary Voltage
Ambient temperature
Indicator
Operating start
CPU RUN
Operating
phase
phase
phase
phase
AC 5A
60/50㎐±5%
AC/DC 110V(86~260V)
-10℃ to 60℃(with no
icing)
●Current setting
Overcurrent range
2~10A Lock(Steps of
0.5A)
20~80A Lock(Steps of
5A)
Instantaneous range
●Time setting & curve IEC 255-3
Overcurrent time lever
0.25~40(Steps of 0.25)
Instantaneou
Less than40ms
(over 200%)
NI=
∙Very inverse time
VI=
∙Extremely inverse time
EI=
∙Definite time
DE=
Resetting Value
Reset time
> 95%
< 100ms
●Burden
Overcurrent
Aux Voltage
Break
DEESYS TOTAL PRODUCTS GUIDE
0.02-1 �
13.5
-1
80
2-1
2
�
�
�
tp
10
tp
10
tp
10
tp
10
0.5VA
12VA(AC),6W(DC)
●Contact
Output Relay
Trip & Alam contact capacity
Make
58
0.14
∙Normal inverse time
Trip 1c, Alarm 1a
AC 240V 10A(L/R=0ms)
DC 1000W0.5sec(L/R=0ms)
AC 240V 3A(L/R=0ms)
DC 30W 0.5sec(L/R=0ms)
LED(Red)
LED(Gre)
LED(Red)
●Operating time
Over Current
Normal inverse time
Very inverse time
Extremely inverse time
Instantaneous time
Degree Protection
Thermal Withstand Capability
●Vibration resistance
Malfunction
●Shock resistance
Destruction;
●Insulation to IEC 255
Dielectric withstand
Insulation resistance at 500V
Impluse Voltage Withstand
Surge transient simulator
Weight
Lever #10
300% 6.3 sec
700% 3.5 sec
300% 6.75 sec
700% 2.25 sec
300% 10 sec
700% 1.67 sec
300%
IP52
for 1s 80xIn Continuously
3xIn
10㎐ 5mm double
amplitude 30s each in X
and Y directions
16.7㎐ 2.5mm double
amplitude 600s each in
X,Y, and Z directions
300㎨(approx. 30G)3 time
each in 3 directions
2kV for 1 minute between
all terminals and case earth
>100㏁
5kV-1.2/50 ㎲
2.5kV 1MHz/200Ϊ
2kg
Over Current Relay [50/51 2] [50/51 3]
Operating time curves
Normal Inverse
Very Inverse
Extermely Inverse
Definite Time
DEESYS TOTAL PRODUCTS GUIDE
59
Over Current Relay [50/51 2] [50/51 3]
전류정정 방법
Current Setting Mode
한시 전류 정정
변류기 비율을 참조하여 계약전력의 150% 부근에 정정합니다.
Time limit current setting
In consideration of current transformer ratio, setting shall
be conducted some where around contract demand 150%
TAP ≒
1 X 5
CT
X 1.5
TAP ≒
TAP = 계전기의 정정 TAP
= 계약전력의 전류치(=계약전력 (kw)/√
3×6.6(kv)
1
1 X 5
CT
X 1.5
TAP = Relay setting tap
1
CT = 변류기 1차 정격전류
= Current value of contact demand
CT = Rated current of primary in transformer
한시시간 정정
전력회사와 협조하여 정정하십시요.
Time limit setting
Required to set current it cooperate with electric
corporation concerned
순시전류 정정
변압기의 돌입여자전류로 인하여 오동작하지 않도록 1차, 2차의 보호
협조를 고려하여 정정하십시오. 일반적으로 변압기의 용량으로 계산하
여 전류치의 1,000~1,600%에 정정합니다.
Instantaneous current setting
Required to set power in consideration of primary and
secondary protective coordination, that wrong operating
fault can not occur due to exciting in-rush of transformer.
Generally measuring capacity, setting shall be done at
1,000~1,600(current value)
TAP ≒
1 ′
X5
CT
X (10~16)
TAP = 계전기 정정 APT
‘
1
= 변압기의 용량(KVA)에 의해 계산된 전류치
CT = CT 1차 정격전류(2차 전류는 5A)
TAP ≒
1 ′
X5
CT
X (10~16)
TAP = Setting tap
‘
1
= Current value based on KVA
CT = Primary rated current of CT(Secondary Current 5A)
Dependent-time element current setting
Contract
CT Primary current(A)
demand
5
10
15
20
30
40
50
75
100
150
200
300
(kw)
(A)TAP α(%) (A)TAP α(%) (A)TAP α(%) (A)TAP α(%) (A)TAP α(%) (A)TAP α(%) (A)TAP α(%) (A)TAP α(%) (A)TAP α(%) (A)TAP α(%) (A)TAP α(%) (A)TAP α(%)
3
136
50
6
136
3.5 159
3.5
121
3
138
4
138
100
6
138
4.5 155
3.5
161
5
172
3.5 120
3
137
4
137
3
171
200
6
137
4.5 154
3.5 160
5
171
4
122 3.5 134
6
137
4.5
137 4
153 3
172
300
5
153 4.5 172
3.5 120
3
137
6
137 4
137
500
4.5 154
3.5 160
5
171
750
1,000
1,500
60
DEESYS TOTAL PRODUCTS GUIDE
6
137
4
4.5
5
122
137
153
6
137
3
137
3.5
160
3.5
4
4.5
5
120
137
154
171
6
137
3
137
3.5
160
4
4.5
5
122
137
153
3
137
3.5
160
Over Current Relay [50/51 2] [50/51 3]
동작특성 설명
Characteristics
1. 선로의 과부하 및 단락전류가 외부의 변류기를 통하여 본계전기의
입력단자에 흐르면 계전기 내부에 있는 각상에 대한 검출용과 전원
용 CT에 입력이 됩니다.
2. 검출된 회로에서는 입력레벨의 Filter를 거쳐 A/D컨버터와 마이크
로 프로세서에 의해 고장처리 및 동작표시기를 동작시켜줍니다.
3. 레벨 판정연산은 각상에 따른 사고(과부하, 단락)를 판정하여 각상
의 고장상태를 표시합니다.
표시기능 : 1)전류계측 2)시동 및 경과시간 3)각정정탭표시
1. In case overload or short circuit current is fed to input
terminals of the relay from external transformer, the current
will then flow to built-in transducers for phase current
detection and power supply.
2. In the detection circuit, signal current of different by
microprocessor to determine if the signal level reached
pick up point to activate the relay.
3. The level deciding operation finds out faulty phase
(overloaded, two phase short, or three phase short) line
and indicates the by target of repective phase.
The Function Includes indication of: 1) current measurement.
2)start and time elapse, and 3)value of set tap.
전류계측
각상에 흐르는 전류신호를 데이터 처리하여 전류계측 연산을 하여 상
에 흐르는 전류중 가장 높은상의 전류를 FND에 표시하여 주고 0.1A
이상부터 동작하여 표시합니다.
시동 및 경과시간
동작이 시작되면 카운트를 시작합니다. 이때 0~9까지의 경과시간을
두고 동작되며, 동작시작을 표시하는 operating start LED가 점멸
되어 동작진행을 알수 있습니다.
각 정정탭 표시
계전기의 정정 장치를 표시하는 기능으로 한시전류정정(A) 한시시간
정정(TAP)의 위치를 확인할 수 있습니다.
Indication
Indicator
Circuit Trouble
over current
2Phase
instantaneous
RS
ST
TR
RST
RS
ST
TR
RST
R
●
…
●
●
●
…
●
●
S
…
…
…
…
…
…
…
…
Current measurement
The current of phase are date processed and operated for
measurement of the currents. Only the largest current
among phases but within the range of 0.2A and up to set
value immediately before pick-up level is indicated by LED.
Start and time elapse
In case set value for start time limit is exceeded before
starting, the indication turns to zero (0)which infer that the
relay might activate to break in any moment. The time
elapse is displayed counting from 0 tp 9 according to the
2 Phase
level of current and at the moment display of 9 turns to 10,
Trip
the relay trips momentarily. At this instance, operating start
T
Instantaneous
lamp (red LED) warns the operation by binking that time
…
…
elapse lamp (red LED) warns the operation be pinking that
●
…
time elapse nearing trip is visibly noticeable.
●
●
…
●
●
●
…
●
●
●
●
Confirmation display of set values
The display indicates set values of OCR so that set values of
time limit current(A) and time limit time(TAP) can be confirmed.
Block diagram
3 Phase
Indicator
Circuit Trouble
over current
2Phase
instantaneous
RS
ST
TR
RST
RS
ST
TR
RST
R
●
●
●
●
…
●
●
S
●
●
●
●
●
…
●
Trip
T
Instantaneous
…
●
…
●
…
●
…
…
●
●
●
●
●
●
●
DEESYS TOTAL PRODUCTS GUIDE
61
Over Current Relay [50/51 2] [50/51 3]
Wiring
Non draw out
Draw out
Non draw out
Draw out
Terminal Arrangement
Non draw out
Draw out
Non draw out
Draw out
Dimension
Case : ABS 난연성(Non flamable)
Digital type draw out
62
DEESYS TOTAL PRODUCTS GUIDE
Color : Black(N1.5)
Cutting Size: 165 X 122mm
Ground Over Current Relay (Earth Fault Relay)[50/51N]
DCG-M22D
특징
Feature
이 접지 과전류 계전기는 마이크로 프로세서 기술을 적용한 접지 요소
를 가진 계전기 입니다. 보호협조를 위하여
1. 반한시, 강반한시, 초반한시 곡선중 1요소와 순시요소를 조합하여
정정하거나
2. 정한시 요소를 단독으로 적용 할 수 있도록 선택 할 수 있습니다.
이 계전기는 A/D컨버터 및 CPU를 내장하고 있기 때문에 일반 정
지형이나 기계식에 비하여 월등히 정확하고 신속하게 동작합니다.
The OCGR is a microprocessor based digital type protective
relay that has ground overcurrent detecting elements. For
protecting coordination, it could be applied with:
1. Instant. GOC with one of normal inverse, very inverse, and
extremely inverse curves or
2. Alone with definite time
Since a fault level is treated by A/D converter and
calculated by CPU, the fault detected, is more correct and
precise than E/M type or static type.
적용
Application
이 접지 과전류 계전기는 직접접지 또는 저항접지계통에 적용 할 수
있으며, 정정범위가 넓어 설계단계에서도 리레이 선택이 용이 합니다.
The OCGR is applied to solid ground or resistance ground
network. More-over the relay could be chosen at the
begining of design stage, since its adjustable range is
wider than other relays.
Front plate
1. Current Display / Operating Count
2. Curr. Limits Element
3. Time Lever Element
4. Io Element
5. Pick up Start Indicator
6. Power Indicator
7. CPU RUN Indicator
8. Monitor Select
9. Setting verify
10. Test Switch
11. Time curve Position Select
12. Operating Indicator(oc)
13. Operating Indicator(inst)
14. Reset Switch
15. Draw-out Handle
DEESYS TOTAL PRODUCTS GUIDE
63
Ground Over Current Relay (Earth Fault Relay)[50/51N]
IEC255 JEC 2500, 2510
DCG-M22(Non Draw out)
DCG-M22D(Draw out)
Specification
◆MODEL
DCG-M22(Non Draw out)
DCG-M22D(Draw out)
◆Rating
Rated current
Frequency
Auxiliary Voltage
Ambient temperature
◆Current setting
Overcurrent range
Instantaneous range
◆Operating time
Over Current
Normal inverse time
AC 5A
60/50㎐±5%
AC/DC 110V(86~260V)
-10℃ to 60℃(with no icing)
0.2~2A Lock(Steps of 0.05A)
1~40A(Steps of 0.5A)
0.25~40(Steps of 0.25)
Less than 40ms(over
200%)
∙Normal inverse time
NI=
∙Very inverse time
VI=
∙Extremely inverse time
EI=
0.14
13.5
-1
80
2-1
2
DE=
Resetting Value
Reset time
> 95%
< 100ms
Break
LED(Red)
LED(Gre)
DEESYS TOTAL PRODUCTS GUIDE
◆Vibration resistance
Malfunction
tp
tp
10
tp
�
10
tp
�
10
�
0.5VA
12VA(AC),6W(DC)
◆Contact
Output Relay
Trip & Alam contact capacity
Make
Degree Protection
Thermal Withstand Capability
0.02-1 �10
∙Definite time
◆Burden
Overcurrent
Aux Voltage
64
Extremely inverse time
Instantaneous time
◆Time setting & curve IEC 255
Overcurrent time lever
Instantaneous
Indicator
Operating start
Operating
Very inverse time
Trip 1c, Alarm 1a
AC 240V 10A(L/R=0ms)
DC 1000W 0.5Sec(L/R=0ms)
AC 240V 3A(L/R=0ms)
DC 30W 0.5Sec(L/R=0ms)
◆Shock resistance
Destruction;
◆Insulation to IEC 255
Dielectric withstand
Insulation resistance at 500V
Impluse Voltage Withstand
Surge transient simulator
Weight
Lever #10
300% 6.3 sec
700% 3.5 sec
300% 6.75 sec
700% 2.25 sec
300% 10 sec
700% 1.67 sec
Iess then 0.04 sec(200%
overcurrent)
IP52
for 1s 80xIn Continuously
3xIn
10㎐ 5mm
double
amplitude 30s each in X
and Y directions
16.7㎐ 2.5mm double
amplitude 600s each in
X,Y, and Z directions
300㎨(approx. 30G) 3
time
each
in
3
directions
2㎸
for 1 minute
between all terminals
and case earth
>100㏁
5kV-1.2/50 ㎲
2.5kV 1MHz/200Ϊ
2.0kg
Ground Over Current Relay (Earth Fault Relay)[50/51N]
Operating time curves
Normal Inverse
Very Inverse
Extermely Inverse
Definite Time
DEESYS TOTAL PRODUCTS GUIDE
65
Ground Over Current Relay (Earth Fault Relay)[50/51N]
접지계산 방법
Calculation
● 중성점을 직접 도체로 접지하는 방식으로서 1선 지락전류는 단락전
류와 등가이다. 그러므로 다른 접지방식에 비하여 지락전류가 가장
크며 지락사고시 중심점의 전위 변화는 매우 적다. 따라서 변압기
및 전로의 절연강도를 내릴 수 있어 경제적이나 유도장해가 매우
커서 고속도차단이 필요하다. 또한, 고장전류가 많아서 계전기가 확
실하게 동작할 수 있고 신뢰도가 가장 높아 고압 계통에서 이 방식
이 많이 채택되고 있다.
● As a mode that neutral point grounds by means of
conductor directly, one wire earthing current is equal to
short current. So earth current is the largest one
comparing with other grounding method. In case of earth
fault time, the electric potential is very small. Accordingly,
this can decrease insulation intensity level of transformer
and power line, also be economical. But inductive
disturbance is very serious problem. Therefore high speed
circuit breaking should be instantly taken. Also this method
is adapted in measurement of high voltage because of
high reliability.
● 예를들어 6,600V의 중성점에 NGR 38Ω의 저항을 사용하였을 경
우에 1선 지락전류를 계산하여 보면
3Ea
6,600
Ea=
Zo
√3
Zo = 3RN = 3×38
(3 은 영상회로는 1선분의 전류를 다루는데 반해 RN에는
3선분의 전류가 흐르기 때문이다.)
3Ea
3×6,600/ √
3
∴Ig=
Ea=
= 100A
Zo
3×38
Ig=
● Example 6,600V Neutral NGR 38Ω Resistance
3Ea
6,600
Ea=
Zo
√3
Zo = 3RN = 3×38
(3 RN is accountable for 1 line zero phase,
and to RN flowes 3 lines zero phases.)
3Ea
3×6,600/ √
3
∴Ig=
Ea=
= 100A
Zo
3×38
Ig=
Block diagram
Ig = ground fault current
Wiring
Non draw out
Terminal arrangement
Non draw out
Demension
Digital type draw out
66
DEESYS TOTAL PRODUCTS GUIDE
Draw out
Draw out
Case : ABS 난연성(Non flamable)
Color : Black(N1.5)
Cutting Size: 165 X 122mm
Multi Function Over and Under Voltage Relay[59/27]
DOU-M22D
[ 1∅ ]
[ 3∅ ]
특징
Characteristics
● 종래의 과전압, 부족전압을 별도의 계전기로 사용하던 것을 과, 부
족 전압을 1대의 계전기에 내장하였습니다.
● 고정밀 기능과 다기능의 조합으로 보호협조 및 수배전단의 적용에
최적입니다.
● 계전기 전면에 정밀 Volt meter가 설치되어 있어 계측용으로 가능
합니다.
● 전자식 동작표시기 및 LED가 부착되어 있어 정전 및 사고상태의
판별이 명확히 표시됩니다.
● Up to now OVR and UVR relays were separately set and
also operated but they are compacted in one relay unit.
So very convenient for handling too.
● As assembled with state of art and multifunctions, it is most
suitable and applicable to protective coordination.
● Volt meter being installed, it can be used fer measuring
● Electronic indicator target accurately show the troubles
and surely indicate electric trouble.
Front plate
1. Voltage Display / Operating Count
2. Voltage Limits Element
3. Time Lever Element
4. Instantaneous Element
5. Over Voltage Setting Element
6. Time Lever Element
7. Monitor Selection Switch
8. Over & Under Voltage State
9. CPU Run LED
10. Under Voltage Curve Setting
11. Over Voltage Curve Setting
12. Under Voltage Test
13. Over Voltage Test
14. Target
15. Draw-out Handle
DEESYS TOTAL PRODUCTS GUIDE
67
Multi Function Over and Under Voltage Relay[59/27]
IEC255 JEC 2500, 2511
Model
DOU-M22(Non Draw out)
DOU-M22D(Draw out)
Specifications
◆MODEL
DOU-M22(Non Draw out)
DOU-M22D(Draw out)
◆Operating time
Over Voltage
Under Voltage
Degree Protection
◆Rating
Rated Voltage
Frequency
Auxiliary Voltage
Ambient temperature
AC 110V
60/50㎐±5%
AC/DC 110V(80~260V)
-10℃ to 60℃(with no icing)
◆Voltage setting
Over Voltage range
Under Voltage range
115~150V/(Steps of 5V)
20~100V/(Steps of 5V)
◆Time setting & Curve Definite time or Inverse time
Over Voltage time lever
0.05~10.3(steps of 0.05)
0.05±25ms, 0.1~10S±10%
Under Voltage time lever
0.05~10.3(steps of 0.05)
0.05±25ms, 0.1~10S±10%
Under Voltage Instantaneous
20~80V(Steps of 5V)
Resetting Value
OV:V<95%, UV:V> 105%
Reset time
< 100ms
◆Burden
Over Voltage
Under Voltage
Aux. Voltage
Less than 2VA
Less than 2VA
12VA(AC), 6W(DC)
◆Contact
Out put Relay
Trip & contact capacity
Make
Break
◆Indicator
Operating start
Operating
68
DEESYS TOTAL PRODUCTS GUIDE
OV : 1C / UV : 1C
AC 240V 10A(L/R=0ms)
DC 1000W
0.5Sec(L/R=0ms)
AC 240V 3A(L/R=0ms)
DC 30W
0.5Sec(L/R=0ms)
LED(Red)
LED(Red)
◆Vibration resistance
Malfunction
◆Shock resistance
Destruction;
◆Insulation to IEC 255
Dielectric withstand
Insulation resistance at 500V
Impluse Voltage Withstand
Surge transient simulator
Weight
Inverse or definite time
Inverse or definite time
IP 52
10㎐
5mm double
amplitude 30s each in X
and Y directions
16.7㎐ 2.5mm double
amplitude 600s each in
X,Y, and Z directions
300㎨ (approx. 30G)
3 time each in 3
directions
2kV for 1 minute
between all terminals
and case earth
>100㏁
5kV-1.2/50 ㎲
2.5kV 1MHz/200Ϊ
2.0kg
Multi Function Over and Under Voltage Relay[59/27] 3
IEC255 JEC 2500, 2511
DOU-M33
DOU-M33D
DOV-M33
DOV-M33D
DUV-M33
DUV-M33D
[59/27] 3∅ (Non Draw out)
[59/27] 3∅ (Draw out)
[59] 3∅ (Non Draw out)
[59] 3∅ (Draw out)
[27] 3∅ (Non Draw out)
[27] 3∅ (Draw out)
Specifications
◆Rating
Rated Voltage
Frequency
Auxiliary Voltage
Ambient temperature
AC 110V
60/50㎐±5%
AC/DC 110V(80~260V)
-10℃ to 60℃(with noicing)
◆Voltage setting
Over Voltage range
Under Voltage range
100~160V/(steps of 5V)
50~120V/(steps of 5V)
LED(Red)
LED(manual Reset)
◆Operating time
Over Voltage
Under Voltage
Degree Protection
Inverse or definite time
IP 52
◆Vibration resistance
Malfunction
◆Time setting & Curve
Over Voltage time
Under Voltage time
Instantaneous time
Reset Value
Reset time
INST. 0.1~10(steps of 0.1)±10%
INST. 0.1~10(steps of 0.1)±10%
Less than 60ms
OV:V<95%, UV:V> 105%
Less than 100ms
◆Burden
Over Voltage
Under Voltage
Aux. Voltage
Less than 2VA
Less than 2VA
12VA(AC), 6W(DC)
◆Contact
Output Relay
◆Indicator
Operating start
Operating(Trip)
DOU-M33/M33D Trip 2c(OV,UV)
DOV-M33/M33D Trip 1c.Alarm 1a
DUV-M33/M33D Trip 1c.Alarm 1a
Trip & contact capacity
Make
AC
DC
Break AC
DC
240V 10A(L/R=0ms)
1000W 0.5Sec(L/R=0ms)
240V 3A(L/R=0ms)
30W 0.5Sec(L/R=0ms)
◆Shock resistance
Destruction;
◆Insulation to IEC 255
Dielectric withstand
Insulation resistance at 500V
Impluse Voltage Withstand
Surge transient simulator
Weight
10㎐
5mm double
amplitude 30s each in X
and Y directions
16.7㎐ 2.5mm double
amplitude 600s each in
X,Y, and Z directions
300㎨(approx. 30G) 3
time
each
in
3
directions
2kV for 1 minute
between all terminals
and case earth
>1,000㏁
5kV-1.2/50 ㎲
2.5kV 1MHz/200Ϊ[IEC 255-6]
2.2kg
DEESYS TOTAL PRODUCTS GUIDE
69
Multi Function Over and Under Voltage Relay[59/27] 1 , 3
Operating time curves
Under voltage relay
Over voltage relay
70
DEESYS TOTAL PRODUCTS GUIDE
(Inverse time)
(Definite time)
(Inverse time)
(Definite time)
Multi Function Over and Under Voltage Relay[59/27] 1
Block diagram
Wiring : Dou-M22, 22D
Non draw out
Draw out
※ Aux, Power는 별도의 AC/DC 100V를 사용하십시요
Terminal arrangement
Non draw out
Block diagram
Draw out
DEESYS TOTAL PRODUCTS GUIDE
71
Multi Function Over and Under Voltage Relay[59/27] 3
Wiring
V-Connection 110V
Y-Connection 110V
Terminal Arrangement
Non draw out
Draw out
√
Y-Connection190V/ 3
Demension
Case : ABS 난연성(Non flamable)
Digital type draw out
72
DEESYS TOTAL PRODUCTS GUIDE
Color : Black(N1.5)
Cutting Size: 165 X 122mm
Over, Under Voltage Relay[59], [27] 1
DOV-M15D, DUV-M20D
개요
Introduction
이상 전압에는 발전기의 고장으로 인해 전압의 급상승과 정전시 또는
단락시에 전압이 저하됩니다. 전압계전기는 교류회로의 전압변동에 대
응하여 전압을 미리 정정하여 놓고 정정치 이상이 되면 검출하여 동작
하는 계전기 입니다.
In abnormal voltage condition, voltage shall be dropped
because of sudden increasing voltage due to generator's
fault and power off or short circuit time.
Normally, voltage relay setting shall be done priorly against
the voltage variation.
When voltage become over the setting value, voltage relay
shall be operated.
특징
Characteristics
● 고정밀 반도체로 내부회로를 구성하여 반영구적으로 사용이 가능
하며 진동이나 충격에 오동작할 염려가 없습니다.
● A/D Converter 회로를 구성하여 입력전압을 FND로 Display
함으로 Volt Meter 대용으로 사용 가능합니다.
● 사고를 정확하게 표시하는 Target을 부착하였습니다.
● 소비 전력이 적어서 PT의 부담이 적어도 되므로 경제적입니다.
● Control voltage is obtained from power transformer
secondary without requiring any separate source of power
supply that system configuration wiring and handling are
convenient.
● Internal circuit constructed of semiconductors offer
semipermanent sevice life without worries for
malfunctioning caused by mechanical vibration and
shocks.
● A/D converter circuit offers digital display of input
voltages(substitutes AC voltmeter)
● Target shall show the fault condition accurately.
● Due to low power consumption and low burden of PT, this
relay is economical.
Front plate
1. Voltage Display / Operating Count
2. Voltage Limits Element
3. Time Lever Setting Element
4. Instantaneous Element
5. Under Voltage Test
6. Monitor Selection Switch
7. Under Voltage Curve Setting
8. Operating Start LED
9. CPU Run LED
10. Target
11. Draw-out Handle
DEESYS TOTAL PRODUCTS GUIDE
73
Over, Under Voltage Relay[59], [27] 1
IEC255 JEC 2500, 2510
DOV-M15(Non Draw out)
DOV-M15D(Draw out)
DUV-M20(Non Draw out)
DUV-M20D(Draw out)
Specifications
● Indicator
Operating start
Operating(trip)
● Model
DOV-M15(Non Draw out)
DOV-M15D(Draw out)
DUV-M20(Non Draw out)
DUV-M20D(Draw out)
● Rating
Rated Voltage
Frequency
Auxiliary Voltage
Ambient temperature
● Voltage setting
Over Voltage range
Under Voltage range
Under voltage
instantaneous range
AC 110V
60/50㎐±5%
AC/DC 110V(80~260V)
-10℃ to 60℃(with no icing)
Less than 2VA
Less than 2VA
12VA(AC), 6W(DC)
● Contact
Out put Relay
Trip 1c, Alarm 1a
Trip & contact capacity
Make
AC 240V 10A(L/R=0ms)
DC 1000W 0.5Sec(L/R=0ms)
Break AC 240V 3A(L/R=0ms)
DC 30W 0.5Sec(L/R=0ms)
74
● Vibration resistance
Malfunction
115~150V/(steps of 5V)
20~100V/(steps of 5V)
20~80V/(steps of 5V)
● Time setting & Curve Definite time or Inverse time
Over Voltage time
0.05~10.3(steps of 0.05)
Under Voltage time
0.05~10.3(steps of 0.05)
0.05±25ms, 0.1~10S±10%
Instantaneous time
Less than 60ms
Reset value
OV:V<95%, UV:V> 105%
Reset time
Less than 100ms
● Burden
Over Voltage
Under Voltage
Aux. Voltage
● Operating time
Over Voltage
Under Voltage
Degree Protection
DEESYS TOTAL PRODUCTS GUIDE
Shock resistance
Destruction;
Insulation to IEC 255
Dielectric withstand
Insulation resistance at 500V
Impluse Voltage Withstand
Surge transient simulator
Weight
LED(Red)
Target(Manual Reset)
Inverse or definite time
IP 52
10Hz 5mm double
amplitude 30s each in X
and Y directions
16.7Hz 2.5mm double
amplitude 600s each in
X,Y, and Z directions
300㎨(approx. 30G) 3
time
each
in
3
directions
2kV for 1 minute
between all terminals
and case earth
>100㏁
5kV-1.2/50 ㎲
2.5kV 1MHz/200Ϊ
2.0kg
Over, Under Voltage Relay[59], [27] 1
Operating time curves
Under voltage relay
Over voltage relay
(Inverse time)
(Definite time)
(Inverse time)
(Definite time)
DEESYS TOTAL PRODUCTS GUIDE
75
Over, Under Voltage Relay[59], [27] 1
Block diagram
Wiring
Non draw out
Draw out
Terminal Arrangement
Non draw out
Dimension
Digital type draw out
76
DEESYS TOTAL PRODUCTS GUIDE
Draw out
Case : ABS 난연성(Non flamable)
Color : Black(N1.5)
Cutting Size: 165 X 122mm
Ground Over Voltage Relay[64]
DVG-M11D
특징
Characteristics
● 본 계전기는 수배전단의 비접지방식의 전력계통에 사용되는 지락과
전압계전기로 GPT를 이용하여 지락사고시 CB를 TRIP시키는데 사
용되는 계전기입니다.
● 지락시 GPT의 3차측에서(a,f간) 유기된 지락전압을 이용하여 동작
하는 계전기로 cable의 정전용량에 대해 오동작 우려가 없습니다.
● 소비전력이 적어 PT의 부담이 작아도 되므로 경제적입니다.
● 동작특성에 대한 구성은 정밀급 반도체로 구성되어 있어 오차범위
가 적습니다.
● 계전기가 동작되면 전자 동작표시가(Target)가 있어 사고후의 상태
를 알수 있습니다.
● The relay is used in non-grounded power system of
distribution lines of power station for the purpose of
tripping circuit breaker through the use of GPT.
● As it is operated by detecting ground fault from third end
of GPT, no concen for malfunction caused by static
capacity of cable to ground.
● It is enconomical to use as modest power dissipation
formal PT. Accordingly smaller current limiting resistor(W)
will be required.
● Since the operation is highly sensitive, it is adequate for
use in detection grounding fault of generators.
● Target shall show the fault condition accurately.
Front plate
1. Voltage Display / Operating Count
2. Voltage Limits Element
3. Time Lever Setting Element
4. Groud Voltage Test
5. Monitor Selection Switch
6. Time Curve Selection Switch
7. Groud Voltage Start LED
8. CPU Run LED
9. Trip Indicator(Manual Reset)
10. Draw-out Handle
DEESYS TOTAL PRODUCTS GUIDE
77
Ground Over Voltage Relay[64]
IEC255 JEC 2500, 2511
DVG-M11(Non Draw out)
DVG-M11D(Draw out)
Specifications
● MODEL
DVG-M11(Non Draw out)
DVG-M11D(Draw out)
● Operating time
Over Voltage
Degree Protection
● Rating
Rated Voltage
Frequency
Auxiliary Voltage
Ambient temperature
AC 110V/190V
60/50㎐±5%
AC/DC 110V(86~260V)
-10℃ to 60℃(with no icing)
● Voltage setting
Over Voltage range
10~85(steps of 5V)
● Time setting
Over Voltage time tap
Resetting Value
Reset time
● Burden
Over Voltage
Aux. Voltage
● Shock resistance
Destruction;
0.05~10.3lever(steps of 0.05)
0.05sec±25ms, 0.1~10sec±10%
>85%
Less than 100ms
Less than 2VA
10VA(AC), 6W(DC)
● Contact
Out put Relay
Trip 1c, Alarm 1a
Trip & Alarm contact capacity
Make
AC 240V 10A(L/R=0ms)
DC 1000W 0.5Sec(L/R=0ms)
Break AC 240V 3A(L/R=0ms)
DC 30W 0.5Sec(L/R=0ms)
● Indicator
Operating start
Operating(trip)
78
● Vibration resistance
Malfunction
LED(Red)
Target(Manual Reset)
DEESYS TOTAL PRODUCTS GUIDE
● Insulation to IEC 255
Dielectric withstand
Insulation resistance at 500V
Impluse Voltage Withstand
Surge transient simulator
Weight
Inverse or definite time
IP 52
10㎐
5mm double
amplitude 30s each in X
and Y directions
16.7㎐ 2.5mm double
amplitude 600s each in
X,Y, and Z directions
300㎨(approx. 30G) 3
time
each
in
3
directions
2kV for 1 minute
between all terminals
and case earth
>100㏁
5kV-1.2/50 ㎲
2.5kV 1MHz/200Ϊ
2.0kg
Ground Over Voltage Relay[64]
Operating time curves
(Inverse time)
(Definite time)
Dimension
Case : ABS 난연성(Non flamable)
Digital type draw out
Color : Black(N1.5)
Cutting Size: 165 X 122mm
DEESYS TOTAL PRODUCTS GUIDE
79
Ground Over Voltage Relay[64]
Block diagram
Wiring : DVG-M11, M11D
Non draw out
Draw out
Terminal arrangement
Non draw out
80
DEESYS TOTAL PRODUCTS GUIDE
Draw out
Directional Ground Relay[67]
DDG-M22D
특징
Characteristics
비접지계의 지락보호 방식으로 사용되는 지락방향계전기는 배전계통의
1선지락시에 발생하는 영상전압과 영상전류로 동작하는 계전기입니다.
● 왜파에 대해서도 정확히 동작할 수 있도록 입력부에 정밀도 Filter
회로를 내장하였습니다.
● 영상전압(Vo) 입력부의 부담을 적게 하였으므로 부담이 적은 접지
용변압기 (G.P.T)한대로도 많은 계전기를 동시에 수용할 수 있습니
다.
● 고속 및 시간 정정탭이 설치되어 후비보호협조가 가능합니다.
Directional ground relay being non-grounded type ground
protection is activated by zero phase sequence
voltage(tertiary voltage of GPT installed on bus line) and zero
phase sequence current (secondary current of ZCT installed
on each phase)
● A precision fillter circuit is employed at input end for
accurate determination of the detection even when signal
wave form is distorted.
● Since the burden of zero phase sequence voltage (Vo)
input end is minimized, any single unit of small capacity
ground potential transformer (GPT) can support several or
more relays at one time.
● Taps provided for time limit setting offer convenient means
of reserver protection.
Front plate
1. Display
2. Io Element(G.V.T)
3. Time Elemnent
4. Vo Elemnent
5. Angle Elemnent
6. Vo Value Indicator
7. Io Value Indicator
8. CPU RUN Indicator
9. Power Indicator
10. Monitor Select S/W
11. Setting Check S/W
12. Test S/W
13. Frequency Select
14. Pick-up Indicator
15. Trip Indicator
16. Reset S/W
DEESYS TOTAL PRODUCTS GUIDE
81
Directional Ground Relay[67]
IEC 255 JEM 1394
DDG-M22 (Non Draw out)
DDG-M22D(Draw out)
Specifications
● Model
DDG-M22(Non Draw out)
DDG-M22D(Draw out)
● Rating
GPT input
ZCT
Frequency
Auxiliary Voltage
Ambient temperature
● Current setting
Operating
Current Setting tap(lo)
Voltage Setting tap(Vo)
Characteristic angle
Zone of operating
● Time setting Curve
Operating
Time tap
Resetting Value
Reset time
AC 110/190
200㎃/100㎷
50/60Hz±5%
AC/DC 110V(86~260V)
-10℃ to 60℃(with no icing)
● Indicator
Operating(trip)
● Vibration resistance
Malfunction
0.1-1.0A(0.1A step)±10%
5~82.5V(steps of 2.5V)
0~180。
(steps of 5。
)
±90(Error±10。
)(lead)
● Shock resistance
Destruction;
0.05~10s (steps of 0.05 sec)
>95%
<100ms
● Burden
G. P. T terminal(G1, G2) Less than 1VA
Aux. Voltage
8VA(AC)
Operating time curve
82
● Contact
Out put Relay
Trip 1c, Alarm 1a
Trip & Alarm contact capacity
Make
AC 240V 10A(L/R=0ms)
DC 1000W 0.5Sec(L/R=0ms)
Break AC 240V 3A(L/R=0ms)
DC 30W 0.5Sec(L/R=0ms)
DEESYS TOTAL PRODUCTS GUIDE
● Insulation to IEC 255
Dielectric withstand
LED
10㎐ 5mm double amplitude 30s
each in X and Y directions
16.7㎐ 2.5mm double amplitude
600s each in X,Y, and Z
directions
300㎨(approx. 30G) 3 time each
in 3 directions
2kV for 1 minute between all
terminals and case earth
Insulation resistance at 500V >100㏁
Impluse Voltage Withstand 5kV-1.2/50 ㎲
Surge transient simulator 2.5kV 1MHz/200Ϊ
Weight
2.2kg
Directional Ground Relay[67]
Phase-angle characteristices
Block diagram
Wiring
Non draw out
Draw out
※ 1. a,f간 결선 및 Z1,Z2 결선을 반드시 확인 하십시요.
2. ZCT 사양은 200㎃/100㎷(Nickel Core)용으로 사용하십시요
※ 200mA/1.5mA ZCT Setting 가능(Option)
Terminal arrangement
Non draw out
Draw out
Dimension
Digital type draw out
Case : ABS 난연성(Non flamable)
Color : Black(N1.5)
Cutting Size: 165 X 122mm
DEESYS TOTAL PRODUCTS GUIDE
83
High Voltage Zero-Phase Current Transformer (ZCT) HZR-Series
HZR . HZS TYPE
Sophisticated ZCT for supporting Ground fault relay
● 사용시 안정성을 추구하였고, 종래의 ZCT보다 저가품으로 설계되
었습니다.
● 사용전류 범위가 광폭형으로 설계되어 Cable 작업시 편리한 구조
로 되어 있습니다.
● 경구조물로 되어 있어 판넬 취부에 용이하고, Cable 선정에 따라
다른 종의 영상변류기가 구비되어 있습니다.
● It aims to provide excellent usability and safety, and
designs more economical than conventional ZCT.
● With wide range of operation currents, it is conveniently
structured for cabling nwork.
● Light and easy for panel setting and also various kind of
ZCT according to selection cable.
Specifications
Item
Rated Voltage(V)
Rated curr.(A)
Dia(∅)
Freq.(㎐)
Weight(㎏)
HZR-050
HZR-065
6,600/3,300
150
50
50/60
0.75
6,600/3,300
200
65
50/60
1
HZR-080
6,600/3,300
400
80
50/60
1.7
HZR-100
6,600/3,300
600
100
50/60
2.3
3.4
HZR-120
6,600/3,300
800
120
50/60
HZR-150
6,600/3,300
1,000
150
50/60
4
HZR-200
6,600/3,300
1,500
200
50/60
5.5
Rated zero-phase pri. curr
200㎃/100㎷(Load 2㏀)
Confroming to JEC 1201 Dielectric Strength characteristics : 6A
Dielectric strength
22,000VAC, 50/60㎐ for 1min
(between primary conductor and coil, and between Primary conductor and mounting flange)
2,200VAC,50/60Hz for 1min(between secondary coil and test coil)
Insulation resistance
>1,000MΪ at 500VDC (between each coils, and between each coil and munting flans
Dimension
Item
A
B
C
D
E
F
G
H
Hole(∅)
HZR-050
50
25
131
100
122
7
32
36
6
6
HZR-065
65
26
143
114
133
7
39
37
HZR-080
80
34
174
160
180
7
40
40
6
HZR-100
100
38
203
160
180
7
40
40
6
HZR-120
120
45
225
180
210
16
55
35
10
HZR-150
150
45
260
180
210
16
55
35
10
HZR-200
200
53
310
260
286
10
70
35
10
Specila Specification
Mold
ITEM
Use of Relay
Epoxy
Mold
65∅,120∅
150∅,200∅
HGR,DGR
※ 상기 제품은 주문에 의해 공급합니다.
※ DGR용 ZCT는 Nickel-core로 제작됩니다.
84
DEESYS TOTAL PRODUCTS GUIDE
Static Phase Open Relay[47]
DPR-011D, 019D
특징
Characteristics
● 전력계통의 전압결상 및 반상 기능으로 후비보호에 최적이며 전압
검출을 이용하여 구동시키므로 결선이 간편하고 고압 및 저압에 사
용되는 계전기 (PT 2차 사용)
● 결상이 되면 동작표시기(LED)가 설치되어 있어 사고의 판별이 명확
히 구분됩니다.
● 계전기는 3상 입력 전압이 있어야 정상동작 합니다.
●The relay is best suitable for back up protection reserve
against loss and damage caused by open phase in power
system and applicable to both high and low voltage without
requiring power source. It offers wiring convenience since it
is driven by detecting voltage
●When a phase open is detected, indicator lamp(LED) is
turned on for the phase line so that the fault line is
identified visibly.
●It will not operate when 3 phase line power is not available.
Front plate
Operating time
DEESYS TOTAL PRODUCTS GUIDE
85
Static Phase Open Relay [47]
DPR-011(Non Draw out)
DPR-011D(Draw out)
DPR-019(Non Draw out)
DPR-019D(Draw out)
Specifications
● Model
DPR-011(Non Draw out) AC 110(3∅)
DPR-011D(Draw out) AC 110(3∅)
DPR-019(Non Draw out) AC 190(3∅)
DPR-019D(Draw out) AC 190(3∅)
● Rating
Rated Voltage(3∅)
Frequency
Auxiliary Voltage
Ambient temperature
● Under voltage setting
Rated voltage setting
AC 110,190V
50/60㎐
Non Power
-10℃ to 60℃(with no icing)
300㎨(approx. 30G) 3 time each
in 3 directions
70~90%, ±10%
● Reverse
Operating time
Degree Protetion
Less than 1sec
IP52
● Burden
Rated burden
1VA
● Contact
Out put Relay
Trip-1c Alarm-1c
Trip & Alarm contact capacity
Make
AC 240V 10A(L/R=0ms)
DC 1000W 0.5Sec(L/R=0ms)
Break AC 240V 3A(L/R=0ms)
DC 30W 0.5Sec(L/R=0ms)
86
● Shock resistance
Destruction;
10㎐ 5mm double amplitude 30s
each in X and Y directions
16.7㎐ 2.5mm double amplitude
600s each in X,Y, and Z
directions
● Insulation to IEC 255-5
Dielectric withstand
● Open and Under voltage time setting difinite time
Setting tap
1~4sec±10%
● Indicator
Operating RVS
Trip
Resetting
● Vibration resistance
Malfunction:
LED(YEL)
LED(RED)
Manual Reset(Indicator)
DEESYS TOTAL PRODUCTS GUIDE
Insulation resistance at 500V
Impluse Voltage withstand
Surge transient simulator
Weight
2kV for 1 minute
between all terminals
and case earth
>100㏁
5kV-1.2/50㎲
2.5kV 1MHz/200Ϊ
2.2kg
Static Phase Open Relay [47]
Block diagram
Wiring
Draw out
Non Draw out
(DPR-serise)
Terminal arrangement
Non draw out
Draw out
DEESYS TOTAL PRODUCTS GUIDE
87
High Voltage Ground Relay [51G]
DHG-021ND
특징
Characteristics
비접지식에 사용되는 고압 지락계전기는 공장 또는 고압설비 및 기기
의 지락 사고를 신속히 검출하는 무방향성 지락계전기로서 영상 변류
기와 조합하여 사용되는 계전기입니다.
● 고조파 및 Surge의 영향을 받지 않는다.
● 자체 스위치 시스템에 있어 계전기의 정상상태 확인이 가능합니다.
● 동작표시가 부착되어 있어 사고후 판별이 가능합니다.
● 인출형이 가능하여 점검 및 보수가 편리합니다.
H. V ground relay is applied for protection of factories. HV
heavy-duty facilities or the relative apparatus, detecting
instantly earth-fault. This non-directional relay is inconbination
with ZCT
● Free from high frequency or surge.
● With self checking switch set, normal operation can be
easily confirmed at any operation at any time, if need.
● Indicator can detect any wrong-operation after earth fault.
● Easy check-up and maintainance.
설치시 주의사항
고압지락 계전장치는 과전류계전기에 비하여 검출하는 전류가 대단히
적기 때문에 다른 전력선으로부터의 유도나 공사상 부주의로 불필요한
동작, 오동작 또는 부동작의 원인이 되기 때문에 설치 및 운용에 있어
다음을 주의할 필요가 있다.
● 관통형 ZCT를 사용하는 경우의 접지공사
● 관통형 ZCT에 Cable을 관통시켜 사용할 경우 실-드접지 위치는
인입용 cable의 어느 경우에도 원칙적으로 cable 1개에 대하여 1
점으로 접지한다.
● ZCT의 2차 배선은 2가닥을 합친상태에서 다른 전력선보다 최소한
30cm이상 거리를 띄울것(ZCT의 2차단자간의 전압은 수mV~수십
mV로 극히 작으므로 정전유도, 전자유도에 따른 영양을 받을수 있
다. 그러기 때문에 오동작을 방지하기 위하여 원칙적으로는 독립된
2심 일괄 실-드선을 사용하는 것이 바람직하다. 전력선과 근접하고
있을 때에는 반드시 실-드선을 사용해야 한다. 또한, 실-드선은 접
지를 해야한다. ZCT의 2차(kt,lt)는 상시 개방을 하여 두고 계전기
시험시에만 사용한다. k,l단자(Z1, Z2)는 절대 개방하지 말아야 한
다. 개방시 고압이 유도되어 감전사고의 원인이 발생하고 만약
ZCT 분리시에는 단락하여 둔다.
Operation time
88
DEESYS TOTAL PRODUCTS GUIDE
Installation
Compared with overcurrent relay, the relay detects very little
and raises unnecessory reaction. You shall pay attention to
the following.
● Grounding in useing of through-type ZCT.
● Put cable into the through-type ZCT shield grounding
location at any event ground at only point/per piece.
● ZCT secondary wiring distance shall be kept minimum
30Cm away then as in other line installation in the state of
combining two line into one. This serves to protect wrong
operation.
Front plate
High Voltage Ground Relay [51G]
KS C4601
DHG-021N(Non Draw out)
DHG-012ND(Draw out)
Specifications
● Operating time
KSC 4601 over 130%
over 140%
Degree Protection
● Model
DHG-021N(Non Draw out)
DHG-012ND(Draw out)
● Rating
1ry operating current
200㎃/100㎷(2㏀
Combination)
50/60㎐±5%
AC/DC 110V±20%
-10℃ to 60℃(with no
icing)
Frequency
Auxiliary Voltage
Ambient temperature
● Current setting
Operating
Current temperature
0.2-0.3-0.4-0.5-0.60.8-1.0-Lock(A)
● Time setting Curve
Over current 130%
Over current 400%
0.1~0.3sec
0.1~0.2sec
● Burden
Aux. Voltage
10VA(AC), 6W(DC)
● Contact
Out put Relay
Trip & Alarm contact capacity
Make
Break
● Vibration resistance
Malfunction:
● Shock resistance
Destruction;
● Insulation to IEC 255-5
Dielectric withstand
Insulation resistance at 500V
Impluse Voltage with stand
Surge transient simulator
Weight
0.1~0.3sec
0.1~0.2sec
IP52
10㎐ 5mm double
amplitude 30s each in X
and Y directions
16.7㎐ 2.5mm double
amplitude 600s each in
X,Y, and Z directions
300㎨(approx. 30G) 3
time each in 3
directions
2㎸ for 1 minute
between all terminals
case earth
>1,000㏁
5㎸-1.2/50㎲
2.5㎸ 1㎒/200Ϊ
2.0kg
Trip 1c, Alarm 1a
AC 240V 10A(L/R=0ms)
DC 1000W 0.5Sec(L/R=0ms)
AC 240V 3A(L/R=0ms)
DC 30W 0.5Sec(L/R=0ms)
DEESYS TOTAL PRODUCTS GUIDE
89
High Voltage Ground Relay [51G]
지락사고 검출방식
Mode of detection
지락사고 검출방법에는 사용하는 계전기에 따라
① 지락전류 검출방식
영상변류기 + 지락과전류 계전기 + 지락계전장치
② 영상전압검출방식 : 지락과전압계전기
③ 위상검출방식: 지락방향계전기의 방법이 있으나 변압기 2차측은 평
상 배전길이가 짧고 Feeder수가작은 것에는 ①,②
의 방법으로 검출하면 된다. 특히 전압측의 비접지
방식에서는 접지보상용 콘덴서의 적용이 필수적이다.
The designation of relay varies as follows according to
detecting method.
① GR Detection:
ZCT + OCGR + GR apparatus
② GPT Detection : OVGR Relay
③ Phase Detection ; DGR Relay
Where distribution line is very short and the number of
feeder is small too. (1),(2) methods are applicable and
suitable. Especially, in non grounding mode is required to
apply the condenser of zero-phase detction unit
∴ 콘덴서계산식 C =
2lt
2πf √
3V
(F)
lt : 계전기 정정치
∴ Condenser C =
fc √3V(A)
∴ 완전지락시 계산식은 lg = 2π
2lt
2πf √
3V(A)
(F)
lt : Relay setting value
∴ Ground Fault lg = 2π
fc √3V(A)
감도전류정정탭의 설정
Setting tap of sensitivity current
수용가 구내에 대지간 정전용량이 적으면 고압기기 등의 보호(미소자
락 전류에서 동작시키면 피해가 적다.) 를 생각하여 최소탭으로 놓는
것이 좋다. 그러나 구내에 고압케이블 배선이 많고. 100m 를 넘을 경
우에는 현행 KS의 제품은 비방향성이므로 200mA탭 이하에서는 수용
가 구내가 아니고, 구외의 (ZCT부터 전원측) 배선의 지락사고를 불필
요하게 동작되는 경우가 있다. 배전선의 미소지락 사고등으로 가끔 관
계없는 수용가측에서 정전이 되는 불편을 주고, 이와 같은 경우에는
탭을 1~2단계 높여서 400mA~600mA로 하면 불필요동작을 하지
않게 된다. 고압기기와의 보호관계상수용가 지락계전장치의 탭을
200mA로 놓을 경우 혹은 600mA, 800mA등 최고 탭에 대해서도 협
조가 안되는 경우에는 비접지식의 것으로, 방향성을 갖는 것을 사용하
면 불필요한 동작이 없고 충분히 만족을 시킬 수 있다. 이런 경우에는
방향성계전기인 DDG-M22형을 사용하면 된다.
Conisidering that once electrostatic capacity in between
service area in consumer end is small, and high voltage
device shall be protected small, and high voltage device shall
be protected(operation in tiny earth fault causes little
damage)keeping tiny tap in minimum will be suitable. But
when there are high voltage wiring in service area, ground
fault can frequently occur. Accordingly, consumer end is
troubled with power cut-off, due to tiny fault of power
distribution. In such case, tap shall be raised 1~2 steps to as
much as 400mA~600mA. Poor coordination continues
caused by max tap, in non-grounding directional relay DDGM22 will get into normal role.
케이블 정전용량 일람표
Cable electrostatic
capacity
norminal area
(㎟)
for 0.2A setting
(m)
for 0.4A setting
(m)
8
14
22
38
60
100
150
200
250
135
115
100
85
70
60
50
50
47
270
230
200
170
140
120
100
100
95
(CV cable 6,600)
90
DEESYS TOTAL PRODUCTS GUIDE
케이블 길이에 대한 충전전류
Cable length of
charging current
Voltage
3.3KV
6.6KV
Item
3Core
(3 ∅3W)
3Core
(3 ∅3W)
norminal
(㎟)
JISC3606(CV)
㎌/㎞
8
14
22
38
60
100
150
200
250
0.63
0.78
0.90
1.11
1.14
1.41
1.62
1.65
1.77
8
14
22
38
60
100
150
200
250
0.63
0.75
0.84
0.99
1.17
1.41
1.65
1.62
1.65
케이블 길이에 대한 한계 전류치
Cable length of limit
current
High Voltage Ground Relay [51G]
지락보호 협조
Protective Coordination
● 지락보호에 대해서도 과전류계전기와 같이 전력회사의 보호방식에
대응하여 수용가측에서는 시한협조 및 지락전류 협조를 가질 필요
가 있다.
● 특히 파급사고의 대부분이 지락사고에 따른 것이다. 그러므로, 적어
도 ZCT부터 부하측에서 발생하는 것은 모두 수용가 측에서 차단하
는 것이 필요하다.
● 운용상에 있어서는 전력회사와 충분히 연락을 취하여 협의할 필요
가 있다.
● 일반적으로는 현행의 수용가용 고압지락계전장치는 한시적으로는
문제가 없고 감도전류치를 적절히 선정하는데 따라서 대개의 경우
배전용 변전소의 지락보호계전 장치와 협조가 된다.
● For the protection of ground fault, as in overcurrent relay,
consumer shall have time and ground fault coordination
corresponding with suppliers protective measures
● Most of ground faults are caused by influension effect.
There fore consumers shall take action to break down
grounding from the ZCT burden
● For the managing ground fault, consumer ends shall
coordinate fully enough with power supplier.
● As a rule HVGR which consumer use, operates timely
without any hitch. By choosing sensitivity properly. HVGR
coordinates smoothly with, protective ground relay in
distribution purposed-power plant.
지락보호 구성
Construction
● 지락보호를 하는데 있어서의 방식은 방향을 선택하여 차단하는
DGR이 있으며, GPT의 영상 전압만으로 동작하는 OVGR이 있다.
● OVGR은 전압요소에 따라서만 동작하기 때문에 보통 과전류계전기
와 같이 동작전압치는 가변되는 탭(일반적으로 25~60V)과 동작시
간을 변경하는 레버가 있어 가변이 가능하다.
● 지락계전장치의 감도는 JIS (고압지락계전장치)에서는 200mA,
400mA, 600mA 3점의 절체탭을 반드시 구비하여야 한다. (연속
절체는 안된다.)
● 예를 들면 235mA 또는 422mA와 같이 슬라이드 저항 등으로 미
소한 변화를 주는 것은 JIS에서는 불가로 되어 있다. 연속가변이 아
닌 탭을 부가하여도 관계없다.
● 동작시간은 과전류정정치의 130%에서 0.1~0.3초, 400%에서
0.1~0.2초로 되어 있다. 이 특성에서보면 반한시 특성을 가지고 있
는 것 같이 보이나 실제는 정한시에 가깝다.
● In protection of ground fault, there are two kinds of relay :
DGR for directional Selection and OVGR toroperating with
Zero voltage from G. P. T.
● OVGR operates in accordance with voltage and time
adustable Knob, each.
● High voltage ground relay shell be provided as following
sensitivity Tap according to JIS 200mA, 400mA, 600mA
● The setting taps shell be fixed taps, not be linear sliding
type like 235 or 422 instead of 200mA or 400mA.
● Operating time : Overcurrent Setting Valus 130%0.1~0.3secs, 400%-0.1~0.2secs. Based on the above
characteristics. HGR seems to be inverse time
characteristic. But it is definite time characteristic.
실-드 접지공사 방법(How to wiring the shield)
DEESYS TOTAL PRODUCTS GUIDE
91
High Voltage Ground Relay [51G]
Block diagram
Wiring
Non draw out
Non Draw out
※ ZCT사양은 200mA/100mV용을 사용하십시요
Terminal arrangement
Non draw out
92
DEESYS TOTAL PRODUCTS GUIDE
Draw out
High Voltage Ground Relay [51G]
Dimension
● Digital type draw out
Case : ABS 난연성(Non flamable)
Color : Black(N 1.5)
Cutting Size: 165 X 122mm
● Digital type non draw out / Static type DGR, POR, HGR
Cutting Size: 165 X 122mm
DEESYS TOTAL PRODUCTS GUIDE
93
Marine type
Protective Relays
■Marine Type 3 Phase Voltage and Frequency Relay
■Marine Type 3 Phase Phase Fail Relay
■Marine Type 3 Phase Phase Sequence Indicator Relay
■Marine Type Single or 3 Phase Synchroscope
선박용 계전기
VOLT/Hz, PFR, PSI, SYNC
선박용 3-Phase Voltage and Frequency Relay
DFV-011
특징
단상 전압 및 주파수 계전기로 High-Low setting이 가능하고 한
Unit에 내장되어 있어 전압과 주파수 콘트롤이 동시에 가능합니다.
Specification
Part Name
Style
노출형(DIN Rail 사용기능)
Type
DFV-011
Connection
Input
Aux. Power burden
Voltage set range
외부 VT 사용 또는 Direct 결선
VT : AC440V, Burden : 0.3VA, Frequency : 60㎐
DC24V, 10W
Low : 90~100%(396~440V), High : 100~110%(440~484V)
Frequency set
Low : 50~60㎐, High : 60~70㎐
Operating time
200ms app
Contact
Reset
Temperature
Vibration
Shock
Weight
Dimension
96
3-Phase Voltage and Frequency Relay
DEESYS TOTAL PRODUCTS GUIDE
AC110V 10A 0.5sec(cos∅=1.0)
Auto Reset
Operating temperature -10~55℃ RH < 95%
Storage temperature -20~+70℃
Vibration frequency:16.7㎐ Double amplitude:0.4㎜ Direction:horizontal, vertical, transverse
Shock acceleration:50G Shock application direction:horizontal, vertical, transverse
Shock times : 3 times
1.0㎏
Connection diagram
선박용 3-Phase Phase Fail Relay
DFR-021
특징
3상에 흐르는 부하전류를 검출하여 정상상태에서 불평형 및 결상상태가 될 시
즉시 정밀차단하여 모터의 소손을 미연에 방지, 보호하는 계전기로 전류검출
컨버터를 조합하여 사용하는 결상계전기 입니다.
Specification
Part Name
Style
Type
Connection
Input
Aux. Power
Aux. Power burden
Current set range
Operating time
Accuracy
Contact
Temperature
Vibration
Shock
Weight
Dimension
3-Phase Phase Fall Relay
매입형(Flush mounted type)
DFR-021
외부 CT사용, Current converter(MCT와 조합사용)
CT : AC5A(2차), Burden : 0.3VA
Voltage : AC110V, AC220V, Frequency : 50/60㎐
7VA
AC 1~80 or 64~160A (1’
ry current of MCT 3∅)
Less than 4sec
±10%
AC 110V 5A 30min (cos∅=1.0)
Operating temperature -10~60℃ RH < 95%
Storage temperature -20~+70℃
Vibration frequency:16.7㎐ Double amplitude:0.4㎜ Direction:horizontal, vertical, transverse
Shock acceleration:50G Shock application direction:horizontal, vertical, transverse
Shock times : 3 times
0.5㎏
Connection diagram
Equipment
Rated Curr.
1~2.5
2~5
4~10
8~20
16~40
32~80
64~160
MCT SelectionMCT
Model
Tap(A)
20
MCT-31
MCT-32
40
80
160
P.F.R
1’ry turns
8
4
2
1
1
1
1
dial set.
0.25
0.5
1
2
4
8
16
DEESYS TOTAL PRODUCTS GUIDE
97
선박용 3-Phase Phase Sequence Indicator
DPS-011
Feature
3상의 상위상을 감지하는 표시기로 3상위상이 정상이면 녹색(Green)
Lamp가 점등 되고 위상이 바뀌면 적색(Red) Lamp가 점등되어 정상
상태의 위상을 판별하는 표시기입니다.
Specification
Part Name
Style
매입형(Flush mounted type)
Type
DPS-011
Connection
Input
Aux. Power
외부VT 또는 Direct 사용
AC110/190/220/380/440V Burden:3VA(Aux.포함)±10%
Voltage : AC110~600V(입력 정격전압과 동시사용) Frequency :50/60㎐
Normal
Green LED : R�S�T, S�T�R, T�R�S
Reverse
Red LED : S�R�T, T�S�R, R�T�S
Temperature
Vibration
Shock
Weight
Dimension
98
3-Phase Phase Sequence Indicator (Relay겸용)
DEESYS TOTAL PRODUCTS GUIDE
Operating temperature -10 ~ 55℃ RH < 95%
Storage temperature -20 ~ + 70℃
Vibration frequency:16.7㎐ Double amplitude:0.4㎜ Direction:horizontal, vertical, transverse
Shock acceleration:50G Shock application direction:horizontal, vertical, transverse
Shock times:3 times
0.5㎏
Connection diagram
선박용 Single or 3-Phase Synchroscope
DVF-011
Operation/Starting
Rotation
O㎐<S㎐
� (LED)
O㎐>S㎐
� (LED)
Feature
본 Meter는 processor를 이용하여 Starting Generator의 주파수를
자동 판별하여 동작하며 Starting Generator의 위상에 대하여 정확한
동작이 이루어집니다.
Starting Generator의 주파수가 Operating Generator 주파수보다
±3Hz를 벗어난 범위에서는 지침(Lamp)이 빠르게 회전합니다.
Metor의 지침(Lamp)이 움직이기 시작하는 주파수 범위는 Operating
Generator의 정격 주파수의 ±3Hz 이내에야 합니다.
Operating Generator의 주파수보다 대기중인 Starting Generator의
주파수가 높을 경우 지침(Lamp)은 SLOW 방향으로 회전하고
Operating Generator의 주파수보다 Starting Generator의 주파수가
높으면 지침 (Lamp)은 FAST 방향으로 회전합니다.
Starting Generator와 Bus의 주파수 및 위상이 같게 되면 지침
(Lamp)의 위치는 Meter 위 부분의 Marking지점(lamp)에 위치 하게
되는 상 동기 검출기입니다.
Specification
Part Name
Synchroscop
Type
DVF-011
Style
매입형(Flush mounted type)
Type
DVF-011
Connection
Input
Temperature
Vibration
Shock
Weight
Dimension
외부VT 또는 Direct 사용
AC110V±20% Burden : 6VA(Aux. power 포함)
Operating temperature -10 ~ 55℃ RH < 95%
Storage temperature -20 ~ + 70℃
Vibration frequency:16.7㎐ Double amplitude:0.4㎜ Direction:horizontal, vertical, transverse
Shock acceleration:50G Shock application direction:horizontal, vertical, transverse
Shock times:3 times
0.5㎏
Connection diagram
DEESYS TOTAL PRODUCTS GUIDE
99
선박용 Dimension
Dimension
DFV-011
DFR-021
DPS-011
DVF-011
100
DEESYS TOTAL PRODUCTS GUIDE
국가형식검정품(한국소방검정공사)
Digital Earth Leakage
Detector and Relay
▶ Multi Function Digital Earth Leakage Detector and Relay[ELD, ELR]
▶ Analog/Micom Earth Leakage Detector and Relay[ELD, ELR]
ELD
누전경보기(Digital, Analog, MICOM)
D2K-ED Series Earth Leakage Detector & Relay
Feature
누전경보기설치대상물
● 소방법 시행령 제 24조 2항, 3항에 의거
누전으로인한 화재 및 재해발생예방에 경보기를 설치해야할 소방대상물
대상면적 (㎡)
대상전력용량(A)
연면적 500㎡이상 설치(업무시설, 통신촬영시설, 교육연구시설 및
전시시설의 경우에는 1,000㎡이상) 하여야 한다.
계약전류용량(동일건축물에 계약종별이 다른 전기가 공급되는 경우
에는 그중 최대 계약전류 용량을 말한다)이 100A를 초과하는 경우
에는 설치 하여야 한다.
※500㎡이하 및 100A 이하의 곶에도 설치하여 누전으로 인한 재해방지를 하는것이 좋습니다.
System and Protection
교류600V미만의 교류 전원에서의 전기설비 절연불량으로 인한 누전을 영상 변류기를 통하여 동작하는 다기능 다회로의 누전으로인한 화재발생 예방
누전경보 시스템이다. 입력의 신호중에 혼입된 각종 Noise 및 고조파를 Analog Filter 및 Digital Filter를 통하여 정상적인 신호로 변환하여 판독하므
로 정밀한 동작을 구현한다. 또한 16Bit Micro Processor를 이용하여 고속처리 및 RS-485통신기능을 부가하여 원격에서 계전기를 제어 감시할 수
있다.
1대의 누전경보 및 계전기로 8회로, 16회로, 24회로, 32회로까지 감시 및 보호할 수 있다. 기본형은 8회로로 구성되며 8회로를 내장된 별도의 Module
을 이용하면 최대 32회로까지 연결시킬 수 있다. 8회로는 기존의 경보기제품과 동일한 Case에 내장되어 호환이 가능하며 16회로, 24회로 및 32회로
는 19inch Rack의 2/3 크기의 Case를 사용한다. 누전경보 동작시 년/월/일/시/분/초 단위까지 기억되므로 사고 발생시 경보기에서 사고의 순서를 10
개 까지 확인 할 수 있어 누전으로 인한 화재감시등의 평가 수단으로 이용될 수 있다.
Display Mode
각 회로의 현재 시점을 기준으로 하여 누전 상태를 실시간으로
LCD(Liquid Cristal Display)표시창에 Scrolling 하며 감시한다.
Fault Memory
사고 Data의 횟수는 10회까지 Memory 한다.
- Fault Date
- Fault Time
- Fault Feeder
- Fault Current
Operating Current and time setting
고감도의 누전부터 대전류의 누전까지 정정할 수 있도록 광범위한 누전전류 Tap을 구비하고 있고, 순간 누전상태 및 동작지연 시간을 적절하게 보호협조
할 수 있도록 Time Delay 기능을 구비하고 있다.
Communication and Monitoring
원격에서 계전기를 제어 감시할 수 있도록 RS-485 Port를 적용한 통신기
능이 내장되어 있다.
- 사고 전류의 확인
- 동작전류, Time Delay의 설정
- 현재 흐르는 누전 및 지락 전류량 확인
- 사고시의 날짜 및 시간 확인
- Buzzer On / Off 기능
- 수동 자동 설정 가능
102
DEESYS TOTAL PRODUCTS GUIDE
D2K-ED Series Earth Leakage Detector & Relay
Typical substation architecture
Eather-net (TCP/IP)
Communication for Specification
통신사양
- 통신속도 : 19,200bps
- 통신거리 : 1.2km
- 통신방식 : RS-485(2wire)
- 최대노드수 : 1~16대
Fault event
- current : 8ch, 16ch, 24ch, 32ch
- data : date, time, circuit
DEESYS TOTAL PRODUCTS GUIDE
103
D2K-ED Series Earth Leakage Detector & Relay
D2K-ED08(8circuit)
D2K-ED24(24circuit)
D2K-ED16(16circuit)
D2K-ED32(32circuit)
Product name
Model
Certificate No.
Monitoring Circuit
Power Source
Rated Current Sensitivity
Time Setting Range/Deviation
Operating Current
Non-Operating Current
Rated current Z.C.T
Contact
Display
Key Method
Earth Leakage Detector [ELD]
D2K-ED08
D2K-ED16
07-13
8Circuit
D2K-ED24
D2K-ED32
07-16
07-14
07-10
16ircuit
24ircuit
32ircuit
AC 110/220 ± 15%, 50/60㎐ (Default), DC 110/125 ± 20%
AC 200mA~1000A (100mA Step), Default-0.5A
0.1�3.0Sec/0.1:±50ms, 0.2~3.0:±15%(0.1sec, Step), Default-0.2Sec
Between 53% and 75% of resonable value
Below 52% of reasonable value
200mA / 100mV(75~125mV at 2㎘ Resistance)
1a(All circuit)
1a(All circuit)
16a(ED16)
24a(ED24)
8a(ED08)
32a(ED32)
L.C.D(20Char, X 4Line)
MODE,ESC,ENTER,Direction Keys(�,�,�,�)
RUN(green) : C.P.U.Error 동작상태감시
AUTO(yellow) : 동작 후 Relay 및 Lamp의 복귀 [On(Flickering) : Auto / Off : Manual]
BUZZER(yellow) : 동작시 buzzer 울림[OFF(Flicker)시 꺼짐 / On : 올림]
LED(Lamp)
COMM(yellow) : 깜박일때 신호 출력 중
ZCT(red) : Faulty ZCT 연결 불량 및 연결이 되지 않았을 경우
PICK(red) : Pick-up 누전전류 동작시 점등
SYS(red) : 내부회로 및 소자 불량시 점등(System Error)
ALARM(red) : 누전에 의한 동작 표기시
Fault Memory
Resetting Method
Temperature
Mounting Method
Capacity of contact Point
Buzzer
Insulation Resistance
최고사고치 10회 Memory 가능 및 사고선로별 회로 표시 “1”
( 이 가장 최근 사고를 표시함)
Auto Reset/Manual Reset가능(program에 의하여 선택 방법)
`-10�60℃(in operation), -20�70℃(to be kept)
Flush Mounted Type
AC 250A 5A 0.5sec(L/R=0)
75dB(within 1m)
1’
st-ground / 2’
nd-ground / 1’
st-2nd : 100㏁ or more DC500V Megger
1’
st-ground : AC 1,500V
Withstand voltage
2’
nd-ground : AC 500V
1’
st-2’
nd : AC 1,500V
Lighting impulse Withstand voltage
Vibration
Aux. power - ground 1.2㎲×50㎲×6㎸ Positive/Negative electronics. 3time
Vibration frequency:16.7㎐ Double amplitude : 0.4㎜ Direction:horizontal, vertical, transverse
Shock acceleration:50G Shock application direction:horizontal, vertical, transverse
Shock
Weight
104
DEESYS TOTAL PRODUCTS GUIDE
Shock times : 3 times
2kg
7kg
D2K-ED Series Earth Leakage Detector & Relay
Front View
LED indicator
CPU(RUN)Error check
Auto/Manual Set
Buzzer On/Off Set
Communication con.
ZCT connection check
Pick-up/system check
Display
General Setting
Level Setting point
Fault check
Communication
Self test mode
Key part
Up↔Down menu
Right↔Left menu
Key Part
Top menu modekey
Escape Key menu
Cursor menu key
Reset
Lamp and CPU reset
Menu Specification
Start on display
- 제어전원이 인가되거나 “CPU Reset” Key를 누르면 Back
Light와 함께 아래의 Logo 화면이 5초정도 Display된 후 다음
상태인 Display On / Off Mode나 상태 Display Mode로 자동
이동된다.
- Default : Display On Mode
D 2 K - E D
D E E s y s
S e r i e s
V 1 . 0 0
Display On Mode
- 다음의 Display 값이 5초 정도 지속된 후 다음 Mode(상태
Display Mode)로 자동 이동한다.
D i s p l a y
2 0 0 0
0 1
O n
0 1
M o d e
a u l t
D
C u r r
3
0 . 7 2
9
1 . 6 3
F
0
0
0
d
1
2
3
0
0
0
S
.
.
.
C
2
1
4
5
2
7
0
0
0
S
.
.
.
T
3
2
7
s
s
s
C
0
0
0
u
.
.
.
r
2
1
7
r
0
0
2
F
Top menu
- 상태 Display Mode에서“MODE”Key를 누르면 다음과 같이
Top Menu가 Display 된다. 10초 이내에 아무런 Key 입력이
없으면 상태 Display Mode로 전환된다.
1 2 : 1 5 : 3 6
Fault가 발생된 경우
- Display On / Off Mode에 관계없이 Fault 발생시에는 다음과
같이 Display 한다.
- Fault Memory창으로 이동하며 최대 10회까지 저장된다.
-“Esc”Key를 누르면 상태 Display Mode로 됨
F
F
0
ㅁ0
Display Mode
- Fd(Feeder) : 감시회로
- SC : Set Current
- ST : Set Time(Delay)
- Curr(Current) : 현재 누전량 표시
- F(Fault 상태) : 누전 동작을 표시한다. (×표시)
- 상기 상태는 Scrolling하고 있으며 Up/Down 방향 Key(↑,↓)를
1회 누를 때마다 1Line씩 이동된다.
D a t e
0 1 0 7
0 1 0 7
T
1 . G e
2 . L e
ㅁ3 . F a
T
n
v
u
O
e
e
l
P
M E N U
r a l
S e t
l
S e t
t
C h e c k
�
T i m e
1 7 : 3 6
1 7 : 3 6
DEESYS TOTAL PRODUCTS GUIDE
105
D2K-ED Series Earth Leakage Detector & Relay
Sub Menu
General Set
Display On / Off Mode 설정, Buzzer On / Off 설정,
Reset Auto / Manual 설정 / Memory Erase/ Date / Time Set
Level Set
동작 전류 및 Delay Time 설정
Fault Check
누전 발생시 Fault 확인 (누전된 Feeder, 누전 전류, 누전 발생 시
간)
Communication
통신에 관계된 항목의 설정
Test
자체동작 시험에 관한 항복 설정
System Menu
106
DEESYS TOTAL PRODUCTS GUIDE
D2K-ED Series Earth Leakage Detector & Relay
● General Set
∙Top Menu에서 1. General Set에 Cursor를 위치한 후 Enter를
누르면 다음과 같이 Display 한다.
G
1 . D i
2 . B u
ㅁ3 . R e
e
s
z
s
n
p
z
e
e r a l
S
l a y
[ O
e r
[ O
t
S e t
e
n
n
[
t
]
]
A u t o ]
�
● Memory Erase [Yes / No]
∙Memory Erase에 위치한 Enter를 누르면 Memory를 지운다.
∙정정값이 Save 되면 전 단계 Sub Menu로 이동된다.
M e m o r y
E r a s e
Y E S : U P
[ N ]
N O : D O W N
∙Display Time의 변경이 없는 경우는 Enter key를 누르고, 변경
시에는 이어서 동일한 절차에 의하여 설정한 후 Enter Key를 누
르면 다음과 같이 Display 된다.
C u r r e n t
S e t
[ 0 . 5 ] A
D e l a y
T i m e
[ 0 . 2 ] s
A r e
Y o u
S u r e . ? ( Y )
Y E S : U P
N O : D O W N
∙변경후 Enter Key를 누르면“Are you Sure( )”
라는 Message
가 나타난다. Up / Down Key를 눌러 Y를 입력한 후 Enter
Key를 누르면 변경된 값이 입력된다.
∙정정값이 Save 되면 Top Menu로 이동된다.
● Communication
∙Top Menu에서 4. Comm set에 Cursor를 위치한 후 Enter를
누르면 다음과 같이 Display 한다.
●“Each”
로 개별 설정할 경우
S
0
0
ㅁ0
E T
M O
1
A [ 0 .
2
A [ 0 .
3
A [ 0 .
D
5
5
5
E
]
]
]
( I
D
D
D
/
t
t
t
d
[
[
[
t
0
0
0
)
. 2 ]
. 2 ]
. 2 ]
C O M M
1 . P o r t
2 . B a u d
ㅁ3 . P a r i t
�
∙각가의 Feeder에 누전 및 지락 전류를 Up/Down 방향 Key를
이용하여 입력하고 Dt는 Mode Key를 입력하고 Up/Down 방향
Key를 이용하여 값을 설정한다. Display된 Feeder의 정정을 완
료하면 마지막 Line 끝에 Cursor를 위치한 후 좌측 방향 Key를
눌러 Feeder가 Scroll 되도록 하여 Setting을 한다.
∙같은 방법으로 각 Feeder를 입력한 후 Enter Key를 누르면 다
음과 같이 Display 된다.
S E T
M O D E
A r e
Y o u
S u r e . ? ( Y ) \
Y E S : U P
N O : D O W N
S E T
N o .
r a t e
y
M O D E
[ 0 0 ] �
[ 1 9 2 0 0 ]
[ E v e n ]
● Port No
C o m m
(
P o r t
N o .
[ 0 1 ]
1
1 6
)
H I : U P
L O W : D O W N
∙Up / Down 방향 Key를 누르면 Come Port를 설정할 수 있습
니다.
∙Port 값이 Save 되면 위 Sub Menu로 이동한다.
( I / d t )
∙Are You Sure?라는 message가 나타나면 Y를 입력하고 Enter
를 눌러 정정값을 모두 변경한다.
∙변경하고자 하는 Feeder가 1개면 해당 Feeder의 정정값을 변경
후 Enter를 누르면 변경된다.
∙정정값이 Save 되면 Top Menu로 이동된다.
∙Default: <Fault Current : 0.5A / Time Delay : 0.2Sec>
●“ALL”
로 일괄 설정할 경우
C u r r e n t
S e t
[ 0 . 5 ] A
D e l a y
T i m e
[ 0 . 2 ] s
H I : U P
L O W : D O W N
● Baud rate
∙19,200bps로 고정되어 있습니다.
● Stop Bit 설정
∙1로 고정되어 있습니다.
● Test
∙Top Menu에서 5. Test Set에 Cursor를 위치한 후 Enter Key
를 누르면 아래와 같이 Display 한다.
T o p
3 . F a u l t
4 . C o m m
S
ㅁ5 . T e s t
S
M
C
e
e
e n u
h e c k
t
t
∙모든 Feeder의 Test가 끝나면 Esc Key를 입력하면 Top Menu
로 이동한다.
∙일괄 설정으로 하여 Enter Key를 누르면 다음과 같이 Display된다.
∙Current Set에서 Up / Down 방향 Key를 이용하여 설정한다.
DEESYS TOTAL PRODUCTS GUIDE
107
D2K-ED Series Earth Leakage Detector & Relay
Wiring
�8C
External Wiring(ED 8 CIRCUIT TYPE)
T1~T8
: “a”
접점
Tcom
: Common 접점
PP PN
: AC 110/220V(DC110V)Aux, Power
Ta Tb Tc
: 일괄 Alarm 접점
E
: 외함 접지단자(E3)
Z1~Z8
: ZCT 각회로 단자(각회로와 동일함)
Zcom
: ZCT 공통단자
ABG
: 통신(RS-485)단자
DA: (+), DB(-), DG(통신접지), 통신용접지는 외함 접지단자와
분리하십시요.
Wiring
T1~T32
: “a”
접점(각회로와 동일함)
Tcom
: Common 접점
PP PN
: AC 110/220V(DC110V)Aux, Power
Ta Tb Tc
: 일괄 Alarm 접점
E
: 외함 접지단자(E3)
Z1~Z32
: ZCT 각회로 단자
Zcom
: ZCT 공통단자
ABG
: 통신(RS-485)단자
DA: (+), DB(-), G(통신접지), 통신용접지는
외함 접지단자와 분리하십시요.
108
DEESYS TOTAL PRODUCTS GUIDE
D2K-ED Series Earth Leakage Detector & Relay
Terminal arrangement
�8C, 16C, 24C, 32C
Dimension
�8C
� 16C, 24C, 32C
DEESYS TOTAL PRODUCTS GUIDE
109
한국검정공사 형식승인품
전자기 적합성 시험필
Earth Leakage and
Ground Fault Relay
■Multi Function Earth Leakage Detector and Fire Alarm
■Earth Leakage Fire Alarm and Relay [ELR] 1C, 5C, 10C
■Earth Leakage Relay [ELR] 1C
■Multi Function Ground Relay [GFR] 5C, 10C
■Aux Relay Board [Isolation] 5C, 10C
■Ground Fault Relay 1C
누전경보기
지락검출계전기
(Analog/MICOM) (Analog/MICOM)
DEESYS TOTAL PRODUCTS GUIDE
111
Multi Function Earth Leakage Detector & Fire Alarm
누전경보기를 설치행야 할 시설물(소방법 제 29조 3항)
누전경보기를 설치해야 할 소방 대상물(내화구조가 아닌 건축물로서 벽∙바닥 또는 반자의 전부나 일부를 불연재료 또는 준불연재료가 아닌 재료에 철
망을 넣어 만든것에 한한다)은 다음과 같다. 다만 가스시설 또는 지하구의 경우에는 그러하지 아니하다.(개정 94.7.20, 97.9.27)
연면적 500㎡∙이상(업무시설∙통신촬영시설 교육연구시설 및 전시시설의 경우에는 1,000㎡이상)인 것(개정 94.7.20)
계약전류용량(동일 건축물에 계약종변이 다른 전기가 공급되는 경우에는 그중 최대계약전류 용량을 말한다)이 100암페어를 초과하는 것
Facilities requiring installation of leakage detection and fire alarm devices:
<As per the enforcement laws articles 17-8, 18-6, and 19-7 of the laws for prevention and extinguishing of fires>
Objective facilites
Aggregated area
Contract current capacity
-Hotels, Motels
300㎡ or more
Above 100A
-Dorm Inatories
All lines below same as above
All lines below same as above
500㎡ or more
Above 100A
All lines below same as above
All lines below same as above
100㎡ or more
Above 100A
All lines below same as above
All lines below same as above
Class Ⅰ facilities per article 17-8
-Theaters, Stadiums
-Conference halls, Restautrants
-Public markets, Supermarkets
-Hospitals
-Welfare institution for the seniors
-Welfare institution for the handicapped
-Kindergartens
-Bathhouseds
Class Ⅱ facilities per article 18-6
-Rail stations & Bus terminals
-Passenger’
s waiting rooms
-Churches & Temples
-Multi-family housings of 4 stories and up
-Schools
-Exhibition halls
-Factories and Work places
Class Ⅲ facilities per article 19.7
-Warehouses
-Garages
-Hangars
112
DEESYS TOTAL PRODUCTS GUIDE
Multi Function Earth Leakage Detector & Fire Alarm [ELD]
Optional Specification
(For example)
∙DED-M10 : Set MICOM type
ELD 10 circuit
∙DED-A05 : Set ANALOG type
ELD 5 circuit
DE D 05 : 5 circuit Set type
10 : 10 circuit Set type
D : General
Alarm
Purpose
R : Relay(Trip)
M : Micom
A : Analog
Rating and Performancea
Description
Model No
Type approval No
Rated supply voltage
Rated supply frequency
Nominal operating current
Current
Micom type
Analog type
DED-M10(10C)
DED-M05(5C)
DED-A10(10C)
DED-A05(5C)
07-4
07-5
07-17
07-12
AC:110/220V in common
50/60㎐
0.2~0.5~1.0A(3 steps) ZCT Input:200㎃/100㎷
Operating
53%~75% of nominal operating current 1sec 이내
Non operating
52% nominal operating current
Allowable supply voltage fluctuation
Reset Method
Warning circuit voltage
80%~120% of rated supply voltage
Manual/Automatic
Below AC 600V
Leakage level:Digital
LED indication
Leaking circuit: RED LED
Leaking circuit: RED LED
Warning:RED LED
Warning:RED LED
Power supply:GREEN LED
Power supply:GREEN LED
ZCT continuity:YELLOW LED
ZCT continuity:YELLOW LED
Cont/Auto-alarm:YELLOW LED
Cont/Auto-alarm:YELLOW LED
Buzzer alarm:YELLOW LED
Buzzer alarm:YELLOW LED
Power consumption
3.5VA
3.0VA
8VA
6VA
Operating
6.0VA
5.5VA
9VA
7VA
Ambient temperature
Sound level
-10℃(Thru + 50℃)
Buzzer(more than 75dB)
Primary-case
Insulation resistance
Secondary-case
100㏁ or more (Tested by 500V megger)
Primary-Secondary
Primary-case:1500V
Dielectric strength
Secondary-case 500V
AC 60㎐, 1Min
Primary-Secondary:1500V
Impluse wave withstand voltage
Vibration strength
Mechanical shock resistance
Contact point capacity
Duration of wave tail:30~50㎳ and up
On duty:Full wave width 1㎜, 1000rpm, 10min
Not on duty:Full width 4㎜, 1000rpm, 60min
On duty:Natural drop 15 times
Not on duty:Accelebration of 5㎏ Max force in any direction for 5 times
1a:AC 250V,0.5A or DC 30V, 2A / contact
Fuse rating
Weight
Peak value:6.0㎸, Duration of wave front:0.5~1.5㎳
Between terminals
Power supply terminals to case
0.1A
1.9㎏
0.2A
1.7㎏
2㎏
1.9㎏
Casing
ABS Resin/Black N1.5
Mounting method
Flush mounting
DEESYS TOTAL PRODUCTS GUIDE
113
Multi Function Earth Leakage Detector & Fire Alarm [MICOM]
DED-M10
특징
Features
1. 집합형 누전 경보기는 다회로의 누전을 동시에 감지하여 경보 또는
차단기를 Trip시키는 기능으로 구성되어 있습니다.
2. MCU (A/D converter)내장을 주회로에 장착하여 선로 점검에 필
요한 기능을 디지털로 표지하여 주는 다기능 누전 경보기입니다.
3. 고장 선로 및 누전 전류량을 연산하여 DISPLAY 에 표시, 확인할
수 있고, 복구 조치에도 용이 합니다.
4. 자기 감시 기능을 수용하여 동작에 안정성을 기하였으며 다양한
LED 표시 기능으로 수신기의 동작 상태를 쉽게 판별할 수 있습니
다.
5. 자체 시험 스위치 및 도통 스위치를 사용하며 자체적으로 내부회로
를 검사할 수 있습니다.
1. Multi type earth leakage detector has alarm or CB trip
function with detecting multi circuit leakage.
2. As equipped with MCU(A/D converter) at main circuit, it is
multi function earth leakage alarm unit with digital display
for detection circuit.
3. Available to check leakage current armount and leakage
lines.
4. As equipped with self detecting system, easy to check
operation condition stably with various LED indication
function.
5. Self detecting and checking system make it be easy to
inspect internal circuit.
Front plate
1. Leaking line number indicator
2. Leaking level indicator(mA)
3. Line current check
4. Self-test button(switch)
5. Leaking circuit indicator lamp
6. Sensitivity selector switch
7. ZCT continuity indicator lamp
8. ZCT continuity test button(switch)
9. Cont/Auto warning lamp
10. Cont/Auto selector switch
11. Buzzer on/off warning lamp
12. Buzzer on/off switch
13. Reset switch
14. Power supply indicator lamp
15. Warning lamp
114
DEESYS TOTAL PRODUCTS GUIDE
Multi Function Earth Leakage Detector & Fire Alarm [MICOM]
기능별 명칭 및 설명
1. 누전회로 표시부
누전이 발생한 선로를 숫자로 표시합니다.
2. 누전량 표시부
누전이 발생한 선로의 누전량을“mA”단위로 표시합니다.
3. 회로검사 스위치 (TACT)
회로검사 스위치를 1회 누를때마다 한 선로씩 회로 표시와 누전
량이 해당 표시부(①,②)에 표시됩니다.
4.자체시험 스위치(TACT)
누전 경보기의 모든 기능을 일괄적으로 검사하는 스위치로 누전
회로 표시부, 누전량 표시부, 회로별 누전 표시등, 지속/자동 주의
등, 경보등, 부져 주의등을 점등하여 각 기능의 이상유무를 확인
합니다.
5. 회로별 누전 표시등(적색 LED)
누전 발생시나 자체 시험 스위치를 눌렀을 경우 또는 도통 스위
치를 눌렀을 경우 해당 회로의 표시등이 점등 됩니다.
6. 감도 설정스위치
0.2/0.5/1.0A의 탭중 설정된 값 이상의 누전이 발생시 경보 또는
트립 시킵니다.
7. ZCT 도통 표시등(황색 LED)
8. ZCT 도통 스위치(PUSH)
변류기가 수신부의 각 회로 단자에 정상적으로 연결되었을 경우,
도통 스위치를 누르면 해당 회선의 도통 표시등이 점등되고 실제
누전과 동일한 시험기능입니다.
9. 지속/자동 스위치 주의등(황색 LED)
10. 지속/ 자동 선택 스위치
지속/자동 스위치를 자동으로 설정하였을 경우에는 지속/ 자동
스위치 주의등이 점멸하여 스위치 상태가 자동에 설정되어 있는
것을 경고합니다.
11. 부져 ON/OFF 주의등(황색 LED)
12. 부져 ON / OFF 선택 스위치
부져 ON / OFF 스위치는 OFF로 설정하였을 경우에는 부져
ON/OFF 주의 등이 점멸하여 스위치 상태가 OFF에 설정되어 있
는 것을 경고합니다.
13. 복귀(Reset)스위치
수신부의 전 기능을 초기 감시 상태로 환원 시키는 스위치입니
다.
14. 전원등(녹색 LED)
전원전압 (AC 110/220V)이 정상적으로 공급될 때 점등됩니다.
15. 경보등(적색 LED)
누전 발생시 또는 회로 시험시 점등됩니다.
Component Parts and Functions
1. Leaking circuit indicator
It indicator leakage fault circuit number on LED.
7. ZCT continuity indicator lamp(Yellow LED)
It lights to indicate continuity.
2. Leakage level indicator
It indicates the level of leakage in mA unit.
8. ZCT continuity switch(Push button type)
If the switch is pressed on condition that current
transformer is connected to applicable line terminals of
the receiving part, the continuity lamp of the line turns
on enabling to perform leakage test in simulated
circumstance of real leakage.
3. Circuit test button(Tact type)
At each time button<or switch>is pushed. circuit is newly
selected one by one with the indication of circuit
number and level of leakage. It is convenient to check
levels of leakages of each line though it happens in
plural number of circuits at a time.
4. Self-test switch(Tact type)
It is used to check as a whole any abnormality in
performance of every functional components like leaking
circuit indicator, leakage level indicator, leakage fault
line indicator lamps, cont./auto warning lamp, alarm
lamp and buzzer warning lamp.
5. Leakage fault indicator lamp by line<Red LED>
In case to leakage fault, the lamp of subject line turns
on uncondition of continuity button(or switch) is pressed
or self-test switch is pressed.
6. Sensitivity selector switch
Sensitivity is adjusted by the switch to an one among
three steps of 0.2./0.5/1.0A as appropriate to specific
line.
9. Continue/Auto warning lamp(Yellow LED)
10. Continue/Auto selector switch
If Auto, position is selected by Cont/Auto switch, the
continue/Auto selection warning lamp blinks to call
attention on the setting.
11. Buzzer on/off warning lamp(Yellow LED)
12. Buzzer on/off selector switch
If the switch is set to off, the buzzer on/off warning lamp
blinks to warn the selected switch position.
13. Reset switch
If pressed, it activates entire receiver function to initial
status.
14. Power supply indicator lamp(Green LED)
It turns on only when power(AC110-220)(AC240V) is
supplied normally.
15. Alarm lamp(Red LED)
It lights in case of leakage occurrence and testing.
DEESYS TOTAL PRODUCTS GUIDE
115
Multi Function Earth Leakage Detector & Fire Alarm [MICOM]
동작 특성 설명
1. 집합형 누전경보기는 여러 회로를 집합하여, 동시에 감시하며 전
원장치 및 경보장치를 1조로 하여 구성된 경보기입니다.
2. MCU의 선로 감시 명령에 의해 모든 경계선로를 동시에 감시 합
니다.
3. 경계 선로에 누전이 발생하면 경계 선로에 설치한 영상 변류기에
서 전압이 출력되어 수신부의 누전검출 회로에 입력됩니다.
4. 입력 전압은 증폭되어진후, 중앙처리장치에 입력됩니다.
5. 중앙처리장치(MCU)는 증폭된 입력전압을 A/D로 변환하고 감도
설정된 기준값과 비교한 후 일정 비율 이상이 되면 다음과 같이
경보 표시합니다.
① 경보등(적색LED)의 해당 회로가 점등됩니다.
② 부져를 동작시켜 경보합니다.
③ 회로별 누전표시등(적색LED)의 해당 회로가 점등됩니다.
④ 누전 회로 표시 디지털에 누전회로가 숫자로 표시됩니다.
⑤ 누전량 표시 디지털에 누전회로의 누전량이 (mA)단위로 표시
됩니다.
(주의) 지속/자동 스위치를 자동으로 설정하였을 경우 지속/
자동 스위치 주의등(황색 LED)이 점멸하고, 누전량이 없어졌
을 경우 자동적으로 모든 경보표시가 소멸됩니다.
(주의) 부져 On/Off 스위치를 Off로 설정하였을 경우부터
On/Off 주의등(황색 LED)이 점멸하고 기준치 이상의 누전이
발생하여도 경보음은 울리지 않습니다.
6. 표시확인
두 개 이상의 선로에 누전이 발생하였을 경우, 회로별 누전표시
등은 누전선로를 전부 점등하지만, 누전회로 표시 디지털과 누전
량 표시 디지털에는 가장 먼저 누전이 발생한 선로의 값만 표시
합니다. 다른 선로의 값을 확인하고자 할 때에는 회로검사 스위
치(TACT)를 눌러 각 회로의 누전량을 점검할 수 있습니다.
7. 복귀(RESET)
선로의 누전상태를 보수한후 지속/자동 스위치가 지속으로 설정
되어 있을 경우에는 누전표시가 지속되므로 복귀 스위치를 눌러
수신부의 기능을 환원시켜야 합니다.
Performance Features
1. Being a set type leakage detector, it sets and monitors
plural number of line circuits simultaneously and features a
combination of power supply and alarm system in a unit.
2. According to line monitoring instruction from MCU, it
monitors all lines hooked simultaneously.
3. In case leakage is developed in any monitored line, the
residual current transformer generates voltage which is
fed to the leakage detection circuit of receiver as an input.
4. The input is amplified and then fed to MCU for processing.
5. At MCU, amplified input is converted by A/D converter
for comparison against the voltage one of selected
sensitivity. And if a ratio higher than predetermined value
is obtained, warnings become activated as follows ;
1) Alarm lamp(Red LED) turns on.
2) Buzzer-alarm.
3) Leakage fault line indicator lamp(Red LED) of subject
line turns on.
4) Leaking line number is circuit indicator.
Internal block diagram
116
DEESYS TOTAL PRODUCTS GUIDE
5) Leakage level indicator displays lever of leakage in
mA nuit.
Note 1 : When Cont/Auto switch is set to auto. position,
warning lamp(Yellow LED) will blink and when
the leakage stops, all warnings and alarm will
be canceled.
Note 2 : When buzzer on/off switch is set to off position,
warning lamp(Yellow LED)will blink and will not
alarm if the leakage exceeds the critereon.
6. Clarification of warning indications in case two or more
lines is leaking concurrently, the leaking line indicator
lamps of such line will all light concorrently, but the
leaking line number indicator and leaking level indicator
will display the value of first detected line only. Leaking
level of other lines can be checked by pressing the line
test switch(Tact type).
7. Reset if Cont/Auto switch remains after the leakage is
removed, reset to cont, position.
Multi Function Earth Leakage Detector & Fire Alarm [MICOM]
설치전 점검 사항
경보기를 설치하기전 다음 사항을 점검하여, 경보기의 기능을 확인
하시기 바랍니다.
1. 수신부의 P0, P1 단자에 전원 전압(AC220V)을 연결하십시오. 만
약 AC 110V를 사용하실 경우 뒷면의 슬라이드 스위치를 AC
110V로 전환 조정하여 사용하십시오.
2. 전원을 연결한 후, 뒷면의 On/Off 스위치를 On으로 설정하면 전
원 투입상태 (전원 LED 점등)가 됩니다.
3. 회로검사 스위치(TACT)를 눌러 디지털 표시를 점검합니다. 스위
치를 누를 때마다 누전 회로 표시가 1회로씩 순차적으로 변환되
고 누전량은 000 을 표시합니다. 스위치를 누르지 않고 약 5
초가 경과하면 자동으로 표시가 소멸됩니다.
5. 다음은 회로시험 및 ZCT 도통 스위치를 회로별로 눌러 회로 시
험을 합니다. 각 회로별 스위치를 누르면 회로별 누전표시 LED
와 경보 LED가 점등되고 누전회로 표시 디지탈에는 해당회로,
누전량 표시 디지탈에는 999 를 표시합니다. 개별 시험 후 복
귀 S/W를 눌러 초기상태 복구시키십시오.
6. 지속/자동 S/W를 자동(LED 점멸상태), 부져 On/Off S/W를
Off(LED 점멸상태)로 설정하고 5항의 시험을 행하십시오. 이때
부져는 울리지 않고 모든 표시 장치는 자동으로 환원됩니다.
(주의 : ZCT 도통 LED(황색)는 회로별 단자에 ZCT를 접속한 후
도통 스위치를 눌러야 점등합니다.)
7. 이상의 시험이 끝나면 On/Off를 Off로 한 후 전원을 제거하십시오.
4. 자체시험 스위치를 눌러 수신부의 내부회로를 점검합니다. 스위
치를 누르면 도통 LED(황색)를 제외한 모든 표시장치와 경보장치
가 자동적으로 차례로 동작한 후 초기상태로 환원됩니다. 이때 누
전회로 표시 디지털과 회로별 누전표시 LED는 자동적으로 하나
씩 증가하고 누전량은 888 을 표시하여 디지털 Segment의
이상 유무를 확인합니다.
Checking Items Before Installation
The following points should be checked before installation
to ensure operability.
1. Connect control power(AC 220V) to terminals P0 and P1
of ELD(Note: Since the control power is set to AC220V at
factory on delivery, convert slide switch on the back of
ELD to AC110V if it is used AC110V for control power)
2. After connecting control power to the terminals, set
power on/off switch to "on" position to energize the
detector(Red LED turns on).
3. Check digital display of leaking line number indicator
and leaking level indicator by pressing line test
switch(Tact type). Every time the switch is pressed the
line number on display advances to very next higher
number in burn and the leakage level indicator will
display zeros. After an elapse of about 5 minutes without
additional pressing, the indications will disapear
automatically.
4. Check intenral circuits by pressing selftest switch. If the
switch is pressed, all displays and alarms turn back
initial stage automatically one by one except the
continuity indicator lamp(Yellow LED) At that times the
display of leaking line indicator changes the display
sequence by with steps by one at each time when the
switch is pressed and leakage level indicator will
unchange to show Adn thus check of digital segment is
accomplished.
5. Check lines by pressing line test and ZCT continuity
switch. When line test switch is pressed, line leakage
indicator LED and alarm LED turn on. And leaking line
number indicator will display leaking current of subject
line number. After checking all items, return in initial
stage by pressing the return s/w
6. Repeat checks of paragraph 5. set Cont/Auto switch to
Auto. Position(LED blinks) and buzzer on/off switch to
off(LED blinks). At this time, the buzzer does not sound
and all indicators return to automatically.(Note: ZCT
continuity indicator LED (Yellow) will turn on only when
ZCT is connected before the continuity test is performed.)
7. After completion of all check ups in preceeding
paragraphs, set the power on/off switch to 'off' and take
off control power from the terminals.
DEESYS TOTAL PRODUCTS GUIDE
117
Multi Function Earth Leakage Detector & Fire Alarm [MICOM]
설치시 점검사항
Checking Items for Installation
1. 설치하고자 하는 장소에 수신기의 치수에 맞게 제작 설치합니다.
2. 경계선로에 ZCT를 선정합니다.
1)부하용량에 맞게 ZCT를 선정합니다.
2)대전류 모선 혹은 강한 자장으로부터 10cm 이상의 위치에 설치
하여 주십시오.
3) 단상,3상 구별없이 부하 선로에 설치합니다.
4) 3상 4선식인 경우도 중성선을 포함 4선을 모두 ZCT에 관통시
킵니다.
3. 수신기 뒷면 단자 결선
1) 변류기측 2개의 단자 중(단자의 극성구별은 없음) 1개는 수신부
각 회로 단자 ①. ②, ③, ④, ⑤, ⑥, ⑦, ⑧, ⑨, ⑩에 결선하고,
1개의 단자는 공통단자로 수신부 ⓩ 공통단자에 연결합니다.
2)단자 Ta,Tc(무전압접점)는 외부에 부져를 설치시 연결합니다.
3)단자(E)는 접지단자로 배전반 그라운드로 연결하십시요.
4. 수신기의 전원은 다른 회로 전원과 병렬로 연결하지 마시고 분기이
전의 별도 전원을 사용해야합니다.
1. Arrange a mounting panel suitable to the receiver and
install it on the desired location
2. Install ZCT on lines to monitor.
1) Select ZCT of adequate capacity for each line.
2) install ZCT lotated at 10cm or more distance current
bus or strong magnet field
3) Install ZCT on load side whether the power supply is
single phase or 3 phase.
4) In case of 3 phase 4 line system. all 4 lines including
the neutral should go through the ZCT.
3. Connections to terminals on back of receiver
1) The one terminal of ZCT,s two terminals (not distinction
of the polarity) should be connected to line terminals ①,
②, ③, ④, ⑤, ⑥, ⑦, ⑧, ⑨, ,⑩ and the other terminal
which is the common shall be to common terminal ⓩ of
the receiver.
2) The Terminal Ta and Tc(no voltage contacts) are used
when a buzzer is installed on the outside.
3) The terminal E for grounding should be connected to
the grounding terminal of distribution board.
4. The control power of receiver should be connected an
independent source which is not distributed from main
source
설치후 점검사항.
Checking Items After Installation
1. 전원등이 점등되었는지 확인합니다.
2. 회로 시험 및 ZCT도통 스위치를 약 1초간 눌러 각 회로별 동작상
태 및 해당회로의 ZCT 도통 LED가 점등되는지 확인합니다.
만약 점등되지 않을 시에는 해당 단자의 연결상태를 점검하시기 바
랍니다.
3. 복귀 스위치를 눌러 수신부의 전기능을 초기감시상태로 환원시킵니
다.
4. 회로 검사 스위치를 눌러 각 회로의 누전량을 확인하시기 바랍니다.
5. 회로에 기준치 이상의 누전이 발생했을 시, 누전회로 표시 디지털과
누전량 표시 디지털에는 최초의 누전 전류값이 표시되고 회로별 누
전 표시등에는 고장 회로가 전부 점등됩니다.
6. 회로의 누전량이 1.0A를 초과할 경우에는 999 를 표시합니다.
1. Check whether the power lamp is turned on or not
2. Press circuit test switch and ZCT continuity switch
during about one second and Check whether circuits
are in normal status and ZCT continuity indicator lamp
turns on. If the lamp do not turn on, please check up
the connection of respective terminals.
3. Please Initialize entire receiver function by pressing
reset button.
4. Check levels of leakage on each circuit by pressing
circuit test switch.
5. In case of a leakage exceeding the criterea, leaking
circuit number indicator and leakage level digital
indicator will display the first detected leaking circuit
number and its level of leakage while leakage fault
indicator lamps will indicate leaking lines individually.
6. If the leakage level exceeds 1.0A, the 999 will display
on the leakage level indicator.
118
DEESYS TOTAL PRODUCTS GUIDE
Multi Function Earth Leakage Detector & Fire Alarm [Analog]
DED-A10
동작 특성 설명
Performance Features
전기적 환경에 대한 서지보호 대책으로 전자기 적합성 시험을 필한 제
품으로 어느 환경에서나 사용가능하며 전기적 환경에 대응할수 있는
회로를 추가하여 제작된 제품입니다.
1. In case of leakage, output voltage that is induced in the
current transformer is storaged to leakage detection circuit.
2. Receiver adjusts input voltage deriving to leakage to
sensitivity scale for comparison with the criterion. And if the
value is determined to be exceeding the criterion, it
generates warning and alarm as follows.
1) The alarm lamp(Red LED) turns on.
2) The buzzer sound on to sign the fault.
Note : If buzzer on/off switch is set to off, position buzzer
on/off lamp will blink without sounding.
3) Leaking circuit indicator lamp (Red LED) of the
applicable circuit turns on or off.
Note : If Continue / Auto switch is set to Auto position,
continue / Auto warning lamp will blink. When the
leakage is stopped or the circuit is recovered to
normal state, the alarms of subparagraphs 1) and 2)
will automatically disappear.
3. Reset
If Continue / Auto switch is set to continue position, press
reset button to initiaize receiver function as soon as the
leakage defect is removed.
1. 선로에 누전이 발생하면 해당 선로 변류기의 출력 전압이 누전 검출
회로에 입력되어 집니다.
2. 수신부는 누전 검출 전압을 감도 조정 회로에 의해 재조정한 뒤, 비
교 판정을 하고 기준치 이상이 되면 다음과 같이 경보 표시 합니다.
① 경보등(적색 LED)을 점등합니다.
② 부져를 동작시켜 경보합니다.
(주의 : 부져 on/off 스위치를 off로 설정하였을 경우에, 부져
(on/off 주의) 등이 점멸하고 부져는 동작하지 않습니다.)
③회로별 누전 표시등(적색 LED)의 해당 회로가 점등됩니다.
(주의 : 지속/자동 스위치를 자동으로 설정하였을 경우에는 지속/
자동주의 등이 점멸하고, 누전이 복구되거나 없어졌을 때 자동적
으로 위 ①,②항의 경보표시가 소멸됩니다.
3. 복귀(Reset)
선로의 누전상태를 보수한 후 지속/ 자동 스위치가 지속으로 설정
되어 있을 경우에는 복귀 스위치를 눌러 수신부의 기능을 초기 상
태로 환원합니다.
Internal block diagram
DEESYS TOTAL PRODUCTS GUIDE
119
Multi Function Earth Leakage Detector & Fire Alarm [Analog]
설치전 점검사항
Checking Items Before Installation
※ 경보기를 설치하기전 다음 사항을 점검하여, 경보기의 기능을 확인
하시기 바랍니다.
Note : Check following items to ensure normal function of the
device before installation
1. 수신부의 P0,P1 단자에 전원 전압(AC 220V)를 연결하고 뒷면의 전
원 on/off 스위치를 on으로 설정하십시요.
(경보기의 전원 전압은 공장 출하시 설정치가 AC 220V입니다. 만
약 AC 110V를 사용하실 경우 뒷면의 슬라이드 스위치를 AC 110V
로 전환 조정하여 사용하십시오.)
1. Connect power line (AC 220V) to terminals P0 and P1 of
the receiver and set power on/off switch to on position.
(The power is set to AC 220V at factory for delivery. If AC
110V is used, set the position of selector switch to AC
110V position.)
2. 전원등 (녹색 LED)이 정상적으로 점등되면, 회로 시험 및 ZCT 도
통 스위치를 회로별로 눌러 회로시험을 합니다. 각 회로별 스위치
를 누르면 회로별 누전 표시 LED와 경보 LED가 점등되고 경보음
이 울립니다. 개별 시험후 복귀 스위치를 눌러 초기상태로 복귀시키
십시요.
2. When power lamp (Green LED) is turned on to indicate
normal status, carry out circuit tests by pressing circuit test
switch and act continuity switch for each circuit. When
circuit test switch of a line is pressed, leakage indicator
LED and warning LED of the circuit turn on with alarm.
When the test is over, intialize all the funclion by pressing
reset button.
3. 2의 시험을 지속/자동 스위치를 자동에, 부져 on/off S/W를 off로
설정하고 재차 행하십시요. 이때 부져는 울리지 않고 모든 표시장치
는 자동으로 환원됩니다.
(주의: ZCT 도통 LED는 회로별 단자에 ZCT를 접속한 후 도통 스
위치를 눌러야 점등합니다.)
4. 이상의 시험이 끝나면 뒷면의 on/off 스위치를 off 상태로 전환한후
전원을 제거하십시요.
3. Repeat the testing explained in above paragraph 2 with
Cont/Auto switch that is set to Auto position and buzzer
on/off switch that is set to off position. In this instance.
/and buzzer will not sound and all the indicators will return
to normal status automatically.
(Note : ZCT continuity LED will light only when ZCT is
connected to circuit terminals and continuity test switch is
pressed).
4. After the completion of above tests, return the power
switch on back panel that is set to off and then remove
power connection
설치후 점검 사항.
1. 전원등이 점등되었는지 확인합니다.
2. 회로시험 및 ZCT 도통 스위치를 눌러 각 회로별 동작상태 및 해당
회로의 ZCT도통 LED가 점등되는지 확인합니다. 만약 점등되지 않
을 시에는 해당 단자의 연결상태를 점검하시기 바랍니다.
3. 복귀 스위치를 눌러 수신부의 전기능을 초기감시상태로 환원시킵니
다.
120
DEESYS TOTAL PRODUCTS GUIDE
Checking Items After Installation
1. Check whether power supply lamp is turned on or not
2. Press circuit test switch and ZCT continuity switch. And
check whether if circuit state indicator lamp and ZCT
continuity indicator lamp of the circuit turn on. If no, check
connections of terminals.
3. Initialize the performance of receiver by pressing reset
button.
Multi Function Earth Leakage Detector & Fire Alarm [Analog]
External terminal arrangement
BZ:BUZZER
: AC 110/220 Selection S/W
: Power ON/OFF S/W
ⓕ:FUSE
P , P₁: 110/220V Common
0
Ta Tc : Warning relay contacts(no voltage)
1~10 : ZCT Secondary circuit terminals
Z : ZCT Secondary circuit common terminal
E : Grounding terminal
NC : Idle terminal
Leakage detector external wiring
1. In case of 3 phase 4 line power system, go through all 4
lines into ZCT.
2. Control power shall be connected to P0 and P₁for AC
110/220V in common(Check setting of voltage selector
switch).
3. Terminal Ta and Tc. (no voltage) is used to connect
externally installed buzzer and warning lamps.
4. Terminal Z is common to all circuits. That all common
terminals shall be connected to terminal Z.
5. Terminal E is for grounding, It should be connected ground
terminal on terminal Z.
6. Use power service outlet for it self alone without tapping.
※ ZCT Common단자는 내부에서 연결이되어 있으므로 한단자만 사용해도 됩니다.(10C만 해당)
External dimension(ELD-M10/M05,ELD A10/A05)
Cutting Size: 165 X 122mm
DEESYS TOTAL PRODUCTS GUIDE
121
Earth Leakage Fire Alarm & Relay [ELR]-1C, 5C, 10C
Features
Flush mounted type
1. This earth leakage relay have same function with earth
leakage detector and is more developed relay that is able
to use the external terminal
※How to use the external terminal.
1) control at same time trip equippment and earth indicator
& detector at same time.
2) useing for leakage fault indicator of central control
board
3) Use timer for delaying the trip time of C∙B on leakage
fault
Soket type
Specification
Micom type
Description
Model No
Type approval No
Analog type
DER-M10/M05
DER-A10/A05
07-9
07-8
Installation
07-3
07-7
DER-F03
DER-F11
DER-F12
DER-P03
DER-P11
DER-P12
승인미필
07-21
07-22
07-15
07-6
07-11
10c Flush mounted
1c Flush mounted
Auxiliary voltage
AC110/220V
Frequency
50/60㎐
Nominal operating current(A)
Current
1c Socket type
0.2-0.5-1.0
0.03-0.05-0.07-0.1
0.1-0.2-0.3-0.5
Operating
53%~75% of nominal operating current 1sec 이내
Non operating
52% nominal operating current 30sec 이내
Allowable supply voltage fluctuation
0.2-0.5-0.7-1.0
0.03-0.05-0.07-0.1
0.1-0.2-0.3-0.5
0.2-0.5-0.7-1.0
80%~120% of Rated Voltage
Reset
Manual/Auto(Muiti type)
manual
Warning circuit voltage
Less than AC 600V
Leakage indicator : Digital
Leaking circuit indicator:Digital LED(Red color)
LED indicator
Buzzer alarm indicator : LED(Red color)
Detector indicator:LED(Red color)
Power indicator:LED(Green color)
Power indicator:LED(Green color)
ZCT penetration indicator:LED(Yellow color)
ZCT penetrationindicator:LED(Yellow color)
Continue/Auto-alarm:LED(Yellow color)
Continue/Auto-alarm:LED(Yellow color)
Buzzer alarm:LED(Yellow color)
Buzzer alarm:LED(Yellow color)
Detector alarm indicato:LED(Red color)
Power consumption
Non operating
4.5VA/4VA
9VA/7VA
Operating
7VA/6.5VA
10VA/8VA
ZCT(Input)
2.5VA
3VA
200㎃/100㎷
Ampient temperature
-10℃+ 50℃
Sound level
Buzzer(more than 75dB)
Primary-case
Insulation resistance
Secondary-case
more than 100㏁ (DC 500V megger)
Primary-Secondary
Primary-case:1500V
Dielectric strength
Secondary-case:500V
AC 60㎐, 1miniute
Primary-Secondary:1500V
Impluse wave withstand voltage
Vibration strength
Mechanical shock resistance
Contact capacity
Between-terminal
Power terminals-case
On duty:Full wave width 1㎜, 1000rpm, 10min, Not on duty:Full wave width 4㎜, 1000rpm, 60min
On duty:Natural drop 15times
Not on duty:Accelebration of 50g Max force in any direction for 5 times
AC 250V 3A, DC 30V 5A
Rate of fuse
Weight
Casing
0.2A
2.0/1.8㎏
DEESYS TOTAL PRODUCTS GUIDE
0.1A
2.1㎏/2.0㎏
0.7㎏
ABS Resin/Black N1.5(난연성 Non-flamable)
※ELR F03 사용시 SZR(니켈코어)을 사용해야 합니다.
122
Peak value : 6.0kV, 1.2/50㎲
0.7㎏
0.7㎏
0.5㎏
0.5㎏
0.5㎏
Earth Leakage Fire Alarm & Relay [ELR]-1C, 5C, 10C
Internal wiring connections
External wiring of circuit
breaking for leakage on load side
External wiring of central control board
leakage fault indicator
BUZZER contact(No Voltage)
※ ZCT Common단자는 내부에서 연결이되어 있으므로 한단자만 사용해도 됩니다.(10C만 해당)
External terminal arrangement
DEESYS TOTAL PRODUCTS GUIDE
123
Earth Leakage Relay [ELR]-1C
External wiring diagram
Installation diagram
Example for usage (leakage)
Tripping
For load break
Tripping after setting
For time delay
Internal block diagram
Cutting Size: 56x94mm
124
DEESYS TOTAL PRODUCTS GUIDE
※Dimension은 136page를 참조하십시오
Multi Function Ground Fault Relay [GFR]-5C, 10C
특징
DGF-M10
1) 집합형 지락검출계전기는 다수(10C 또는 5C)의 경계선로의 지락전류를 동시에 감지하며 각 선로의 현재
의 지락 전류량과 사고시 사고지락 전류량을 표시할 수있는 다기능 계전기입니다.
2) 8BIT MCU(A/D CONVERTER 내장)를 주회로에 첨단기능을 장착하여 신뢰성을 향상시켰습니다.
3) 종래의 단회로 지락검출계전기를 다수의 회로(5~10회로)를 1대에 수용한 집합형 계전기입니다.
4) 경지락 전류(0.1A)부터 중지락 전류(10A)까지 검출 가능합니다.
5) 배전선 보호 협조에 용이하도록 동작시간정정탭을 구성하였습니다.
6) 다양한 표시기능으로 CHECK 기능을 향상시켰습니다.
7) 자기감시기능(WATCHDOG FUNCTION)에 의해 오동작을 자체 방지합니다.
8) 각 선로의 최종 지락사고후 전류량을 메모리에 기억하므로 사고후 대책이 용이합니다.
9) 외부 케이스를 ABS 제품으로 대체하여 제품의 내구성을 향상시켰습니다.
10) E. M. C에 대한 시험을 하여 SURGE 및 고주파의 영향을 받지 않습니다.
※ 주) GFR 사용시 Aux, Ready Board 내장형과 외장형을 다음 페이지에서 구분 적용하여주시기 바랍니다.
Features
1. Multi-ground fault relay(GFR) is multi-functional and is able to detect multiple ground faults of monitoring circuit and is displayed
leakage in the circuit and fault current when earthing.
2. It is installed 8 bit MCU with A/D conventer and is configured to perform advanced functions for high relability.
3. It is a collective device that is intergrated many ground fault detector of conventional single unit.
4. It is capable to detect from minor grounding fault current(0.1A) to medium level fault current (10A)
5. It is configured to have operating time taps for adjustment of time setting is easy for protection coordination of distribution circuit
6. As wide display and indicators, it is able to enhance checking up and performance.
7. Watch dog function assures error - free operation.
8. The memory stores the last record of ground fault current of each circuit to facilitate following up in the event of accidents.
9. The ABS casing newly adopted offers improved durability and extended life of product.
10. All GFRs are tested EMC to ensures and high frequency & surge do not interfere design performance of GFR.
Rating & Specification
Items
DGF-M10(For 10 Circuits
DGF-M05(For 5 Circuits)
Testign Institute
Korea Electric Research Institute
Usage
for protection against minor and major ground Leakage faults
Control Power Voltage
AC 110/220V Operable in Common or AC 240V
Frequency
50/60㎐ Operable in common
Operating current setting
9steps, of 0.1, 0.3, 0.5, 1, 2, 3, 5, 10 and Lock T:70% to 100% of current setting
Operating Time setting
9steps, of 0.05, 0.1, 0.3, 0.5, 1, 2, 3, 5, 10sec T:±10% for 0.05 T=0.1±25㎳
Ground Fault Detection Circuit
10Circuits
5Circuits
Operating status Indicator
LED (Red) and Digtal Display one for each Circuit
Resetting
Auto/Manual
Ambient Temperature
Vibration Resistance
Impact Resistance
Common frequency
dielecric resistance
Insulating Resistance
Power Consumption
-10℃~+50℃
Energized:Full vibration width 4㎜, 1000rpm, 10min
Deenergized:Full vibration width 4㎜, 1000rpm, 10min
Impact strength of 300㎨ applied to 3 axial directions of right & left. up & down, and behind & forward
Opn Cir-Casing : AC 2000V
Opn Cir-Opn Cir : AC 2000V
Test Cir-Terminals : AC 1000V
Opn cir Casing 10㏁ or more
Opn cir-Opn Cir : 10㏁ or more
Test Cir-Terminals : 10㏁ or more
Weight
by DC 500V megger
7VA
Contact Capacity
ZCT(input)
60㎐, 1min
5VA
AC 125V 5A/DC 30V 5A
2.0㎏
1.7㎏
ZCT Rating 200㎃/100㎷ (ZR, ZS, ZB type)
DEESYS TOTAL PRODUCTS GUIDE
125
Multi Function Ground Fault Relay [GFR]-5C, 10C
GFR 적용 구분 방법
Model
DGF-M05T
DGF-M10T
DGF-M05
DGF-M10
DRB-005. 010
Combination
None(Direct)
Contact
None
5C or 10C
Contact Capacity
DRB(Contact)AC 250V/10A
AC 250V/10A
Purpose
Trip(MCCB)
Alarm & Lamp, Trip(MCCB)
Front plate
1. Line check button
2. Monitored circuit indicator(Digital)
3. Earth leakage level indicator
4. Hold check
5. Auto/Menu
6. Ground fault indicator for each circuit
7. Ground fault sensing current setting switch
8. Operating time setting switch
9. Self-test button for each circuit
10. Sensing current and operating time
11. Reset button
12. Power lamp
13. Sensing current setting check button
14. Operating time setting check button
※ 주의사항
∙DGF-M10T, M05T 제품은 Breaker 차단용으로 Aux, Relay Board와 조합하여 사용하십시요.
∙DGF-M10, M05 제품은 경보 또는 Breaker 차단용을 위한 내장형으로 Aux, Relay Board 사용이 불필요합니다.
126
DEESYS TOTAL PRODUCTS GUIDE
Multi Function Ground Fault Relay [GFR]-5C, 10C
개요
1. LINE CHECK(회로검사 스위치)
회로검사 S/W를 한번 누를때마다 한선로씩 회로 표시와 현재 선
로의 지락전류량이 표시됩니다.
2. LINE CHECK(감시회로 표시디지털)
각 감시선로를 숫자로 표시합니다.
3. LEAKAGE CURR(지락전류량 표시디지털)
각 선로의 현재 지락전류량 또는 사고전류량을 표시합니다.
9. 회로별 자체시험스위치
각 회로별 자체시험 스위치를 누르면 해당 선로의 지락사고등이
점등되고 실제 지락과 동일한 시험을 합니다.(설정된 시간동안 누
르면 동작됨)
10. 감도전류 및 동작시간정정표
각 선로의 지락감도전류 및 동작시간을 설정할 때 참고로 하는
표입니다.
4. HOLD CHECK(사고전류량 확인스위치)
HOLD CHECK S/W 를 누르면 지락전류량 표시디지털에 각 선
로의 사고전류량이 표시됩니다.
11. 복귀스위치(RESET)
5. AUTO/MANUAL (자동/수동 복구 선택스위치)
자동/수동 선택스위치를 자동/수동 복구를 선택합니다.
12. 전원등(녹색 LED)
계전기에 전원전압(AC 110/220)이 정상적으로 공급될 때 점등됩
니다.
6. 회로별 지락사고표시등
지락사고 발생시, 회로별 자체시험 스위치를 누를 경우 해당회로
의 표시등이 점등됩니다.
7. 지락전류감도정정스위치
해당 선로의 특성에 맞게 0.1~10(A)중 선택하여 설정합니다.
계전기의 전기능을 초기상태로 환원시키는 스위치입니다.
(사고메모리 Reset 기능)
13. 감도전류 설정확인 스위치(Position Check)
각 선로의 지락감도 설정을 디지털에 표시하여 확인할 수 있습니다.
14. 동작시간 설정확인 스위치(Position Check)
각 선로의 동작시간 설정을 디지털에 표시하여 확인할 수 있습니다.
※ 주의: LOCK 위치 설정시에는 동작하지 않습니다. (선로 보수시)
8. 동작시간 정정 스위치
해당 선로의 특성에 맞게 0.05~10(S)중 선택하여 설정합니다.
Outline Information
1. Line Check Button
When the switen is pressed, one by one time monitored
circuit number is changed to next circuit number and
ground fault current level of the circuit is displayed.
2. Monitored Circuit Indicator(Digital)
It indicates monitored circuit number in numberals.
3. Earth Leakage Level Indicator
The level of earth leakage or fault current is displayed.
4. Hold Check Switch(Stored memory of fault current
level)
Pressing hold check switch, earth leakage level indicator
is displayed fault current of each circuit.
8. Operating Time Setting Switch
The switch is used to set required interval of operating
time from 0.05 to 10 seconds.
9. Self-Test Button
If the button of a circuit is pressed, the status of circuit is
simulated to real ground fault and ground fault indicator
lamp turns on to alarm fault status.
10. Sensing Current and Operating Time Reference Table
It is a table of current and time values that can be
quoted for current and time setting as the reference.
11. Reset Button
The button, if pressed, is intialized entire relay function.
5. Auto./Manual Switch
If the switch is set to auto position, warning lamp(Red
LED) turns on to warn the status of the switch setting.
12. Power Lamp(Green LED)
It turns on when the power of AC110/220V(or AC 240V)is
regularly supplied.
6. Ground Fault Indicator Lamp
The lamp of leaking circuit turns on when self-test
button of the same leaking circuit is pressed.
13. Sensing Current Setting Check Button
The button is used to display ground fault sensing
current setting for checking purpose.
7. Ground Fault Sensing Current Setting Switch
Select suitable step of sensing current between 0.1 and
10A rating as being reqired by characteristics of a line.
※Note : The relay does not operate in case of lock
position
14. Operating Time Setting Check Button
The button is used to display operating time setting of
circuit for checking purpose.
DEESYS TOTAL PRODUCTS GUIDE
127
Multi Function Ground Fault Relay [GFR]-5C, 10C
동작특성
1. 집합형 누전 검출계전기는 여러 회로를 집합하여 동시에 감시하
며 지락전류량 표시와 사고전류량 표시기능이 함께 내장된 계전
기입니다.
2. MCU의 선로감시 명령에 의해 모든 경계선로를 동시에 감시합니
다.
3. 경계선로에 지락전류가 발생하면 영상변류기에서 전압이 출력되
어 계전기의 지락전류검출회로에 입력됩니다.
4. 입력전압은 증폭처리된후 중앙처리장치에 입력됩니다.
6. 표시확인 : 두개이상의 선로에 지락사고가 발생하였을 경우, 회로
별 지락사고 표시등은 전부 점등하지만 지락선로표시 디지털과
지락전류량 표시 디지털에는 가장 먼저 지락사고가 발생한 선로
의 값만 표시합니다.
다른 선로의 값을 확인하고자 할 때에는 회로검사 스위치를 눌러
각 회로의 지락전류량을 점검할 수 있습니다. 만약 자동복구 상
태에서 이미 사고전류량이 소멸된 경우에는 HOLD CHECK 스위
치를 눌러 메모리된 사고전류량을 확인할 수 있습니다.
7. 복귀(RESET) : 선로의 사고를 보수한후 자동/수동 스위치가 수동
으로 설정되어 있을 경우에는 사고 표시가 지속되므로 복귀스위
치를 눌러 계전기의 기능을 환원시켜야 합니다.
5. 중앙처리장치는 증폭된 입력전압을 A/D로 변환하고 감도전류설
정값과 비교하여 설정값 이상이 될 때 다음과 같이 동작합니다.
① 동작시간정정치가 경과한후 해당회로의 지락 사고표시등이 점
등됩니다.
② 해당회로의 REPLAY가 동작합니다.
③ 지락전류량 표시디지털에 지락전류량이 숫자로 표시됩니다.
※ 주의 : 자동/수동 스위치를 자동으로 설정하였을 경우 적색
LED가 점등되고 지락전류가 소멸될 경우 자동적으로
발생한 모든 동작표시가 없어집니다.
동작특성
1. Multi-ground fault relay monitors a number of circuits
collectively and carries built-in functional arrangement for
ground leakage level indication and fault current level
indication.
2. It performs monitoring of all circuits consequently by the
command of MCU.
3. In case a ground fault current developed, it induces a
voltage in ZCT which is fed to ground fault current
detection circuit as an input.
4. After Input signal(voltage) is amplified, and then it is
supplied to CPU for processing.
5. CPU converts input by A/D converter for comparison to
set value of sensing current. And, if it is found more
exceeding the setting value, it is performed as followings.
1) Turns on ground fault indicator lamp upon the elapse
of setting interval of operating time.
2) Activates GFR or the circuit.
3) Indicates level of ground fault current on ground fault
current indicator in numeral value.
※Note : If Auto/Manual switch is set to Auto position the
warning lamp(Red LED) turns on, and the fault is
repaired, all operating indication of the circuit
will disappear automatically.
128
DEESYS TOTAL PRODUCTS GUIDE
6. Identification of indications : When leakages occur in
plural number of circuits on sometime, ground fault
indicator lamps for applicable circuits will light up at
once. But ground fault circuit number indicator and
ground fault current level indicator will display the value
of first circuit detected. The values of other fault circuits
can be checked by pressing circuit test button of
respective circuit. If it is the auto reset mode, fault
current has been cleared. Such fault current can be
read out from the memory by pressing hold check
button.
7. Reset If Auto/Manual switch is set to manual position
after the ground fault is repaired, press reset button to
initialize the performance or else fault indication will be
kept on.
Multi Function Ground Fault Relay [GFR]-5C, 10C
설치전 점검사항
(계전기를 설치하기전 다음 사항을 점검하여 계전기의 기능을 확인
하시기 바랍니다.)
5. 지락감도설정 확인스위치를 눌러 각 회로의 감도전류설정을 확인
하십시요.
1. 계전기의 P0, P1 단자에 전원전압(AC 110V 또는 220V)를 연결하
십시오.
(주의: 계전기의 전원전압은 공장출하 설정치가 AC 220V입니다.
AC 110V를 사용하실 경우 뒷면의 슬라이드 스위치를 AC110V로
전환 조정하여 사용하십시요.)
6. 회로별 자체시험스위치를 눌러 계전기의 내부회로를 점검합니다.
스위치를 누르면 해당 회로의 RELAY와 지락사고등(RED LED)
이 동작되며 지락전류표시 디지털에 20.5 를 표시하여 각 회로
의 이상유무를 확인합니다. (디지털 표시는 가상의 지락상태를 표
시하며, ZCT의 연결이 안된 상태에서의 숫자임)
2. 전원을 연결하면 전원등(GREEN LED)이 점등되어 전원 투입상
태임을 알립니다.
7. 자동/수동 스위치를 수동으로 설정하고 6. 항의 시험을 다시 행하
십시요.
3. 회로검사 스위치를 눌러 디지털표시를 점검합니다.
스위치를 누를때마다 회로표시가 1회로씩 순차적으로 변환되고
지락전류량은 888 을 표시합니다.
스위치를 누르지 않고 약 25초가 경과하면 자동으로 표시가 소멸
됩니다.
8. 이상의 시험이 끝나면 복귀스위치를 눌러 계전기를 초기상태로
환원시킵니다.
4. 동작시간설정 확인스위치를 눌러 각회로의 동작시간설정을 확인
하십시오.
Checking Items Before Installation
Check up following points befor installation in order to
ensure satisfactory performance of GFR.
1. Connect AC 220V power lines to terminals Po and P1 of
GFR.
※Note : Operating power is set to AC 220V at factory
when delivered. If AC 110V is used, slide the
power voltage selector switch to AC 110V
position.
2. When the power os connected, power lamp(Green LED)
turns on to indicate power suppy.
6. Check up internal circuits by pressing self- test button of
each circuit.
If the button is pressed of a circuit, relay of the circuit
and ground fault indicator lamp(RED LED) and circuit
indicator relay activate to show status of circuits.(The
value of digital display represent assumed state of
grounding fault).
7. Carry out the test of item 6 after auto/manual switch is
set mannual position.
8. Return to the initial status by pressing the reset switch
after finishing the above test.
3. Check up digital displays by pressing circuit test switch.
The circuit number on display changes by advancing
one circuit at each of pressing the button and ground
fault current level indicator will remain displaying
888 all the while of testing. After an elapse of about
25 seconds or so without pressing test button further, the
indication will disappear automatically.
4. Check up operating time settings of each circuit by
pressing operating time check switch.
5. Check up fault sensing current setting by pressing
ground fault sensing setting switch.
DEESYS TOTAL PRODUCTS GUIDE
129
Multi Function Ground Fault Relay [GFR]-5C, 10C
설치시 점검사항
1. 설치하고자 하는 장소에 계전기의 치수에 맞게 판넬을 제작 취부
(매입) 설치합니다. 이어서 경계선로에 ZCT를 설치합니다.
2. 계전기 뒷면 단자 결선(외부결선도 참조)
① 부하용량에 맞게 ZCT 를 설치합니다.
(ZCT 사양 및 용량 결정시 당사에서 생산하는 ELD용 ZCT를
사용하십시요.)
① 변류기측 2개의 단자 중(단자의 극성 구별은 없음) 1개는 계전
기 각회로 단자 ①,②,③,④,⑤,⑥,⑦,⑧,⑨,⑩에 결선하고 1개의
단자는 계전기 ⓩ공통단자에 연결합니다.
② 대전류모선 혹은 강한 자장으로부터 10Cm 이상의 위치에 설
치하여 주십시요.
② 계전기의 ⓐ~ⓘ 단자는 외부 릴레이 접점(a접점), COM 단자
는 외부 릴레이 공통 접점(c접점)으로 차단기구제어, 외부 경
보용 부져 및 중앙감시반 누전사고표시장치에 이용됩니다.
③ 단상/3상 구별없이 부하선로에 설치합니다.
④ 회로별 자체시험스위치를 눌러 계전기와 ZCT와의 단선유무를
검사합니다.
③ Ta, Tc 단자는 외보용 INDICATOR(부져, LAMP) 사용 접점
입니다.
④ 단자(E)는 접지단자로 배전반 그라운드로 연결합니다.
정격전압 5% 이내에서 ZCT가 계전기에 정상적으로 연결되어 있
을 시에는 지락전류량 표시디지털에 18미만의 숫자를 DIGTAL로
표시하고 단선시에는 18이상 숫자를 표시하였을 경우 수신기는
정상입니다.
⑤ 계전기의 전원은 다른 회로전원과 병렬로 연결하지 마시고 분
기이전의 별도 전원을 사용하십시요.
Checking Items for Installation
1. Fabricate relay mounting panel of a suitable size and fix
it on which GFR be installed. Then install ZCT on the
circuits being monitored.
① Install ZCT of adequatable for the load (For selection
of ZCT specification and current rating. use ZCT
manufactured by us for ELD.)
② Ensuring GFR is in stalled at 10cm or more distance
where there are large current bus and strong magnet
field.
③ Install GFR on load circuit of single phase and three
phase power without exception.
④ check confinuity between GFR and ZCT by pressing
self-test button of each circuit line. The receiver is in
nomal status if ground fault current level indicator
shows a value in numerals Below of 18 if the
connection of GFR and ZCT is correctly made, and a
value of 18 if they are disconnected.
2. Connections to terminals on the back of GFR.(Refer to
external wiring diagram)
① One of two ZCT terminals(no ploarities) Shal be
connected to relay terminal of each circuit ①, ②, ③, ④,
⑤, ⑥, ⑦, ⑧, ⑨, and ⑩ and the other terminal to
common terminal ⓩ of GFR.
130
DEESYS TOTAL PRODUCTS GUIDE
② With GFR, terminals ⓐ through ⓙ are‘a’contacts for
external relays, and terminal COM is ‘contact’ for
external relays. The terminals could be used for
control of circuit breakers, external alarm buzzer, and
leakage fault in dication on central control board.
③ Terminals Ta and Tc are provided to use the
contacts for external indicators(buzzer, lamp).
④ Terminal (E) is for grounding which is connedted to
the ground terminal of distribution board. (Refer to
external wiring diagram for connections).
⑤ The control power of relay should be connected an
independent sonrce which is not distributed from
main source.
Multi Function Ground Fault Relay [GFR]-5C, 10C
Internal block diagram
External contacts wiring diagram(Alarm & CB Trip contacts)
External terminal arrangement
Contact output type(Alarm & CB Contacts)
Signal output type(CB Trip Contacts)
※ GFR-M10, 10T의 경우 단자 Z가 내부에서 연결이되어 있으므로 한단자만 사용해도 됩니다.
DEESYS TOTAL PRODUCTS GUIDE
131
Aux Relay Board [Isolation]-5C, 10C
Aux relay board is a power relay which controls output power according to
the input signals of industrial uses, and consists of set type relays controlling
MCCB or MC coils.
Features
�Ensure to use Aux Relays (DRB-010. 005) when DGF-M10, M05 are used to
drive MCCB and trip rather than the using them as central control board lamp
indication.
�It is insulated completely between and among input, output, and power lines.
�Single board is capable to control 5or 10 circuits
�Formerly exposed aux relays are now internally located in order to prevent
mal-functioning caused by moisture hazardous to insulation.
GFR output
Rated Specification
MODEL
DRB-010(10C), DRB-005(5C)
Rated Voltage
AC 110/220V
Rated Frequency
50/60㎐
Relay Contact Rating
AC 250V, 10A
Inetrnal block diagram
External wiring diagram
Terminal arrangement
External dimension
132
DEESYS TOTAL PRODUCTS GUIDE
Ground Fault Relay-1C
Flush mounted type
Soket type
Specification
Model No
Part
DGF-P11(Socket type)
DGF-P12(Socket type)
DGF-F11(Flush mounted)
DGF-F12(Flush mounted)
Auxiliary power
AC 110/220V common(DC110/220V Option)
Frequency
50/60㎐ common
Operating current setting
Operating time setting
0.1-0.1-0.5-1-3-5-7-10-Lock
10-15-20-25-30-35-40-50-Lock
INST-0.1-0.3-0.5-0.7-1-2-3-Lock
INST-0.1-0.3-0.5-0.7-1-2-3-Lock
Operation Indicator
LED lamp (red color)
Reset
Auto / Manual
Extent of supply voltage
85~115% of rated voltage
Ambient temperature
-10℃~+50℃
Power consumption
3VA
Insulation resistane
DC 500V, less than 100㏁
Dielectric strength
primary-case ; AC 2,000V, Secondary-case : AC500V / 1minute
Contact capacity
AC 125V 5A / DC 30V 5A
Weight
0.6㎏
Case
ABS Resin/Black N1.5
ZCT(Input)
ZCT Rating 200㎃/100mV(ZR, ZS, ZB type 사용)
특징
Features
이 정지형 접지검출계전기(GFR)는 ZCT(영상변류기)와 조합하여 접지
전류를 검출하며, 그 고장회로의 차단기를 차단하거나 경보를 울리게
할 수 있도록 출력접점을 내장하고 있습니다. 이 사양서에 표시된 동
작전류란 ZCT의 1차에 흐르는 전류를 의미합니다. 즉 이 ZCT 1차에
흐르는 전류를 기준으로 정정해야 하는데 이와 같이 정정된 전류가
ZCT 1차에 흐르고, 설정된 시간이 지나면 계전기의 출력(트립용 또는
경보용) 접점이 붙게 됩니다.
센서 ZCT의 2차는 GFR과 직접 연결되므로 발주시 한 조로 주문하는
것이 바람직 합니다. 모델“F-xx는 배전반 표면 부착용(플래쉬 마운팅
타입)이며, P-xx는 판넬 내장형으로 수분리형입니다. 자세한 내용은
이 매뉴얼의 관련 부분을 참조하시기 바랍니다.
The static GFR with a sensor(Toroidal CT) is for ground
fault current detection and has an output contact for a fault
circuit trip. The relay is combined with a sensor which is
calibrated as a set. The operating current in the
specification means 1ry current of the CT. While the 1ry
current is reached at set value. the output of the relay is
closed.
Since the 2ry output of the sensor is connected to the input
of the relay. it is recommended that the relay with a sensing
CT has to be ordered as a set. Model.“-F□□”is for semiflush mounting type and“-P□□”is for pin type with a base
socket. Refer to the drawings in the instruction for more
information.
DEESYS TOTAL PRODUCTS GUIDE
133
Ground Fault Relay-1C
적용
Application
이 접지계전기(GFR)는 비접지 회로망에서 회로에 흐르는 영상전류(Io)
및 접지시 모선측에 발생하는 대지간 불평형 캐패시터 성분에 의한 전
류(Ic)가 ZCT를 통하여 흐르는 량을 감지하여 검출하는 방식입니다.
평상시 평형을 이루고 있던 3상간의 대지간 평형 정전용량이 일선 지
락으로 인하여 깨지면서 대지간 캐패시터 성분에 의한 불평형 전류가
발생 되는데 이 전류가 ZCT를 통하여 흐르게 됩니다. 접지전류(Io +
Ic)정정 및 동작시간 정정은 명판위에 있는 로타리 스위치로 설정 할
수 있습니다. 이 로타리 스위치의 <LOCK> 위치에 맞추어 놓으면 이
기능은 작동하지 않습니다. 기능중 Manual(수동) 및 Auto.(자동) 선택
스위치가 있으며, Manual로 선택하면 접지 현상이 제거되어도 계전기
의 접점은 운전원이 RESET 스위치를 누를 때까지 지속적으로 붙어
있으며, AUTO로 선택하면 계전기에 접지가 제거되면 자동으로 출력
접점이 복귀됩니다.
The GFR may be applied where fault circuits should be cut
off detecting current, lo and unbalanced current. Ic in the
non-grounding network. Capacitive components existing in
the bus side from ZCT is balanced between earth and three
phase conductors at the normal condition. The balanced
capacitive components of three phases are broken as soon
as for one of three phases being grounded. And then the
capacitive current becomes to flow thru the ZCT. The fault
current(lo + lc) can be set by rotary switches on the front
plate of the relay. Time delay function is selected by the time
switch as well. By turning to <LOCK> of the rotary switches for
operating current and/or operating time, the function(s) can
be disabled. Reset function for output contact can be
selected either on Manual or on Auto.
정정, 시험 및 운전
Setting, Testing, and Operation
1. 전류정정 탭
0.1-0. 3-0. 5-1-3-5-7-10(A)-LOCK(총 9단계)
1. Current Set : There is a 9 step switch on the front plate for
current set. One of 8 step(0.1, 0.3, 0.5, 1, 3. 5.
7. 10(A)) and lock, can be selected.
2. 동작시간 탭
Inst.(순시)-0. 1-0. 3-0. 5-0. 7-1-2-3-LOCK(총 9단계)
3. Power LED
보조전원이 공급되어 있으면 Power LED(초록)이 켜져 있습니다.
2. Time Set : There is a 9 step switch on the front plate for
time set. a Instant set. 7 steps of delay time and
a Lock set.
3. Power LED(Green) is lighted while aux. power is ON.
4. Trip LED
출력 접점이 출력 되면 Trip LED(적)이 켜집니다.
5. Manual/Auto
이 선택 스위치로 출력 접점을 유지하거나 자동 복귀할 수 있게 합
니다. Manual로 선택한 경우. 접지로 인하여 출력 접점이 붙었을
경우 RESET 스위치를 누르지 않는한 지속적으로 붙어있게 됩니다.
Auto로 선택한 경우 접지 상태가 제거되면 즉시 출력 접점도 자동
복귀됩니다.
6. RESET 스위치는 동작 표시 LED 및 출력 접점을 복귀하는데 사용
합니다.(Manual 선택시)
7. TEST 버튼은 출력 접점 이상 유무를 확인하고자 할 때나 수동 시
험용으로 사용됩니다.
주의: 정상 운전시 이 TEST 버튼을 누르면 접점 S.W가 Manual에
있을 때에는 접점이 계속 유지되므로 반드시 Reset S.W 눌
러 주십시오.
134
DEESYS TOTAL PRODUCTS GUIDE
4. Trip LED(Red) is Lighted when any fault occurs and the
output contact(terminal Ta and Tc) is closed at a same
time.
5. Manual/Auto switch can be selected either Manual or Auto
for reset. “Maunal” means for manual reset of output
contact by pressing reset button and “Auto” means for
automatic reset of output contact as soon as the fault
current cleared.
6. Reset button is used for resetting TRIP LED and an output
contact when Manual/ Auto switch has been turned to
Manual.
7. Test button is used for self-circuit test. If the button is
pressed manually, the output contact(a) is closed and TRIP
LED is lighted simultaneously.
Note : Do not press the <Test> button during in service. Main
CB may be opened
Ground Fault Relay-1C
개체시험 방법(시험회로도 참조)
Test Procedure (Refer to the figure)
1. 아래의 그림 회로에서와 같이 ZCT의 2차(k-l)를 GFR 단자(7 -8)에
연결한다.
1. 2ry of sensor(k & l) and GFR(Terminal 7 & 8) are
connected with wire.
2. 단자 1-3 에 보조 전원 AC110/220V를 연결한다.
2. Terminal 1 & 3 for AC 220V or terminal 1 & 2 for AC 110
aux. power is connected to a source.
3. 단상 전원의 1선만을 ZCT를 통과하게 하고 전원에 연결한다.
4. 계전기에서 전류 탭은 10A에 동작 시간 탭은 0.1초에 설정한다.
5. 보조전원을 켜고, POWER LED가 켜졌는지를 확인한다.
3. One line with an A-meter from current source is
installed through the sensor CT.
4. GFR is set at 10A tap with current dial and 0.1 sec. tap
with time dial on the front plate.
6. 전류 발생 장치를 이용하여 ZCT 1차에 12A를 맞춘다.
7. 전류 발생 장치에서 전류 스위치를 순간적으로 ON한다. 이 때 전류
가 12A가 흘렀는지 확인하고 타임 카운터가 0.1초 10%범위내에서
정지되었는지. 그리고 TRIP LED가 들어왔는지 확인한다.
8. RESET 스위치를 누르면 트립표시용 LED가 복귀한다. 만약 AUTO
로 선택했을 경우는 출력접점은 전류 OFF와 동시에 자동 복귀되고
트립표시 LED도 자동 복귀됩니다.
9. 다른 정정치에서도 위와 동일한 방법으로 시험 할 수 있다.
5. Aux. power switch is "ON". Then the power LED on the
front plate may be lighted.
6. Current through the sensor CT is set 12A (120% of set
value) using current source.
7. Switch current source instantaneously and watch
through-current on A-meter whether 120% of set value
is flowed. Then, confirm time on the time counter if it is
counted 0.1±10%sec. (±10% of time set value) and if the
trip LED is lighted.
8. Press RESET button for reset. If Reset selection is
turned to Auto., the output contact will reset
automatically, but the trip LED shall be reset manually
like doing at Manual.
9. Other ranges can be tested same as the above
procedure.
Internal block diagram
External wiring diagram
DEESYS TOTAL PRODUCTS GUIDE
135
Ground Fault Relay-1C
Dimension
MODEL : DGF-P11, DGF-P12, DER-P03, P11, P12
�Flush mounted type
1,2 : AC110V/120V
1,3 : AC220V/240V
4,5,6 : a,b,c - Contact
MODEL : DGF-F11, F12, DER-F11, F12
Cutting Size : 56x94mm
7,8 : Z,C,T Input
External dimension(GFR-M10/M05, ELR M10/M05, ELR-A10/A05)
Cutting Size: 165 X 122mm
136
DEESYS TOTAL PRODUCTS GUIDE
국가형식검정품(한국소방검정공사)
Low Voltage
Zero-Phase Sequence
Current Transformer
■Zero Phase Sequence Current Transformer [ZR, ZS, ZB, SZR-Series]
■Zero Phase Sequence Current Transformer [ZB-Series]
■Cable & Busbar Through Type [ZR, ZS, ZB, SZR-Series]
■Busbar Mold Type Zero Phase Sequence Current Transformer [3∅ 3W]
■Busbar Mold Type Zero Phase Sequence Current Transformer [3∅ 4W]
■How to Installation and Inspection
ZCT
영상변류기(ZR, ZB, ZS)
Zero-Phase Sequence Current Transforme [ZR, ZS, ZB, SZR-Series]
● 고투자율 Core를 사용 직선성 및 안정도를 높였습니다.
● 고감도용(SZR TYPE)은 Nickel Core를 사용하여 30mA의 작은
전류도 정확히 검출합니다.
● 다양한 Model을 구비하여 선택의 폭을 넓혔습니다.
● 대량 생산을 통해 보다 저렴한 가격으로 공급하고 있습니다.
● As it is used high magnetivity core, it has high linear
characteristics and safety characteristics.
● As SZR type ZCT (Sensitivity type) is used Nickel core, it is
possible to detect small current(30mA) correctly
● As various model, it is very easy to select the ZCT
Ordering Procedure
ZR
-
O3O
025-25∅
ZR-for ELD, GFR
030-30∅
ZR
050-50∅
HZR-for High Voltage Ralay
HZR
065-65∅
SZR
080-80∅
100-100∅
SZR-for High sensitivity &
Static type Directional Ground Relay
120-120∅
150-150∅
200-200∅
150-150㎜
ZS-square type
ZS
SZS
200-200㎜
250-250㎜
ZB3-Busbar mold type(3 wire)
400-400A
600-600A
ZB4-Busbar mold type(4 wire)
800-800A
※ 주 의 : 상기 Series ZCT는 2차 출력이 전압형으로 ELD 및 Static Type
Realy에 적용할 수 있는 특성을 갖고 있으며 유도형 계전기에는
적용이 불가합니다.
※ Note : Because the above ZCT is voltage type on 2ry
output and has characteristics applicable with ELD
and static type relay, it is impossible to apply for
induction type relay.
138
DEESYS TOTAL PRODUCTS GUIDE
ZB3
1000-1000A
1200-1200A
1400-1400A
1600-1600A
ZB4
Zero-Phase Sequence Current Transforme [ZR, ZS, ZB, SZR-Series]
● For earth leakage detector
● For indoor
● Cable & Busbar through type
● Casing ASB (Non-flamable)
● Color : ZR, ZS SZR, HZR, SZS type-Black(N1.5)
소방검정공사 형식승인품(ZR Type)
(Type approval by inspection agency for fire)
Specifications
Model
Cable
Through
Type
Busbar
through
type
ZR-025
SZR-025
ZR-030
SZR-030
ZR-050
SZR-050
ZR-065
SZR-065
ZR-080
SZR-080
ZR-100
SZR-100
ZR-120
SZR-120
ZR-150
SZR-150
ZR-200
SZR-200
ZS-150
ZS-200
ZS-250
Rated
Current(A)
Inside dia.
(㎜)
80
Through wire(EV)㎟
Zero phase
current ratio
Pri./Sec
Dimensioon
(page)
Weight
(㎏)
109
0.4
109
0.5
38
109
0.7
150
100
109
0.9
400
250
200
109
1.5
100
500
325
250
109
2.2
1000
120
-
850
725
109
3.4
1400
150
-
1000
850
109
4.0
2000
200
-
109
7.5
400
400
600
30×150
30×200
30×250
109
109
109
2.8
3.5
3.8
1∅2W
1∅3W,3∅W
3∅4W
25
38
8
5.5
100
30
60
14
8
250
50
150
80
400
65
325
600
80
800
※6T×25
-
ZR,SZR type
200㎃/100㎷
(75~125㎷ at 2㏀)
SZR Type
30㎃/50㎷
※6T×25
※6T×25
※ Note : 1.“※”Mark is busbar size
2. SZR Type ZCT는 고감도(30mA)용으로서 NIckel Core를 사용하였습니다.
3. ZR, Type ZCT는 Test terminal이 없습니다. 필요한 경우 별도 주문하셔야 합니다.
∙Use to Temperature : -10℃~+60℃
∙Withstand voltage : AC 2000V/Min.(between secondary coil and base)
∙Insulation resistance : More Then 1000㏁ DC 500V(bettween coil and base)
SZR ZCT
Digital DGR
200mA/100mV
ELR-Po3. DER-Po3적용
30mA/50mV
영상변류기(Z.C.T)동작원리
(1)정상상태(Normal Condition)
(2) 지락누전상태(Ground Fault Condition)
DEESYS TOTAL PRODUCTS GUIDE
139
Zero-Phase Sequence Current Transformer [ZB-Series]
■
■
■
■
■
For Earth Leakage Detector
For Indoor
Busbar Mold Type
Bake-lite case
Color : Munsell No N1.5(Black)
Specifications
Model
ZB3-400
ZB4-400
ZB3-600
ZB4-600
ZB3-800
ZB4-800
ZB3-1000
ZB4-1000
ZB3-1200
ZB4-1200
ZB3-1400
Rated Current(A)
Busbar Size(㎜)
400
6T×50
600
6T×50
800
6T×75
1000
8T×75
1200
Zero phase current ratio Pri./Sec
Dimension(page)
Weight(㎏)
110
4.3
111
7.4
110
4.3
111
7.4
110
6.6
111
8.8
200㎃/100㎷
110
8.0
(75~125㎷ at 2㏀)
111
11.0
8T×100
110
12.4
1400
10T×100
110
15.0
1600
10T×100
110
15.0
ZB4-1400
ZB3-1600
ZB4-1600
※ ZB3 : 3�, 320 / ZB4 : 3�, 420
∙Use to Temperature = -10℃~ + 60℃
∙Withstand Voltage : AC 2000V/MIN
Between primary conductor and secondary coil
Between Pri. Sec. coil and base
∙Insulation Resistance : More than 1000M at 500V DC
Between primary conductor and secondary coil
Between Pri. Sec. coil and base
∙Busbar 표면은 도금이 되어 있지 않습니다. 석도금이나 은도금이 되야 할 경우는 주문시 지정해주시기 바랍니다.
∙ZB Series ZCT는 Test terminal이 없습니다. 필요할 경우 별도 주문하셔야 합니다.
140
DEESYS TOTAL PRODUCTS GUIDE
Cable & Busbar Through Type [ZR, SZR, ZS-Series]
Round type
UNIT(m/m)
Model-No
A
B
C
D
E
F
G
H
ZR/SZR-025
25
25
87
95
110
9
30
20
ZR/SZR/HZR-030
30
25
108
100
114
7
32
32
ZR/SZR/HZR-050
50
25
131
100
122
7
32
36
ZR/SZR/HZR-065
65
26
143
114
133
7
39
37
ZR/SZR/HZR-080
80
34
174
160
180
7
40
40
ZR/SZR/HZR-100
100
38
203
160
180
7
40
40
UNIT(m/m)
Model-No
A
B
C
D
E
F
G
H
Hole(�)
ZR/HZR
120
45
225
180
210
20
55
35
10
ZR/HZR
150
45
260
180
210
20
55
35
10
ZR/HZR
200
53
310
260
286
10
70
35
10
Square type
UNIT(m/m)
Model-No
A
B
C
D
E
F
G
H
I
ZS-150
50
150
50
250
50
30
50
130
51
ZS-200
50
200
50
300
50
30
50
130
51
ZS-250
50
255
50
350
50
30
50
130
51
DEESYS TOTAL PRODUCTS GUIDE
141
Busbar Mold Type Zero-Phase Sequence Current Transformer [3 3W]
● 400-600A(80�)
Model-No
A
B
C
D
E
F
G
H
I
J
Hole(�)
ZB3-400
50
6
300
100
100
200
160
40
188
195
6
ZB3-600
60
6
300
100
100
200
160
40
188
195
6
Model-No
A
B
C
D
E
F
G
H
I
J
Hole(�)
ZB3-800
75
6
320
100
100
200
160
40
215
230
6
ZB3-1000
75
8
320
100
100
200
160
40
215
230
6
Model-No
A
B
C
D
E
F
G
H
I
J
Hole(�)
ZB3-1200
100
8
330
140
140
280
180
35
210
260
10
Model-No
A
B
C
D
E
F
G
H
I
J
Hole(�)
ZB3-1400
100
10
350
140
140
280
180
35
210
260
10
ZB3-1600
100
10
350
140
140
280
180
35
210
260
10
800-1000A(100�)
1200A(150�)
1400-1600A(150�)
142
DEESYS TOTAL PRODUCTS GUIDE
Busbar Mold Type Zero-Phase Sequence Current Transformer [3 4W]
400-600A(120�)
Model-No
A
B
C
D
E
F
G
H
I
J
K
Hole(�)
ZB4-400
50
180
6
35
300
100
100
100
300
210
225
10
ZB4-600
50
180
6
35
300
100
100
100
300
210
225
10
Model-No
A
B
C
D
E
F
G
H
I
J
K
Hole(�)
ZB4-800
75
180
6
35
320
100
100
100
300
210
260
10
ZB4-1000
75
180
8
35
320
100
100
100
300
210
260
10
800-1000A(150�)
Note : In case of leakage indication appears in plural at a time. check if wiring connetion is wrongly done as drawn example.
In case that circuit NO 2 is leakaged, it is normal to indicate NO 2 circuit signal only. But because common wire is not
connected to No1~No5 circuit, so No1~No5 circuits are indicated leakage singal simunltaneously.
(How to check)check the resistance between common wire and No 1 circuit~No 10 circuit. It is 30~70Ω on normal condition
and is infinity in disconnection condition.
DEESYS TOTAL PRODUCTS GUIDE
143
How to Installation and Inspection
Note : Incorrect installation of ZCT may result in malfunctioning of relay. Please refer to follwing wiring diagrams
WRONG CONNECTION
RIGHT CONNECTION
1) Load on neutral line will cause malfunctioning
1) All of two lines of 1∅ 2W. three lines of 1∅ 3W. three lines of 3∅
3W. and four lines of 3∅ 4W should go through ZCT.
2) Because of load current on neutral line, the current between AB cause erro operation. The relay may not activate relay
operation in cases of leakage.
2) Cut off line B and provide class 2 grounding as required for
ZCT.
3) As load current is divided between A and B grounding, it will
cause missing operation in case of leakage.
3) Earth the wires before ZCT to (the side of power source).
4) When neutral line and distribution board line are jointly
connected to ZCT. malfunction will be introduced as the example
of 3) above.
4) Provide class 3 grounding seperately for neutral line and
distribution board each
5) Leakage indication lacks accuracy.
5) Install ZCT correctly
6) Occurrence of leakage will not activate relay operation.
6) Grounding of frame should be installed after(in the down stream)
the ZCT connection point.
Even if grounding is intentionally made to frame to frame, the leakage
flows directly into to casing grounding without going through ZCT.
Note : The frames are transformer casing, cubicle enclosure, and
structural steel frames.
144
DEESYS TOTAL PRODUCTS GUIDE
Motor Protective
Relay
■Motor Protective Relay
■3E, 4E Motor Protective Relay
MPR(4E,3E)
모터보호계전기(4E, 3E)
Motor Protective Relay
정지형 Motor-Relay의 개요
Static type Motor-Relay
● MOTOR RELAY라 함은 많은 종류가 있으나 산업설비의 전력용으
로서 가장 많이 사용되고 있는 것은 3상유도전동기이며 이것을 보
호하는 것을 모터 RELAY라 합니다. 모터의 보호는 중요하며 이상
을 빨리 감지하여 부하의 피해를 최소한으로 막고 모터의 수명 및
파손을 방지하여야 합니다.
● 모터의 소형화, 경량화 됨에 따라 보호하는 모터 RELAY에도 고성
능, 고신뢰도가 요구되어 종래의 단순한 썸머 RELAY형에서 정지
형으로 변형되어 가고 있습니다.
�MOTOR relays ranging wide in types refer to those relays
purposed to protect three phase induction motors that are
prime source of motive power at most industrial facilities.
Motor protection by means of earlier detection of fault
status to minimize overload damage is important for long
motor life and avoiding damages.
�Ensuring with the trends of motors becoming compact and
light-weighted, motor protection relays (MPR) being required
of high performance and reliability are featuring static state
a change from the conventional simple thermal relay
structure.
Motor relay의 기능(Function)
Element
Feature No.
Remarks
1. Overload
51
∙Prevent motor burning.
2. Open phase
46
∙Minnmize damages to work loads.
3. Reverse phase
4. Ground fault
47
50G
(Careful selection is necessary for correct application.)
∙Offer protection against leakage damages caused by motor insulation faults.
과부하요소(Over load)
● 모터가 과부하가 되어 과전류가 장시간 흐르면 모터가 타버립니다.
그러므로 모터의 손상을 막기 위해서는 즉시 차단하여 모터를 보호
해야 합니다.
● 유도 전동기는 일반적으로 가동시 500~600% 정도의 과전류가
수초에서 수십초간 전류가 흐릅니다.
● 이때 모터 RELAY 동작하면 모터의 오동작 상태가 되므로 가동시
간의 설정을 정확히 할 필요가 있으므로 동작시간 요소는 반드시
필요합니다.
● 전류값에 대해서는 JEM1357에서 규정하는 전류정정치의
105~125%의 범위내로 정하고 있으며 특별히 지정이 없는 모터에
는 이 규격으로 적용합니다.
● 동작시간에 대해서는 동일시각인 JEM1357에서 정하는 전류정정치
의 600% 과전류에서 40초 이하 200%의 과전류에서 4분이하로
정하고 있습니다.
결상검출요서(Open phase)
● 모터의 전원선이 단선되면 TERMINAL 접속부등의 풀림, 개폐기등
의 접촉불량 모터자체 COIL의 단선등에 따라 3상 운전되는 모터가
단상으로 운전되는 상태를 말합니다.
● 모터가 정지되고 있는 상태에서는 단상 운전이 이루어지지 않으며
결상상태에서 기동하면 기동전류가 지속적으로 흐르기 때문에 과부
하(OVER LOAD)로 인한 검출을 하여 모터의 소손을 방지 할 수
있습니다.
● 모터가 정상회전되고 있는 상태에서 결상이 되어 단상 상태가 되고
부하가 작으면(경부하) 모터는 계속 운전될 수 있습니다.
146
DEESYS TOTAL PRODUCTS GUIDE
Elements for overload
�Over loaded operation of motor will flow of over current.
Long time operation of a motor in over current status would
result in motor burning and that current should be cut-off
immediately for protection against the burning.
�Induction motors normally require 5 to 6 times starting
currents than rating current during a few seconds while
starting.
�Should the relay react to such starting over current, the
motor will be in operation fault status. In order to avoid
such a state. precise setting of operating time will be
necessary.
�Current rating is set within the range of 105% to 125% of the
current setting prescribed in JEM 1357 for all motors unless
otherwise specified.
�Relays are timed to operated in 40 seconds or less at
600% over current of the set level as specified in JEM 1357
and 4 minute less at 200% over current likewise.
Element for open phase
�Open phase operation refers to a state of motor operation
in which a three phase motor would run in single phase
power because of loosened terminal connection faulty
switch contact or disconnected motor coil
�Three phase motor does not start in single phase power
from halt status that continous attempt to start in an open
phased state will occur over current. Detection of overload
status is essential to save the motor from burning.
�Should the motor is developed an open phase while the
motor is in rotation the motor may rotate continuous if the
load is resonably low.
Motor Protective Relay
Phase current Vector During one phase open
Current detecting (CD) or Voltage
detecting mathode(VD)
(Fig1)
∙nomal
∙one phase open
(External)
(Fig3)
∙△ phase open
(Internal)
그림2와 같이 변류기를 사용하지 아니하고 전압방식으로 결상을 검출
하는 방식도 있으나 결상검출의 접속점부터 MOTOR까지는 검출이 안
되며 전원측 결상이라 하여도 MOTOR의 부하가 경부하 상태의 운전
중이면 MOTOR에는 단자전압이 걸려 있기 때문에 결상이 검출이 되
지 않는 경우가 있기 때문에 전류검출방식의 결상을 검출하는 것이 가
장 바람직합니다.
● 과전류 요소 만으로는 결상시 모터의 소손을 방지하지 못하는 경우
가 있어 결상요소가 필요합니다.
● 경부하 시에는 결상이 되어도 과전류라고 할수 있는 전류가 흐르지
못하므로 결상검출이 되지 않습니다. 이상을 신속히 검출하기 위하
여는 결상요소가 필요합니다.
● 결상검출 방식은 전압 방식도 있으나 전류방식이 가장 유리합니다.
반(역)상 검출요소(Reverse phase)
● 3상유도전동기는 상순이 바뀌게 되면 모터의 회전방향이 반대로 됩
니다. 모터가 잠깐이라도 반대를 돌게되면 모터의 부하에 치명적인
영향을 끼칠수 있습니다.
● 그러므로 모터의 상순이 역으로 되면 즉시 검출하여 차단시키는 반
상요소가 필요합니다.
● 이 경우에는 모터의 3상 전압을 검출하여 모터의 역회전을 방지합
니다.
● 그림3의 경우 마그네트 전에 반상을 접속했을 경우 반상 상태가 되
면 모터를 기동시키기 전에 검출하게 됩니다.
● 그러기 때문에 이 경우는 절대로 모터의 기동전에 검출하므로 안전
하게 됩니다.
● 특히 전원이 이동될 경우의 모터는 접속변경이 많으므로 이 경우에
는 필히 부착하는 것이 바람직합니다.
Phase reverse detecting mathode(Fig2)
As shown in Fig. 2, open phase is detectable by voltage
method without requiring use of a current transformer. The
method does not, however, offer ability to detect open phase
status between detector contact point to motor. In case of line
side open phase, terminal voltage exists if the motor is
running with light load that open phase may not be
detectable. For this above reason, the current detections
method is desirable.
�Since over current measure alone may not always be able
to prevent motor burning, consideration of open phase
measure will be necessary.
�In case of running with light load, the current in phase fault
may not be large enough to be detected as over current
that status of open phase may not be detected. For this
reason, application of open phase measures for prompt
detection of phase fault will be necessary.
�For this reason, use of current detection method will be
most advantageous although voltage detection method is
available too.
Element for open phase
�Changes in phase sequence of three phase motor would
reverse the direction of rotation. Revers rotation even for a
short time would be detrimental to the lead critically.
�Reverse phase performance for immediate detection and
instantaneous circuit breaking is essential whenever the
phase is reversed.
�Reverse roation is preventable by three phase voltage
detection.
�As shown is Flg 3. reversed phase can be detected before
starting the motor if the detector is connected before the
magnetic switch.
�The connection as such assures complete safety as it
detects reversal factor absolutely before starting.
�When power cource is changed. Installation of the detector
is highly desirable because wiring of motor may be
misconnected very often.
DEESYS TOTAL PRODUCTS GUIDE
147
Motor Protective Relay
Motor Relay의 특징
● 모터는 역율을 개선시키기 위해 모터에 병렬로 진상용 콘덴서를 설
치하게 됩니다. 모터의 경부하시에 흐르는 전류는 대게 무효분이며
고조파가 함유됩니다. 그래서 진상용 콘덴서를 접속하여 불필요한
고조파를 없애줍니다. 이것이 큰경우에는 50/60Hz의 정현파로 설
계되어 있는 결상 및 반상 회로등이 오동작 할 우려가 있습니다. 대
부분의 경우에는 오동작의 경우는 거의 없으나 진상용 콘덴서를
MOTOR 전단에 설치하여 정확한 과전류동작치를 감지하여 선로의
이상 발생을 보호할 필요가 있습니다.
● MOTOR 전류의 불평율의 경우 보통은 수% 정도이나 장시간 오래
사용한 V결선 변압기를 통하여 모터전원이 공급되고 있는 경우는
약 10~20% 이상의 불평형율이 나타나고 있습니다.
Motor Relay의 특성
MCT(Motor relay 용 Current converter)
● MCT(Current Converter)는 MOTOR RELAY를 동작시키기 위
하여 AC전류를 DC 전류로 바꾸어 변환시켜 줍니다.
● 특히 내장된 탭을 변경 사용할 수 있어 폭넓은 전류를 사용할
수 있습니다.
● CONVERTER에 20A TAP에 선정하였을 때 MCT에 2회 권선
하면 10A의 전류에서는 20A의 흐르는 전류로 검출하기 때문에
10A에서 동작 시킬수 있다. 같은 방법으로 4회 감으면 5A에서
도 동작 시킬수 있습니다.
Characteristics of Motor Relay
�For the purpose of improving power factor, lead factor capacitor
is installed in parallel to the motor. Usually the motor current at
light load is Var power containing harmonic waves. The
capacitor is installed to absorb unnecessary harmonic wave. But
if the capacity is too large, the open phase and reverse phase
detection circuits designed with 50/60㎐ sine wave may operate
faulty. Although such a case would rarely occur, performance of
circuit needs to be protected from malfunctioning by
determination of over current reacting point, as having the
capacitor installed before the motor relay.
�In general, motor current shows unbalance by several percent.
However, in case of power supply through long used
transformer of V connection, it may swing up to 10-20 percent
or even more.
Features of Motor Relay
MCT(current converter for moter relay)
�MCT converts AC current into DC voltage to operate
motor relays.
�By changing built-in taps. current level can be selected
in steps.
�If 20A tap of MCT is selected and wounded 2 times. 10A
input current will be detected as 20A that the relay can
be operated at 10A current and if would 4 times, the
relay can be operated even at 5A
MCT출력전압특성표(MCT output voltage characteristics)
과부하요소(OVER LOAD)
● MCT에서 반환된 DC전압을 통하여 MOTOR RELAY의 입력에
서 받아 과부하 검출이 시작됩니다. 이때 전류 정정탭에 정해져
있는 설정치이상 흐르게 되면 동작이 시작됩니다.
● 과부하 상태가 되면 시간정정에 맞는 반한시성으로 동작됩니다.
이때의 과전류 동작시간은 전류정정치의 600%의 과전류가 흐
를경우 1~40초 범위로 변화시킬 수 있습니다.
● 동작이 되면 출력 RELAY는 HOLDING 됩니다.
Element for over load
�Over current is detected by DC voltage obtained from
input of the motor relay after conversion. Should the
current exceed the level set by current regulating taps,
the relay becomes activation.
�The relay operates in inverse time limit to set time when
overloaded, the over current active time length can be
adjusted within a range of 1 to 40 seconds when the
current is greater 600 percent than the set value.
�If the relay is operated, the output relay becomes to
holding status.
148
DEESYS TOTAL PRODUCTS GUIDE
MCT TAP
Input current
Output voltage
20A
8A
8V
40A
16A
8V
80A
32A
8V
Motor Protective Relay
결상요소
결상시의 동작치 및 동작시간 특성은 그림6, 그림도7과 같이 MCT의
3상 출력 파형을 검출하여 결상의 상태를 판별하여 구동시킵니다.
● MOTOR RELAY는 결상 검출이라기보다 불평형율을 검출하도록
설계되어 있으며 불평형율 약 35% 또는 65%에 동작되도록
SETTING 되어 있습니다.
● 결상요소의 동작시간은 불평형 35% 이상시 약 1.6초에 동작합니
다.(고속도 setting 시)
Fig6
Open phase
Open phase relay is activated according to current and time
characteristics when open phase status is detected by three
phase output wave form of MCT as shown in Fig. 6 and 7.
�Motor relays are designed more as current unbalance
detector than open phase detector. They are set to operate
approxirmately at 35 percent or 65 percent level of current
unbalance.
�Active time in open phase is approximately 1.6 seconds in an
unbalance of 35% or more (for High-speed action setting.)
Fig7
반상요소
모터의 역회전을 방지키 위한 반상보호로 구성되어 전원전압(3상)을
이용하여 구동시킵니다.
● 전원전압의 V.W상을 이용하여 자체 MOTOR RELAY에 POWER
를 공급합니다.
● 과부하, 결상은 MCT(CONVERTER)를 이용하여 3E RELAY가
동작되나, 반상 검출상태는 3상의 전압을 이용하여 동작됩니다.
외부결선 방식
● 결선시 과부하 및 결상 방법은 MCT에서 검출된 DC �, � 전압을
가지고 3E RELAY를 동작시키므로 반상 검출이 필요치 않을 경우
에는 U상의 결선이 필요하지 않습니다.
● M.G COIL과 계전기 V.W 전원은 동일 전원 상에 연결하는 것이
좋습니다.
● 진상용 콘덴서는 CONVERTER보다 전단에 설치하십시오. 후단에
넣게 될 경우 3E RELAY의 전류 SETTING시에 콘덴서의 전류를
합성하여 정정해야 합니다.
● CURRENT CONVERTERDML 결선시에 �와 �의 극성을 정확히
RELAY와 결선하여 주십시오.
● 3E RELAY 결선시 MOTORDML 전원전압(3 ) 과 3E RELAY의
전원이 U.V.W에 3� 전압이 결선되므로 사양선택시 주의하십시오.
● CONVERTER 1차측에 변류기(CT) 2차측을 이용할 경우에는
MCT-31을 사용해야 합니다.
Reverse phase
The relay is featured for reverse phase protection circuit and
driven by line voltage(3�)
�Driving power is supplied to motor relay through using of
U-V phase of line voltage.
�In case wiring connection to W phase terminal is removed,
overload and open phase elements are activated but
reverse phase element does not.
�In case of over load and open phase, 3E relay is activated
by the power from MCT and in case of reverse phase, it is
operated by 3 phase power.
How to connect wiring
�Since 3E relay is operated by power of DC voltage
detected at MCT for overload and open phase detection,
connection of W phase is not necessary unless reverse
phase detection is intended.
�It is perferrable for MG coil and U-V ends of relay to share
same power source.
�Phase advance capacitor should be tapped on before
converter (at upstream). If tapped on after (close to load
end) the load, set current of 3E relay should include
capacitor current.
�For connection of relay to current converter, polarity of DC
current should not be reversed.
�Since three phase line voltage is connected to motor and
U-V-W phase of same line voltage is connected to 3E
relay, selection of relay should be carefully made to desired
specifications.
�When an use of CT output for converter input is intended,
MCT-31 should be used.
DEESYS TOTAL PRODUCTS GUIDE
149
Motor Protective Relay
삼상불평형율 계산방법 예)
Example of 3 phase unbalance calculation
3상불평형회로 역상분
불평형률=
Unbalance =
factor
X 100%
3상불평형회로 정상분
1a+a2ib+aic
역상분
정상분
=
100
1a+a2ib+a2ic
100
=1.
60
100
=0.6,
70
100
=0.7 )
Table for unbalance ratio
150
Ratio(%)
1.0
1.0
1.0
0
1.0
0.9
0.8
12
1.0
0.8
0.7
24
1.0
0.7
0.6
36
1.0
0.6
0.65
39
1.0
0.5
0.65
51
1.0
0.4
0.75
55
1.0
0.3
0.8
66
1.0
0.2
0.85
77
1.0
0.1
0.9
95
DEESYS TOTAL PRODUCTS GUIDE
Above formula above shall be quoted to determine unbalance
ratio.
For
example,
assume
R phase=100A. S phase=60A, T phase=70A
R:S:T=1:0.6:0.7 (
으므로 아래 표를 이용하여 부하의 불평형률에 대한(%)를 구할 수 있습니다.
이때 불평형률은 36%를 알 수 있습니다.
Unbalance
X 100(%)
Reverse component
1a+a2ib+aic
=
normal component
1a+a2ib+a2ic
3상의 불평형률은 위의 식을 참고 바랍니다. 예를 들어 부하의 전류상태가
R상=100A, S=60A, T=70A
R:S:T=1:0.6:0.7 (
3phase unbalance
circuit reverse component
3phase unbalance
circuit normal component
100
100
=1.
60
100
=0.6,
70
100
=0.7 )
that unbalance ratio in percentage can be read from the table
at right. In the case of this example. unbalance ratio is 36% as
read from the table.
3E, 4E Motor Protective Relay
MPR 3E
MPR 4E
MCT
Feature
Feature
1. 3상 유도전동기가 확실하게 보호되며 과부하 결상(단상운전)및 반상
(역상)을 4E일 경우 지락까지 신속히 검출하여 모터의 소손을 방지
합니다.
2. 광범위한 전류정정과 시간정정을 1대로서 가능합니다.
3. 입력회로에“Surge”
방지회로가 있어서 오동작의 염려가 없습니다.
4. 반도체 H-IC회로로서 기기오차는 물론 반영구적으로 사용할 수 있
습니다.
5. D4E형은 ZCT(영상변류기)를 이용하여 지락으로 인한 사고를 방지
할 수 있습니다.
1. Protection for 3 phase motor with certain in any cases :
over load, single phase operating, reverse, even earth fault.
2. Wide range of current setting and time setting in one unit.
3. Input circuit is equipped with "surge" protection circuit for
no error
4. Built in semiconductor H-IC circuit : And strong against
shock and vibration.
5. D4E type protects motor from earth fault with ZCT
Products
Rated Voltage
Model No
3E
Rated Current
Function
D3E-F41
AC 110V
Flush mounted
D3E-F42
AC 220V
Over load
D3E-F43
AC 380V
Open phase
Flush mounted
D3E-P41
AC 110V
Revers phase
Socket type
D3E-P42
AC 220V
D4E-011
AC 110V
Over load
Open phase
D4E-022
Flush mounted
Socket type
4E
Reverse phase
AC 220V
Ground Fault
MCT
Installation
MCT-31
Less than 600V
1-80A
A/V(converter)
MCT-32
Less than 600V
61-160A
A/V(converter)
Flush mounted
Flush mounted
DEESYS TOTAL PRODUCTS GUIDE
151
3E, 4E Motor Protective Relay
Specification
Deseription
3E
Motor rating
4E
Cirult voltage
Less than AC 600V(3∅) Primary voltgae
Rated current
AC 1-80A to 64-160A, Primary current
Rated voltage
AC 110V, AC 220V, Ac 380V(3∅)
Extent voltage
85%~110% of Rated voltage
Frequency
50/60㎐ common
Contact capacity
AC 125V 10A, AC 250V 6A(cos∅=1.0), DC 30V 5A, AC 250V 3A(cos∅=0.4)
Control power
Power consumption
VA
Operating value
Operating time curve
AC 110V, 220V, 380V
3.5VA
AC 110V, 220V
7VA
10VA
Operation 115% of current set value(105~125%)
Inverse
Inverse, Definite(Ground)
When over load 600% of current set
Element of over load
Operating time
Inverse:Same as 3E
Operating time tap×1(1~10sec)
Ground Fault : More than
Operating time tap×4(4~40sec)
Reset
Current set value
More than 100% of current set value
Operating value
Less than 75% of current set value
Unbalance factor
H(high sensitivity set)35±10%, L(Low sensitivity)65±10%
Element of open phase
Operating time
Less than 4 sec
Value of Operation
Less than 80% rated voltage
Operating time
Starting Lock
Less than 1 sec
Starting holdtime 5sec/10sec/15sec
SL(start lock) Ambient temperature
Insulation resistance
ON(operating) OFF(Non operating)
Operating value:±10%(-10℃~+50℃), operating time:±20%
∙primary-case
∙secondary-case
∙primary-case
Dielectric strength
∙secondary-case
More than 10㏁
AC 2000V 1 min
∙Mutually dry contact : AC 1000V 1min
1.2/50㎲ positive, negative polarity : 3 times
Impulse wave withstand voltage
Electric circuit to case : 5㎸
Aux power to terminal : 4.5㎸
152
Over load
P’
ry current circuit
Multiple 20 of current set value
Factor
Control power circuit
Multiple 1.15 of rated voltage(3 Hours)
Vibration strength
Viabration frequency 16:7㎐, amplitude 4㎜
Mechanical shock resistance
500㎨ (50g)
DEESYS TOTAL PRODUCTS GUIDE
3E, 4E Motor Protective Relay
Front plate
Over load operating time characteristic
Single phase operating characteristic
Internal block diagram
DEESYS TOTAL PRODUCTS GUIDE
153
3E, 4E Motor Protective Relay
Current setting table
Motor Relay
Current setting
Motor Power
220V 4P
Model
Current Converter(M.C.T)
Current
times ratio
Cable
Turns
Times
setting tap
1~2.5
0.25
8
20
2~5
0.5
4
20
4`~10
1
2
20
(rated current
× sticker no)
tap
1
2
KW
0.2
HP
1/4
A
1.6
3
0.4
1/2
2.5
4
0.75
1
3.8
5
1.5
2
6.6
6
2.2
3
9.1
8~20
2
1
20
MCT
7
3.7
5
14.6
8~20
2
1
20
-31
8
5.5
7.5
21.8
16~40
4
1
40
9
7.5
10
28.2
16~40
4
1
40
10
11
15
40.9
32~80
8
1
80
11
15
20
54.5
32~80
8
1
80
12
22
30
78.2
64~160
16
1
fixed
13
30
40
104.5
64~160
16
1
fixed
14
37
50
128.2
64~160
16
1
fixed
5
2~5
0.5
4
20
In case of over
37㎾ using other C.T
15
MCT
-32
Operating time setting be set from
starting to normal operating
time(3phase lnduction motor)
MCT
-31
1. Above motor power : 4 pole 1800rpm case
2. In case high voltage 3 phase induction motor, use high
voltage CT (2nd tated 5A, 10VA)
Operation indication(OC, RVS, OPEN)
Over current : OC
Reverse : RVS
Open phase = OPEN
Part
Settting
ON
OFF
×1
×4
H
L
ON,OFF
ON
OFF
Over
Current
Open
Phase
Reverse
Characteristic
Over current factor using
Over current factor No using
Operating time 1~10sec
Operating time 4~40sec
Operating unbalance rate 35%
Operating unbalance rate 65%
ON,OFF
Reverse factor using
Reverse factor No using
Operating current
In case setting current 16A
16 X 1,15=18.4
Overload current become
18.4A, operating start.
MCT
setting
20
20
20
20
40
80
Fixed
154
Current Setting
ratio
×0.25
×0.5
×1
×2
×4
×8
×16
4
5
6
1
2
4
8
16
32
64
1.25
2.5
5
10
20
40
80
1.5
3
6
12
24
48
96
DEESYS TOTAL PRODUCTS GUIDE
7
8
1.75 2
3.5
4
7
8
14
16
28 32
56 64
112 128
9
10
Operating time setting
2.25
4.5
9
18
36
72
144
2.5
5
10
20
40
80
160
According to starting current time of load, set between
1~40secs.
Time Tap
Multiple ×1
(sec)
×4
1
1
4
2
2
8
3
3
12
4
4
16
5
5
20
6
6
24
7
7
28
8
8
32
9 10
9 10
36 40
3E, 4E Motor Protective Relay
Manual(3E, 4E RELAY)
※ 취급상 주의 상항(Remark)
■ Reted current and penetrating turns(table 1)
Ampere(A)
Penetrating turns
1-2.5
8
2-5
4
4.-10
2
more than 8
1
취급상 주의 상황
1. 정격전류와 도체관통회수의 관계는 동작 특성상 대단히 중요함으로
상기 표1을 참고하시어 필히 지켜주시기 바랍니다.
2. 정격전류가 1-80A는 MCT-31을 사용하고 64-160A는 MCT-32를
사용하여 주십시요.
3. MCT에 도체관통회수는 정격전류에 따라서 표1에 표시된 회수로 3
선과 다같이 같은 방향으로 설치하여 주십시요.
4. 고압 및 대용량의 전동기의 경우는 시판되고 있는 변류기의 2차측
을 MCT에 관통시켜주십시요.
5. 3E,4E,REALY의 경우 3�전압을 정확한 상순으로 3�모두 결선하
십시요.(U.V.W)
Remark
1. Refer to above table 1 and decide penetration turn
according to the using ampere carafully
2. In case of rated current 1-80A, MCT-31 can be used, and
in case of 64~160A, MCT-32 can be used.
3. MCT penetrating wiring turns refer to table 1 and bind the
3 wire(3�) to same direction.
4. In case high voltage and big capacity motor, normal CT'S
secondary side should be penetrated through the MCT.
5. In case of 3E, 4E relay, connect all the 3 phase wire to
normal phase process(U, V, W).
MCT Dimension
DEESYS TOTAL PRODUCTS GUIDE
155
3E, 4E Motor Protective Relay
사용방법
Application
1. MCT의 정정방법
(제품출하시 전류정정 20A에 정정되어 있음 )( MCT -31경우)
전동기의 정격전류에 따라 MCT에 표시된 도체관통회수와 정정탭을
설정합니다.
예)정격전류가 4-10A의 경우는 표1에 의해 관통회수 : 2회 표2에
의해 정정탭20
2. 전류정정 배율 스티커
MOTOR RELAY전류정정값은 4-10으로 스티커 정격전류와 맞게
붙여서 사용하십시요.
(표2참조)
예)정격전류가 4-10A의 경우는 1이됩니다.
3. 전류정정방법
MOTOR RELAY의 전류정정은 스티커 숫자와 전류정정값의 베율로
하여 정격전류값을 정확히 맞추어 주십시요. 이때 동작값은 정정값
의 115%가 됩니다.
예)정정값 5A 목성배율 스티커0.5일 때,
정정전류값 : (5A X 0.5)→2.5A
동작전류값 : (2.5A X 1.15)→2.9A±10%
(table2)
MCT
Setting
tap
20
40
80
2. Current setting ratio sticker
Motor relay current setting value 4~10 can cooperate with
rated current sticker's
Example) In case rated current 4~10A, setting value become 1
3. How to set current
Motor relay current setting should be decided by current
times ratio setting and current setting value. At this time,
operating value is 115%.
Example) In case setting 5A ratio sticker
setting current value:(5A×0.5)→2.5A
Operating current value:(2.5A×1.15)→2.9A±10%
(unit:A)
Current
Setting
ratio
X0.25
X0.5
X1
X2
X4
X8
X16
4
5
6
7
8
9
10
1
2
4
8
16
32
64
1.25
2.5
5
10
20
40
80
1.5
3
6
12
24
48
96
1.75
3.5
7
14
28
56
112
2
4
8
16
32
64
128
2.25
4.5
9
18
36
72
144
2.5
5
10
20
40
80
160
4. 시간정정방법
시간정정 배율은 스위치 위치에 따라(X1, X4) 서 선택하면 됩니다.
이때의 시간은 600%과전류시의 동작시간을 표시합니다.
(단위:초)
예) 시간정정탭 5
목성배율 X 4
정정시간은 20초 (5 X 4)
따라서 동작시간은 20초임.
※ 주의 : (1) 수중모타는 5sec이하에 Setting 해 주십시요.
(2) 일반 3상 유도전동기의 경우 기동시부터 정상운전까
지의 시간에 설정함.
5. 동작표시 복귀방법
동작표시기가 동작하면 적색 LED가 켜집니다. 이때 출력접점은 지
속(Holding)되기 때문에 점검후 복귀(RESET)보턴을 누르면 원래의
상태로 돌아갑니다.
6. 시험방법
MOTOR RELAY에 시험(TEST)보턴을 눌러 계전기의 동작상태를
확인할 수 있습니다.
(단, 동작시까지 계속 눌러 주십시요.)
156
1. How to set MCT
(Current setting is set 20A at factory)(MCT -31)
Select the setting tap and conductor penetrating turn
according to the motor rated current.
Example) In case rated current 4-10A, penetrating turn
setting tap will be 20 according to table 1.
DEESYS TOTAL PRODUCTS GUIDE
4. How to set time
Time setting ratio can be selected by switch position(×1, ×
4) At this time, it mean 600% over current operating time
(unit:sec)
Example) Time setting tap : 5
Ratio : ×4
Setting time 20sec (5×4)
Operating time is 20 seconds
※Note : In case of under water pump, please set less than
5 seconds. In case of normal 3 phase induction
motor, set the time from starting to normal
operating.
5. Operating indication & how to reset
In case operating indicator, red LED is turned on.
At this time, output contactor become holding condition.
After checking, all situation can be returned by pressing
reset button.
6. How to test
Motor relay operating test can be done by pressing test
button.
3E, 4E Motor Protective Relay
7. 접속후 기동전의 확인 및 시험방법
7. Before starting, how to confirm.
MCT 관통회수와 방향
MCT penetrating No and direction
MCT와 3E, 4E RELAY와의 극성 (+,-) 확인
MCT and 3E, 4E relay polarity(+,-) confrmation
제어전류 인가
Control power supply
3상 전원상순(U,V,W) 확인
Confirmation 3 hase order(U,V,W)
반상시험(3상) 전압의 상을 바꾼다.
Revers test (change the phase)
정상 U,V,W 반상 V,U,W
순간 동작하면 정상
In case of instantaneous
operating, it is normal
정상위치로 되돌린다.
Return to normal position
OCR시험(TEST)보턴을 누른다.
지락 TEST 보턴을 누른다
(정상시간 이상)(3E)
(4E)
Press OCR test button
(over setting time)(3E)
Press earth fault test
butto(4E)
동작한다.
Operate
정상
Normal
8. 지락전류정정 및 시험방법(4E relay)
(1) 감도전류는 0.1, 0.2, 0.3, 0.5, 0.7, 1.0, 1.5, 2.0, Lock(A)
9Tap 입니다.
(2) 시간은 0.1, 0.2, 0.3, 0.5, 0.7, 1.0, 2.0, 5.0 Lock(sec)
9Tap 입니다.
(3) 전류와 시간동작 후 GR TEST 보턴을 누르면 Setting 시간과
동일하게 동작합니다.
(4) OCR동작시 OC LED가 켜지고
GR동작시 GR LED가 켜집니다.
(5) 동작후 RESET 보턴을 눌러 정상위치를 확인하지 않으면 모터
의 기동시 기동이 되지 않습니다.
(6) ZCT는 모터의 용량에 맞게 주문하시면 됩니다.
8. How to set earth fault current and test (4E relay)
(1) Sensible current is 0.1, 0.2, 0.3, 0.5, 0.7, 1.0, 1.5, 2.0,
Lock(A) 9taps
(2) Time is0.1, 0.2 0.3 0.5 0.7 1.0 1.5 2.0, 5.0 Lock(sec)
9taps
(3) After current and time setting by the pressing GR test
button, it operate according to setting time.
(4) In case operating OCR, OC LED is on and in case
operating GR, GR LED is on
(5) Without confirmation of normal position by pressing
reset button, motor can't start.
(6) ZCT can be ordered with suitable capacity.
보수∙점검
Maintenance and inspection
1. 3E, 4E, RELAY 자체가 결상 상태가 아닌가
기동시간 이하에서 동작할 때.
2. MCT의 도체관통회수 및 방향 3선 모두 일정한가.
3. RELAY(3E, 4E)의 전원전압 및 MCT의 심한 불평
In case of operating
at under starting
형이 되지 않은가
TEST보턴을 눌러서 RELAY가
동작하여 표시 되는데도 모터회
로가 차단하지 않을 때
RELAY 점점의 Ta, Tb, Tc를 풀어서 Relay
접점의 도통 관계를 확인한다.
In case motor circuit
tripping failure even
if relay operating
indication comes out
by pressign test button
1. 3E,4E Relay is open phase itself
2. MCT penetration turn No and
direction is correct or not all 3 wire
3. Power suppling voltage of relay and
MCT are unbalance?
After disconneting terminals of relay
contact Ta, Tb, Tc, check whether the
relay contacts are energized or not.
DEESYS TOTAL PRODUCTS GUIDE
157
3E, 4E Motor Protective Relay
External wiring diagram (3E Relay)
�Manual operating (Low voltage)
External wiring diagram (4E)
Dimension (4E)
Casing : 난연성(Non-flamable)
color : Black(N1.5)
158
DEESYS TOTAL PRODUCTS GUIDE
�High voltage motor
External terminal
3E, 4E Motor Protective Relay
Indoor zero sequence transformer specification (Ground protection)
Rated current
Inside diameter
(A)
(∅)
ZR-030
100
30
ZR-050
250
50
Model no.
EV penetration Cable ㎟
3∅ 3W
Weight
3∅ 4W
(㎏)
14
8
0.5
80
38
0.7
ZR-065
400
65
150
100
0.9
ZR-080
600
80
250
200
1.5
ZR-100
800
100
325
250
2.2
UNIT(m/m)
Model-No
A
B
C
D
E
F
G
H
ZR/SZR-025
25
25
87
95
110
9
30
20
ZR/SZR/HZR-030
30
25
108
100
114
7
32
32
ZR/SZR/HZR-050
50
25
131
100
122
7
32
36
ZR/SZR/HZR-065
65
26
143
114
133
7
39
37
ZR/SZR/HZR-080
80
34
174
160
180
7
40
40
ZR/SZR/HZR-100
100
38
203
160
180
7
40
40
Dimension
[D3E]-매입형(Flush mounted)
Casing : 난연성(Non-flamable)
color : Black(N1.5)
[D3E] - 소켓형(Socket type)
Casing : 난연성(Non-flamable)
color : Black(N1.5)
DEESYS TOTAL PRODUCTS GUIDE
159
Power Transducer
■Power Transducer
■Voltage Transducer
■Current Transducer
■Watt Transducer
■Var Transducer
■Watt/Watt Hour Transducer
■Var/Var Hour Transducer
■Power Factor/Phase Angle Transducer
■Frequncy Transducer
■Analog to Pulse Transducer
■Zero Sequence Voltage Transducer(V0)
■DC mV/DC V Transducer
■Isolator/Temperature Transducer
Transducer
전력용 변환기(일반형)
DEESYS TOTAL PRODUCTS GUIDE
161
Power Transducer
Description
�DEESYS transducers are designed to accept AC current and Voltage input and provide DC proportional current and
voltage output with high accuracy.
�DEESYS transducers are compact instruments that have outstanding overload and temperature performance.
�DEESYS transducers provide high capability for long distance transmission of output, micro processing equipment and
other converters.
General specification
Head
Auxiliary power
Input burden
Input over capability
Specification
AC 110/220V(±10%), 50/60㎐(1.5VA)
Less than current 0.5VA, Voltage 0.6VA
Current rated : 1.2 In continuous
2 In 10sec
10 In 3sec
Voltage rated : 1.2Vn continuous
Response
Output ripple
Operating temperature range
Less than 400ms, step change 0~95%
Ripple less than 0.5%Ro peak-peak.(span)
-10℃ to + 55℃
Operating humidity
Calibrate adjustment
Zero adjustment
External magnetic field
Dielectric strength
Output load
Surge/Impulse
Case material
162
DEESYS TOTAL PRODUCTS GUIDE
0~99%, non-condensing
±1% minimum
±1% minimum
Less than 0.01% 100AT/1M center
Terminal to case : 4000V AC rms 1minute
Input to output : 2000V AC rms 1 minute
DC current mode : max 10V drop, DC voltage mode : max 5mA drive
IEC255-4, 5㎸, 1.2X50㎲, IEC 255-22-1, 2.5kV(1MHz/400Hz)
ABS resin, DIN rail type
Voltage Transducer
�High accuracy 0.1% or 0.2%
�Excellent long term stability
�High magnetic field immunity
�Meets IEEE SWC test.
�Outstanding overload and temperature
performance.
�Stability : Maximum 0.01%. ℃
Description
DEESYS Voltage transducers have good linearity and low ripple output.
The elements are totally isolated among input, output, power and others to case. This voltage transducer provide proportional
DC current and voltage output which are not influenced by any load resistance, even under very low load condition, accurate
output is available with quick response.
Transducers are designed to respond to the voltage value of input but calibrated to root mean square (RMS) reading of pure
sinusoid.
Ordering procedure
∙CLASS : 0.1 or 0.2
∙DEESYS VOLTAGE T/D
∙SOURCE
1. 1∅
2. 1∅×3EA
∙INPUT
1. 0~150V
2. 0~300V
3. Option
∙OUTPUT
1. DC 4~20mA
2. DC 0~20mA
3. DC 2~10V
4. DC 1~5V
5. Option
∙HZ
1. 60HZ
2. 50HZ
Standard product
DVT-
Model
Output
Source
DVT-1111
DC 4~20mA
1∅
DVT-1121
DC 0~20mA
1∅
DVT-1211
DC 4~20mA
1∅
DVT-1221
DC 0~20mA
1∅
DVT-2111
DC 4~20mA
1∅X3EA
DVT-2121
DC 0~20mA
1∅X3EA
DVT-2211
DC 4~20mA
1∅X3EA
DVT-2221
DC 0~20mA
1∅X3EA
Order made is avaliable except for standard products.
Output/Load resistance
Output
Load Compliance Ϊ
0~20mA
�500
4~20mA
�500
2~10V
�2K
1~5V
�1K
DEESYS TOTAL PRODUCTS GUIDE
163
Voltage Transducer
Installation and operation
■ Output Linearity
Mounting and dimension
■ 3 Element
■ 1 Element
Connection diagram
■ 3 Element
164
DEESYS TOTAL PRODUCTS GUIDE
■ 1 Element
Current Transducer
�High accuracy 0.1% or 0.2%
�Excellent long term stability.
�High magnetic field immunity.
�Meets IEEE SWC test.
�Outstanding overload and temperature
performance.
�Stability : Maximum 0.01%. ℃
Description
DEESYS Current transducers have good linearity and low ripple output.
The elements are totally isolated among input, output, power and others to case. This ampere transducer provide proportional DC
current and voltage output which are not influence by any load resistance, even under very low load condition, accurate output is
available with quick response.
Transducers are designed to respond to the current value of input but calibrated to root mean square (RMS) reading of pure
sinusoid.
Ordering procedure
∙CLASS : 0.1 or 0.2
∙DEESYS Ampere T/D
∙SOURCE
1.1∅
2.1∅ × 3EA
∙INPUT
1.0~5A
2.0~1A
3.Option
∙OUTPUT
1.DC 4~20mA
2.DC 0~20mA
3.DC 2~10V
4.DC 1~5V
5.Option
∙HZ
1.60HZ
2.50HZ
Standard product
DAT-
Model
Output
Source
DAT-1111
DC 4~20mA
1∅
DAT-1121
DC 0~20mA
1∅
DAT-1211
DC 4~20mA
1∅
DAT-1221
DC 0~20mA
1∅
DAT-2111
DC 4~20mA
1∅X3EA
DAT-2121
DC 0~20mA
1∅X3EA
DAT-2211
DC 4~20mA
1∅X3EA
DAT-2221
DC 0~20mA
1∅X3EA
Order made is avaliable except for standard products.
Output/Load resistance
Output
Load Compliance Ϊ
0~20mA
�500
4~20mA
�500
2~10V
�2K
1~5V
�1K
DEESYS TOTAL PRODUCTS GUIDE
165
Current Transducer
Installation and operation
■ Output Linearity
Mounting and dimension
■ 3 Element
■ 1 Element
Connection diagram
■ 3 Element
166
DEESYS TOTAL PRODUCTS GUIDE
■ 1 Element
Watt Transducer
�High accuracy 0.1% or 0.2%
�Excellent long term stability.
�Real power-able to measure distorted waveform
�High magnetic field immunity.
�Meets IEEE SWC test.
�Outstanding overload and temperature performance.
�Stability : Maximum 0.01%. ℃
Description
DEESYS Watt transducer are designed to accept DC voltage or current and provide output(VI cos�) with high accuracy and quick
response.
Internal circuit are composed entirely of high quality components and power calibration equipment for measuring exact power
energy.
Ordering procedure
∙CLASS : 0.1 or 0.2
∙DEESYS Watt T/D
∙SOURCE
1. 1∅2W, 2. 1∅3W
3. 3∅3W, 4. 3∅4W
∙INPUT(I)
1.0~5A
2.0~1A
3.Option
∙INPUT(V)
1.0~110V
2.0~220V or 190√3
3.Option or 380√3
∙OUTPUT
1.DC 4~20mA
2.DC 0~20mA
3.DC 0~1mA
4.DC 1~5V
5.DC 4~12~20mA(±WATT)
6. Option
Standard product
DWT-
Model
Output
Source
DWT-11111
DC 4~20mA
1∅2W
DWT-21111
DC 4~20mA
1∅3W
DWT-31111
DC 4~20mA
3∅3W
DWT-41111
DC 4~20mA
3∅4W
DWT-11211
DC 4~20mA
1∅2W
DWT-21211
DC 4~20mA
1∅3W
DWT-31211
DC 4~20mA
3∅3W
DWT-41211
DC 4~20mA
3∅4W
Order made is avaliable except for standard products.
Output/Load resistance
Output
Load Compliance Ϊ
0~20mA
�500
4~20mA
�500
0~1mA
�10K
1~5V
�1K
∙HZ
1.60HZ
2.50HZ
DEESYS TOTAL PRODUCTS GUIDE
167
Watt Transducer
Installation and operation
■ Output Linearity
Mounting and dimension
■ 3 Element
Connection diagram
■ DWT-3�3W
■ DWT-3�4W
168
DEESYS TOTAL PRODUCTS GUIDE
Watt Transducer
Theory of operation
1. Watt and Var of conversional equation
Optional output P△, which in modulated according to the conversion method of watt and var transducer, are proportional to input
current l△ and input voltage V△.
P△=K∙V△∙l△[K:proportional constant]
[1]
For the satisfaction above [1] equation. Power(P) input voltage(V) input current(I) should be set up as an integral equation including
time function P(t), K, V(t), I(t)
Pw=
1
∫
T
T
O
V(t)I(t)dt
Pw=VI cosφ[watt]
Pr=VI sinφ[var]
2. Linearity and phase angle of input transformer
Transducer's output linearity is depend on the transformer's primary and secondary turn ratio and phase stability. Especially under the
low load transducer should be designed to maintain the linearity within 5%~10% range, which influence transducer output complience
error.
Winding Ratio a=I1/I2
I1=5%~100%
I1k=akI2k
ak=a(1±0.025%)
I1k=a1kI2k
�� I ± 10minutes I
DEESYS TOTAL PRODUCTS GUIDE
169
Watt Transducer
Theory of operation
2. Calibrating Watt/Var equation
Cailbrating watt =
Max scale value
P.T ratio × CT ratio
Ex1)3P 3W Network
full scale of watt : 600㎾
P.T ratio : 3300/110V
C.T ratio : 100/5A
Cailbrating watts =
Ex1)3P 4W Network
full scale of watt : 2000㎾
22900V
190V
P.T ratio :
3
3
√
√
C.T ratio : 50/5A
600㎾
(3300/110) × 100/5
Cailbrating watts =
= 1.0㎾
(
2000kW
22900V 190V
×(50/5A)
3
√
√3
)
= 1.666kW
Conversion Table
Net work
1P2W
1P3W
P.T.ratio(V)
110
110
220
380
/110
440
/110
3300
/110
6600
/110
22000
/110
22900
/110
Calibrating
watts
3P3W
3P4W
154㎾
/110
208√3
380√3
/190√3
380
/√3
11400√3
/190√3
22900√3
/190√3
1.666㎾
0.6㎾
1.0㎾
2.0㎾
1.158㎾
1.0㎾
1.0㎾
1.0㎾
1.0㎾
0.961㎾
1.0㎾
2.0㎾
2.0㎾
4.0㎾
1.666㎾
5/5
0.6
1
2
4
4
30
60
200
200
1400
2
4
4
100
200
10/5
1.2
2
4
8
8
60
120
400
400
2800
4
8
8
200
400
C.T.ratio
15/5
1.8
3
6
12
12
90
180
600
600
4200
6
12
12
300
600
20/5
2.4
4
8
16
16
120
240
800
800
5600
8
16
16
400
800
25/5
3.0
5
10
20
20
150
300
1000
1000
7000
10
20
20
500
1000
30/5
3.6
6
12
24
24
180
360
1200
1200
8400
12
24
24
600
1200
40/5
4.8
8
16
32
32
240
480
1600
1600
11.2㎿
16
32
32
800
1600
50/5
6.0
10
20
40
40
300
600
2000
2000
14.0
20
40
40
1000
2000
60/5
7.2
12
24
48
48
360
720
2400
2400
16.8
24
48
48
1200
2400
75/5
9.0
15
30
60
60
450
900
3000
3000
21.0
30
60
60
1500
3000
80/5
9.6
16
32
64
64
480
960
3200
3200
2204
32
64
64
1600
3200
100/5
12.0
20
40
80
80
600
1200
4000
4000
28.0
40
80
80
2000
4000
120/5
14.4
24
48
96
96
720
1440
4800
4800
33.6
48
95
95
2400
4800
150/5
18.0
30
60
120
120
900
1800
6000
6000
42.0
60
120
120
3000
6000
200/5
24.0
40
80
160
160
1200
2400
8000
8000
56.0
80
160
160
4000
8000
250/5
30.0
50
100
200
200
1500
3000
10㎿
10㎿
70.0
100
200
200
5000
10㎿
300/5
36.0
60
120
240
240
1800
3600
12
12
84.0
120
240
240
6000
12
400/5
48.0
80
160
320
320
2400
4800
16
16
112.0
160
320
320
8000
16
20
500/5
60.0
100
200
400
400
3000
6000
20
20
140
200
400
400
10㎿
600/5
72.0
120
240
480
480
3600
7200
24
24
168
240
480
480
12
24
750/5
90.0
150
300
600
600
4500
9000
30
30
210
300
600
600
15
30
800/5
96.0
160
320
640
640
4800
9600
32
32
224
320
640
640
16
32
1000/5
120.0
200
400
800
800
6000
12㎿
40
40
280
400
800
800
20
40
1200/5
144.0
240
480
960
960
7200
14.4
48
48
336
480
960
960
24
48
1500/5
180.0
300
600
1200
1200
9000
18.0
60
600
420
600
1200
1200
30
60
2000/5
240.0
400
800
1600
1600
12㎿
24.0
80
80
560
800
1600
1600
40
80
2500/5
300.0
500
1000
2000
2000
15
30.0
100
100
700
1000
2000
2000
50
100
170
DEESYS TOTAL PRODUCTS GUIDE
Var Transducer
�High accuracy 0.2% or 0.3%
�Excellent long term stability.
�Real power-able to measure distorted waveform
�High magnetic field immunity.
�Meets IEEE SWC test.
�Outstanding overload and temperature performance.
Description
DEESYS Var transducer are designed to accept DC voltage or current and provide output(VI sin∅) with high accuracy and quick
response.
Internal circuit are composed entirely of high quality components and power calibration equipment for measuring exact reactive
power.
Ordering procedure
∙CLASS : 0.2 or 0.3
Standard product
DRT-
Model
Output
Source
DRT-11111
DC 4~20mA
1∅2W
DRT-21111
DC 4~20mA
1∅3W
DRT-31111
DC 4~20mA
3∅3W
∙DEESYS Var T/D
DRT-41111
DC 4~20mA
3∅4W
∙SOURCE
1. 1∅2W, 2. 1∅3W
3. 3∅3W, 4. 3∅4W
DRT-11211
DC 4~20mA
1∅2W
DRT-21211
DC 4~20mA
1∅3W
∙INPUT(I)
1.0~5A
2.0~1A
3.Option
∙INPUT(V)
1.0~110V
2.0~220V or 190√3
3.Option or 380√3
∙OUTPUT
1.DC 4~12~20mA
2.DC 0~10~20mA
3.DC 0~0.5~1mA
4.DC 1~3~5V
5.DC 4~20mA(cos� 1/4mA, LAG 0.5/mA)
6.Option
DRT-31211
DC 4~20mA
3∅3W
DRT-41211
DC 4~20mA
3∅4W
Order made is avaliable except for standard products.
Output/Load resistance
Output
Load Compliance Ϊ
0~20mA
�500
4~20mA
�500
0~1mA
�10K
1~5V
�1K
∙HZ
1.60HZ
2.50HZ
DEESYS TOTAL PRODUCTS GUIDE
171
Var Transducer
Installation and operation
Output Linearity
Mounting and dimension
Connection diagram
DRT-1∅2W
DRT-3∅4W
172
DEESYS TOTAL PRODUCTS GUIDE
DRT-1∅3W, 3∅3W
Watt/Watt Hour Transducer
�High accuracy Watt : 0.1% (Option)/ 0.2% + PF 0.15%
W.H : 0.2% + PF 0.15%
�Extremely excellent long term stability with.
�Conversion method with R. C time constant
devided of multiple equation.
�Meets IEEE SWC test.
�Outstanding overload and temperature performance.
�Stability : Maximum 0.02%/℃
Description
DEESYS watt/watt hour transducer are designed to measure the power and energy with various functions simultanously.
Output is adopted time division multiplication method using the R.C.
Watt hour output shall be provided various pulses according to the user's purpose and usage.
Ordering procedure
Standard product
DWW-
∙CLASS : 0.1 or 0.2
∙DEESYS WATT/WATT
HOUR T/D
∙SOURCE
1. 1∅2W, 2. 1∅3W
3. 3∅3W, 4. 3∅4W
∙INPUT(I)
1. 0~5A
2. 0~1A
Model
Output
Source
DWW-111111
DC 4~20mA.1Pulse/Watthour
1∅2W
DWW-211111
DC 4~20mA.1Pulse/Watthour
1∅3W
DWW-311111
DC 4~20mA.1Pulse/Watthour
3∅3W
DWW-411111
DC 4~20mA.1Pulse/Watthour
3∅4W
Order made is avaliable except for standard products.
3. Option
Output/Load resistance
∙INPUT(V)
1. 0~110V or 190√3
3. Option
2. 0~220V or 380√3
∙OUTPUT(DC)
1. DC 4~20mA 2. DC 0~20mA
3. DC 0~1mA 4. DC 1~5V 5. Option
∙OUTPUT(Pulse)
1. 1Pulse/Watt hour
2. 1Pulse/10Watt hour
3. 10Pulse/Watt hour
4. Option
Output
Load Compliance Ϊ
0~20mA
�500
4~20mA
�500
0~1mA
�10K
1~5V
�1K
∙HZ
1. 60HZ
2. 50HZ
DEESYS TOTAL PRODUCTS GUIDE
173
Watt/Watt Hour Transducer
Installation and operation
Output Linearity
Mounting and dimension
Connection diagram
DWW-1∅2W
DWW-3∅4W
174
DEESYS TOTAL PRODUCTS GUIDE
DWW-1∅3W, 3∅3W
Var/Var Hour Transducer
�High accuracy Var : 0.2% (Option)/ 0.3% + PF 0.15%
VarH : 0.3% + PF 0.15%
�Extremely excellent long term stability with.
�Conversion method with R. C time constant
devided of multiple equation.
�Meets IEEE SWC test.
�Outstanding overload and temperature performance.
�Stability : Maximum 0.02%/℃
Description
DEESYS var/var hour transducer are designed to measure the power and energy with various functions simultanously.
Output is adopted time division multiplication method using the R.C.
Var hour output shall be provided various pulses according to the user's purpose and usage.
Ordering procedure
∙CLASS : 0.2 or 0.3
Standard product
DRR-
∙DEESYS VAR/VAR
HOUR T/D
∙SOURCE
1. 1∅2W, 2. 1∅3W
3. 3∅3W, 4. 3∅4W
∙INPUT(I)
1. 0~5A
2. 0~1A
∙INPUT(V)
1. 0~110V or 190√3
3. Option
3. Option
Output
Source
DRR-111111
DC 4~20mA.1Pulse/Var hour
1∅2W
DRR-211111
DC 4~20mA.1Pulse/Var hour
1∅3W
DRR-311111
DC 4~20mA.1Pulse/Var hour
3∅3W
DRR-411111
DC 4~20mA.1Pulse/Var hour
3∅4W
Output/Load resistance
2. 0~220V or 380√3
∙OUTPUT(DC)
1. DC 4~20mA 2. DC 0~20mA
3. DC 0~1mA 4. DC 1~5V 5. Option
∙OUTPUT(Pulse)
1. 1Pulse/Var hour
2. 1Pulse/10Var hour
3. 10Pulse/Var hour
4. Option
Model
Output
Load Compliance Ϊ
0~20mA
�500
4~20mA
�500
0~1mA
�10K
1~5V
�1K
∙HZ
1. 60HZ
2. 50HZ
DEESYS TOTAL PRODUCTS GUIDE
175
Var/Var Hour Transducer
Installation and operation
Output Linearity
Mounting and dimension
Connection diagram
DRR-1∅2W
DRR-3∅4W
176
DEESYS TOTAL PRODUCTS GUIDE
DRR-1∅3W, 3∅3W
Power Factor/Phase Angle Transducer
�High accuracy 0.5/3.0%
�Excellent long term stability.
�High magnetic field immunity.
�Meets IEEE SWC test.
�Outstanding overload and temperature performance.
�Stability : Maximum 0.05%/℃
Description
DEESYS power factor and phase angle transducer measure the load power factor and phase angle between one voltage and
current.
According to the load condition, model shall be devided two types balance and unbalance. Balanco type's external wiring is simple.
Ordering Procedure
∙CLASS : 0.5 or 3.0
DPA
DPF-
∙DEESYS POWER
FACTOR T/D
∙SOURCE
1. 1∅2W, 2. 1∅3W
3. 3∅3W, 4. 3∅4W
∙INPUT(I)
1. 0~5A
2. 0~1A
∙INPUT(V)
1. 0~110V or 190√3
3. Option
∙OUTPUT(DC)
1. DC 4~12~20mA
2. DC 0~10~20mA
3. DC 0~0.5~1mA
4. DC 1~3~5V
∙HZ
1. 60HZ
2. 50HZ
3. Option
2. 0~220V or 380√3
Standard Product
Model
Output
Source
DPF-11111□
DC 4~20mA
1∅2W
DPF-21111□
DC 4~20mA
1∅3W
DPF-31111□
DC 4~20mA
3∅3W
DPF-41111□
DC 4~20mA
3∅4W
DPF-11211□
DC 4~20mA
1∅2W
DPF-21211□
DC 4~20mA
1∅3W
DPF-31211□
DC 4~20mA
3∅3W
DPF-41211□
DC 4~20mA
3∅4W
DPA-11111□
DC 4~20mA
1∅2W
DPA-21111□
DC 4~20mA
1∅3W
DPA-31111□
DC 4~20mA
3∅3W
DPA-41111□
DC 4~20mA
3∅4W
DPA-11211□
DC 4~20mA
1∅2W
DPA-21211□
DC 4~20mA
1∅3W
DPA-31211□
DC 4~20mA
3∅3W
DPA-41211□
DC 4~20mA
3∅4W
Order made is avaliable except for standard products.
Output/Load resistance
∙LOAD
1 : Unbalance
2 : Balance
Output
Load Compliance Ϊ
0~20mA
�500
4~20mA
�500
0~1mA
�10K
1~5V
�1K
DEESYS TOTAL PRODUCTS GUIDE
177
Power Factor/Phase Angle Transducer
Installation and operation
Output Linearity
Mounting and dimension
Connection diagram
178
DPF, DPA-1∅2W
DPF, DPA-1∅3W(Blance)
DPF, DPA-3∅3W(Blance)
DPF, DPA-3∅4W(Blance)
DPF-3∅3W(Unblance)
DPF-3∅4W(Unblance)
DEESYS TOTAL PRODUCTS GUIDE
Frequency Transducer
�High accuracy 0.3%(option)/0.5%
�Excellent long term stability.
�High magnetic field immunity.
�Outstanding overload and temperature performance.
�Stability : Maximum 0.04%/℃
Description
DEESYS frequency transducers are demonstrated in a narrow frequency band and very suitable to detect the deviation from center
frequency.
Ordering procedure
∙CLASS : 0.3 or 0.5
∙DEESYS Frequency T/D
∙SOURCE
1. 1∅2W
∙INPUT(V)
1. 110V
2. 220V
3. Option
∙OUTPUT
1. DC 4~20mA
2. DC 0~20mA
3. DC 2~10V
4. DC 1~5V
5. Option
Standard product
DFT-
Model
Output
DFT-1111
DC 4~20mA
DFT-1121
DC 4~20mA
DFT-1211
DC 4~20mA
DFT-1221
DC 4~20mA
Source
1�
Order made is avaliable except for standard products.
Output/Load resistance
Output
Load Compliance Ϊ
0~20mA
�500
4~20mA
�500
0~1mA
�10K
1~5V
�1K
∙HZ
1. 60HZ(55HZ~65HZ)
2. 50HZ(45HZ~55HZ)
DEESYS TOTAL PRODUCTS GUIDE
179
Frequency Transducer
Installation and operation
Output Linearity
Mounting and dimension
Connection diagram
180
DEESYS TOTAL PRODUCTS GUIDE
Analog To Pulse Transducer
�High accuracy 0.25%
�Excellent long term stability.
�Meets IEEE SWC test.
Description
DEESYS Analog to pulse transducers are designed to accept analog input and provide pulse output proportionally, suitable to
measure the current consumption and total integration of various process.
Ordering procedure
∙CLASS : 0.25
∙DEESYS ANALOG TO
PULSE T/D
∙INPUT(V)
1. DC 4~20mA
2. DC 0~20mA
3. DC 0~1mA
4. DC 0~5V
5. DC 0~10V
6. Option
∙OUTPUT
1. 100Pulse/Hour
2. 1000Pulse/Hour
3. 10000Pulse/Hour
4. Option
Connection diagram
Standard product
DAP-
Model
Output
DAP-12
1000Pulse/Hour
DAP-22
1000Pulse/Hour
DAP-32
1000Pulse/Hour
DAP-42
1000Pulse/Hour
DAP-52
1000Pulse/Hour
Order made is avaliable except for standard products.
Output/Load resistance
Output
Load Compliance Ϊ
0~20mA
�500
4~20mA
�500
0~1mA
�10K
1~5V
�1K
Output linearity
Mounting and dimension
DEESYS TOTAL PRODUCTS GUIDE
181
Zero Sequence Voltage[V0] Transducer
�High accuracy 0.1%(option/0.2%
�Excellent long term stability.
�Meets IEEE SWC test.
�Stability : Maximum 0.01%/℃
Description
DEESYS Zero sequence voltage(V0) transducers, when ground fault occur, detect the abnormal electric potential and convert to DC
output for measuring,
Ordering procedure
∙CLASS : 0.1 or 0.2
∙DEESYS V0 T/D
∙INPUT(V0)
1. 0~150V(110V)
2. 0~260V(190V)
3. Option
∙OUTPUT
1. DC 4~20mA
2. DC 0~20mA
3. DC 0~1mA
4. DC 1~5V
5. Option
∙HZ
1. 60HZ
2. 50HZ
Connection diagram
182
DEESYS TOTAL PRODUCTS GUIDE
Standard product
DVo-
Model
Output
DVO-111
DC 4~20㎃
DVO-121
DC 0~20㎃
DVO-211
DC 4~20㎃
DVO-221
DC 0~20㎃
Order made is avaliable except for standard
products.
Output/Load resistance
Output
Load Compliance Ϊ
0~20mA
�500
4~20mA
�500
0~1mA
�10K
1~5V
�1K
Output linearity
Mounting and dimension
DC mV/DC V Transducer
�High accuracy 0.1%(option/0.2%
�Excellent long term stability.
�Meets IEEE SWC test.
�Stability : Maximum 0.02%/℃
Description
DEESYS DCmV transducers are designed to accept shunt secondary input for measuring the DC big current. DC volt transducers
convert DC source to DC current or lower voltage for measuring.
Ordering procedure
∙CLASS : 0.1 or 0.2
Standard product
DDC-
∙DEESYS DC.V T/D
∙CHOOSE T/D
1. mV
2. V
∙INPUT(V0)
1. DC 0~50mV, 2. DC 0~100mV
3. DC 0~110V, 4. DC 0~120V
5. DC 0~150V, 6. DC 0~300V
7. ±50mV[-50mV(4mA) 0mV(12mA)+50mV(20mA)]
8. Option
∙OUTPUT
1. DC 4~20mA 2. DC 0~20mA
3. DC 2~10V
4. DC 1~5V
5. 0~10V
6. Option
∙HZ
1. 60HZ
2. 50HZ
Connection diagram
Model
Output
DDC-1111
DC 4~20㎃
DDC-1221
DC 0~20㎃
DDC-2311
DC 4~20㎃
Order made is avaliable except for standard
products.
Output/Load resistance
Output
Load Compliance Ϊ
0~20mA
�500
4~20mA
�500
2~10V
�2K
1~5V
�1K
Output linearity
Mounting and dimension
DEESYS TOTAL PRODUCTS GUIDE
183
Isolator/Temperature Transducer
�High accuracy 0.2%(only RTD/2.0%
�Excellent long term stability.
�Meets IEEE SWC test.
�Stability : Maximum 0.02%/℃
Description
DEESYS Isolator transducer is used for isolating DC circuit and among various senser insulation, converting DC input to other
DC input.
Temperature tranducers(RTD) which utilize the resistance variation are designed to accept temperature measure resistance meter
output and provide proportional temperature output.
Ordering procedure
∙CLASS : 0.1 or 0.2
Standard product
DIS
Model
Output
DIS-14
DC 1~5V
∙DEESYS ISOLATOR T/D
DIS-51
DC 4~20㎃
∙INPUT
1. DC 4~20mA, 2. DC 0~20mA
3. DC 0~1mA, 4. DC 0~1V
5. DC 1~5V,
6. DC 0~10V, 7. Option
DIS-11
DC 4~20㎃
DRD-21
DC 4~20㎃
DRD-41
DC 4~20㎃
Order made is avaliable except for standard products.
∙OUTPUT
1. DC 4~20mA 2. DC 0~20mA
3. DC 0~1mA 4. DC 1~5V
5. DC 0~10V
6. Option
Output/Load resistance
Output
∙CLASS : 2.0
DRD
∙DEESYS TEMPERATURE T/D
∙TEMPERATURE RANGE
1. 0~50℃, 2. 0~100℃
3. 0~150℃, 4. 0~200℃
5. 0~300℃, 6. -50~+100℃, -100+100℃
0~20mA
�500
4~20mA
�500
0~1mA
�10K
1~5V
�1K
Output linearity
∙OUTPUT
1. DC 4~20mA 2. DC 0~20mA
3. DC 0~1mA 4. DC 1~5V
Connection diagram
184
DEESYS TOTAL PRODUCTS GUIDE
Load Compliance Ϊ
Mounting and dimension
한국전기연구원 개발시험합격품
Induction Type
Protective Relay
■Induction Protective Relay
■Induction Type Over Current Relay [OCR] 50/51
■Induction Type Ground Over Current Relay [50N/51N]
■Induction Type Over, Under Voltage Relay [59] [27] [64]
■Induction Type Directional(Selective) Ground Relay [67]
유도형 계전기
OCR, OCGR, OVR,
UVR, OVGR, SGR
DEESYS TOTAL PRODUCTS GUIDE
185
Induction Protective Relay
Ordering procedure
�Over current relay
D
OC - A - CID4
DEESYS
CO(OCR) for distribution
C - Normal open contact
CO(OCR) for receiving
I - With instantaneous unit(Non symbol has no IIT coil)
CG(OCGR) for distribution
H - With holding coil
CG(OCGR) for receiving
D - Drawout case(Non symbol D is non drawout type)
5 - 0.5-2.5A(OCGR)
4 - 4 ‐12A
3 - 3 - 9A
OCR
(According to ordering for
setting other current taps)
2 - 2 - 6A
A - Inverse
B - Very inverse
LA-Long time(inverse)
�Voltage relay
D
OV
DEESYS
CD1
OV(OVR)
C - Normal open contact
UV(UVR)
O - Normal colsed contact
VG(OVGR)
D - Draw out case (Non symbol D is Non drawout type)
1 - 110V
2 - 220V
16 - 110V(60~90V)
26 - 220V(160~190V)
9 - 190V
15 - 15V
8 - 8V
5 - 5.5V
�Directional(slective) ground relay
D
SG
C D1
SG(SGR)
DEESYS
186
DEESYS TOTAL PRODUCTS GUIDE
(According to ordering for
setting other voltage taps)
Induction Protective Relay
보호협조
전력계통에 사용되는 계전기는 전계통의 계전기가 상호 보호협조가 되
어야 합니다. 특히 과전류 계전기의 보호 협조는 더욱 중요하며 수전
단에 설치되는 과전류 계전기의 보호협조 주요항목은 다음과 같습니
다.
1) 수용가내의 계통에 있어서 단락및 과부하의 정도에 따라 정확히 동
작 하여야 하며 전후단 계전기와 적절한 동작시간을 설정하여 사고
파급을 최소화 해야한다.
2) PF CB형의 경우에는 PF(한류FUSE)와 CB(차단기)와의 책무 분담
이 적절하여야한다.
(PF의 용량 및 CB의 차단기 용량 선정)
3) 위의 계통에 있어서 배전변전소 OCR과의 동작협조가 취해 져야
한다(OCR의 관성특성이나 차단기의 차단시간을 고려할 것.)
4) 수용가 내의 분기 OCR과의 동작협조가 되어야 한다.
5) 저압측 사고에 따라 수전단 OCR이 동작하지 않도록 저압축 MCC
(배선용 차단기)와의 동작 협조가 되어야 한다.
6) OCR의 한시요소의 동작 시간은 부하 변압기의 열특성 곡선을 넘
어서는 안된다.
7) 사고시에 변압기, 차단기, CABLE, CT등의 기기는 단락 강도나 과
부하 용량에 충분히 견디어야 한다.
8) CT의 선정은 과전류 정수와 BURDEN을 고려하여 선정할것.
�Application diagram for relay
Protective coordination
In general, relays being used in power system should be a
function of protective coordination including over current
relay, The major items of protective coordination for over
current relay are as following
1) On receiving system, the relay should be operated surely
at short circuit and over load, and detected the fault point
and responded currently against the fault current of
impedance.
2) In case of P. F type and C. B type, 2 types should be
charge of it's respective role appropriately (selection of P.
F capacity and C. B capacity)
3) In above system, the relay should be operated on
coordination with OCR in distribution substation.
4) The relay should be operated on coordination with OCR in
feeder distribution line.
5) should be operated on coordination with MCCB of low
voltage side so that OCR of receiving line should not be
operated due to fault of low voltage side.
6) The operating time of definite O. C. R element should not
excess feet characteristic curve of load transformer.
7) When it occures fault, the equipments : transformer,
breaker, cable etc should be endured short circuit strength
or over load suffitiently.
8) When there are to select for relay, please consider of
burden and over current constant for C. T
�Protective coordination
DEESYS TOTAL PRODUCTS GUIDE
187
Induction type Over Current Relay[OCR] 50/51
Features
특징
과전류 계전기는 과부하 및 단락 사고시 동작하는 계전기로서 과부하
고장은 한시요소(ICS)가 동작 및 표시하고 단락 사고 및 대전류가 인
입시는 순시요소(IIT)가 동작 및 표시하여 사고의 크기에 따라 적절히
대응하여 보호하고 사고유형을 파악하기 용이하도록 설계 되었습니다.
1) 배전단 OCR(DCO형)과 수전단 OCR(DOC형)을 그림3, 4 와 같이
구분하여 배전단과 수전단과의 보호협조를 용이 하도록 제작하였
습니다.
2) 진동 및 충격등의 오동작 방지를 위하여
a) 회전부(원판)를 광각형으로 설계 주접점(원판접점)의 간격을
최대화 하였습니다.
b) 회전부 원판의 PIVOT와 축수석을 특수설계하여 충격 진동에
의해 이탈 및 파손 되는 것을 방지하였습니다.
c)회전부 원판의 마찰을 극소화 하였습니다.
3) 부품의 정밀화로 기기의 신뢰성을 향상시켰습니다.
4) 설치 취급시 기존 계전기와 동일하게 사용토록 규격화하여 편리
하게 사용할 수 있습니다.
5) 동작 표시기는 순시( 약 20ms)으로 동작되며 황색표시(Munsell
No.2 5yr 6/13)로 사고 판별이 용이합니다.
For DCO type characteristic of protective coordination
188
DEESYS TOTAL PRODUCTS GUIDE
Over current relay(O. C. R) is operated on overload and
short circuit.
This relay has two elements : one is definitive element for
operating and indicating on fault of overload, the other is
instantaneous element for operating and indicating in rush
current on fault of short circuit.
And then this relay is designed that it is easy to detect a
reason of fault and to response to what fault is some
trouble.
1) As diagram 3 & 4, this relay is two types : one type is
DCO type for distribution, the other type is DOC type for
receiving. These two types will be good coordination for
protective system of line.
2) For protection of misoperation on some shock, impact &
inspection
a) The rotating port (round type disk) is designed wide
angle type and the distance of main contact (the
contact of round type disk) is long.
b) The pivot and main post of rotating round type disk
are designed specially and it will protect them from
seperation and damage the to some shock or
impact.
c) Minimization the friction of round type disk.
3) Improvement of reliablity of the relay the to precision of
all parts
4) Because this relay is manufactured and standardized
some typical type, it is easy to use the relay and
change the relay installed in panel to a new relay
5) The operating target will be operated instantaneous
(about 20ms)and it is easy to distinguish to fault
according to the operating target color. (when it is fault,
the target color will be yellow)
For DOC type characteristic of protective coordination
Induction type Over Current Relay[OCR] 50/51
Specification
�ICS coil impedance
Rating
Coil Ressistance(Ω)
0.81/0.16
1.0/0.17
32/0.85
0.15/0.65
36
0.27
300
1160
1310
2260
2.0
0.62
0.65
5000
18000
0.2A/2.0A
0.5A/2.0A
0.1A/1.0A
0.5A/1.0A
0.1A
1.0A
24V
110V
125V
220V
0.5A
1.0A
2.0A
110V
220V
D.C
A.C
Operating Value
70-90%
of tap value
�DCO Type
Time
Characteristics
Rating
Type
Model No
NonDrawout
DCO-A
Drawout
DCO-A
Inverse
Very
Inverse
NonDrawout
DCO-A
Drawout
DCO-A
NonDrawout
DCO-B
Drawout
DCO-B
NonDrawout
DCO-B
Drawout
DCO-B
C4
C3
C2
C D4
C D3
C D2
CI 4
CI 3
CI 2
CID 4
CID 3
CID 2
C4
C3
C2
C D4
C D3
C D2
CI 4
CI 3
CI 2
CID 4
CID 3
CID 2
A
Hz
5
3
5
3
60Hz
5
3
5
3
5
3
5
3
60Hz
5
3
5
3
Tap
Range
(A)
4-12
3-9
2-6
4-12
3-9
2-6
4-12
3-9
2-6
4-12
3-9
2-6
4-12
3-9
2-6
4-12
3-9
2-6
4-12
3-9
2-6
4-12
3-9
2-6
IIT Unit
(A)
Burden
(VA)
20-80
20-80
20-80
20-80
20-80
20-80
10
8
12
10
8
12
10
8
12
10
8
12
10
7
12
10
7
12
10
7
12
10
7
12
IIT Unit
(A)
Burden
(VA)
20-80
20-80
20-80
20-80
20-80
20-80
5.0
7.0
4.0
5.0
7.0
4.0
5.0
7.0
4.0
5.0
7.0
4.0
20-80
20-80
20-80
20-80
20-80
20-80
Operating Burden
ICS
5.5
5.0
4.0
5.5
5.0
4.0
5.5
5.0
4.0
5.5
5.0
4.0
5.5
5.0
4.0
5.5
5.0
4.0
5.5
5.0
4.0
5.5
4.0
5.0
ICS+IIT
12
14
24
12
14
24
12
14
24
12
14
24
ICS Unit
(DC A)
Weight
(Kg)
1.0
3.0
0.5/2.0
0.1/1.0
4.0
1.0
3.0
0.5/2.0
0.1/1.0
4.0
1.0
3.0
0.5/2.0
0.1/1.0
4.0
1.0
3.0
0.5/2.0
0.1/1.0
4.0
ICS Unit
(DC A)
Weight
(Kg)
1.0
3.0
0.5/2.0
0.1/1.0
3.8
1.0
3.0
0.5/2.0
0.1/1.0
3.8
�DOC Type
Time
Characteristics
Very
Inverse
Rating
Type
Model No
NonDrawout
DOC-B
Drawout
DOC-B
NonDrawout
DOC-B
Drawout
DOC-B
*DOC-B : Very Inverse
C4
C3
C2
CD4
CD3
CD2
CI4
CI3
CI2
CID4
CID3
CID2
*2-6:2-2.5-3-3.5-4-5-6
A
Hz
5
3
5
3
5
3
5
3
60Hz
Tap
Range
(A)
4-12
3-9
2-6
4-12
3-9
2-6
4-12
3-9
2-6
4-12
3-9
2-6
*3-9:3-4-5-6-7-8-9
Operating Burden
ICS
2.8
2.0
1.8
2.8
2.0
1.8
2.8
2.0
1.8
2.8
2.0
1.8
ICS+IIT
9
12
14
9
12
14
*4-12:4-5-6-7-8-10-12
DEESYS TOTAL PRODUCTS GUIDE
189
Induction type Over Current Relay[OCR] 50/51
DCO-LA Type (Long time OCR)
For motor protection
Time
Characteristics
Inverse
Type
Model No
NonDrawout
DCO-LA
Drawout
DCO-LA
A
CI
CI
CI
CI
CI
CI
4
3
2
D4
D3
D2
Rating
Hz
5
3
60Hz
5
3
Tap
Range
(A)
4-12
3-9
2-6
4-12
3-9
2-6
IIT Unit
(A)
Burden
(VA)
20-80
20-80
20-80
20-80
20-80
20-80
4
5
6
4
5
6
Operating Burden
ICS
ICS+IIT
4.8
6.0
7.2
4.8
6.0
7.2
9
12
14
9
12
14
ICS Unit
(DC A)
Weight
(Kg)
1.0
3.0
0.5/2.0
0.1/1.0
4.0
*DCO-LA : Long Time Inverse
Specification
[JEC 2510 Application]
Item
Definitive element (ICS)
Instantaneous element (IIT)
Operating Value
below ±5% of each setting value
Resetting Value
on time Lever 10. over 90% of minimun current setting value
DCO-B
Operating time
very Inverse
OPERATING
TIME
DOC-B
TIME OVER CURRENT (SEC)
LEVER 300% 500% 1000%
#10
5.0
2.3
1.4
#7
3.5
1.6
0.98
#4
2.0
0.92
0.56
#10
4.0
1.6
0.76
#7
2.8
1.12
0.53
#4
1.6
0.64
0.3
below± 10% of each setting value
TIME ERROR (%)
300% 500% 1000%
±12
±7
±7
±10
±6
±6
±8
±5
±5
±12
±7
±7
±10
±6
±6
±8
±5
±5
over 10% of minimun current
setting value
below 40mS
in input 200%
inertia
current setting minimun time setting 1000% of tap #10 value operating time : over 80% of nominal
characteristics
operating time
temperature
below ±20% in -20℃ ~ +60℃ (operating time : measuring in 300 % of input current)
characteristics
overload
Two times during 0.25 second in twenty times (100A) of rated current
characteristics
(operating value and time : minimun tap)
Vibration
In case of two times of vibration to each direction 4 front and left. above and below) in frequeney
characteristics
16.7hz. with 0.4mm in condition of 80% value of minimun seifty operating current. all part of relay should be good
Impacting
characteristics
Insulation resistor
Dielectric voltage
In case of impacting two times 30g weight to allparts. all parts of relay should be good
over 10MΪ by DC 500V Megger in condition of all circuit to cubicle, contact to contact. and circuit to circuit
AC 2000 1 minute common frequency in condition of all circuit to case. circuit to circuit
AC 1000 1 minute common frequency in condition of contact to contact
Main Contact AC 220/10A
contact capacity
AC 110/15A
Contacting time : 0.5 sec
190
DEESYS TOTAL PRODUCTS GUIDE
Induction type Over Current Relay[OCR] 50/51
Time & Curve Characteristics
�Inverse
�Very inverse
DCO-A
DCO-B
For incoming
�Very inverse
�Instantaneous OperatingTime Characteristics (IIT)
DOC-B
DEESYS TOTAL PRODUCTS GUIDE
191
Induction type Over Current Relay[OCR] 50/51
Time & Curve characteristics
● Long time inverse(장반하시)
● How to setting the relay
�definitive current setting
The relay will be set about 150% current of contract
power according to the current transformer ratio
TAP
≒
X5
1
CT
X 1.5
TAP
= setting tap of relay
1
= current value of contract power
CT
= primary rating current of CT (secondary current is 5A)
순시전류정정
변압기의 도입여자전류로 오동작하지 않도록 변압기
용량에서 계산되는 전류치의 1,000~1,500%로 조정합니다.
TAP
≒
1
X5
CT
X 10~16
TAP
= 계전기의 정정탭
1
= 변압기의 용량(KVA)에 의해계산된 전류치
CT
= CT의 1차 정격전류 (2차 전류는 5A)
Error caculation for operating time of deffinitive element
tNError=
● TRIP부 전류 증가방법
계전기 동작(TRIP)시 ICS(동작표시기겸 보조접촉기)를 확실하게 동
작 시키기 위해 ICS 정격의 2~3배의 전류가 흐를수 있도록 차단용
AUX. RELAY 또는 52TC 의 임피던스를 적절히 조정할 필요가 있
습니다.
도 9-1과 같이 Coil과 병렬로 저항(R)을 접속하여 ICS에 흐르는 전
류를 조정합니다.
예) TC=1.5A DC110v의 경우 그림 9-1과 같이 Relay 2대가 동시
에 동작되는 사례도 발생됩니다. 따라서 저항 R값을 정격으로
사용하십시오.
110V
R=
=27.5�25Ϊ, 100W
2A×2
● How to increase current of trip coil(ICS)
On operating the relay(Trip), the impedance of Aux Relay or
52TC should be adjusted in order to operate the ICS
(operating target and Aux contact) according to conducting
more 2~3 times current than rated ICS current. As
diagranm 9-1, it can be adjusted the current of ICS with
connecting a resistor and the 52TC coil in parrallel circuit
Ex) In case of TC=1.5A, DC 110V, 2 sets of relay connecting
as diagram9-1. The value of resistor as following.
R=
192
110V
2A×2
=27.5�25Ϊ, 100W
DEESYS TOTAL PRODUCTS GUIDE
N
10
× t10
T10
×100(%)
T10 : Rating operating time
tN : measuring operating time of operating time lever(n)
N : Locating of operating time lever(tap)
● How to increase current of trip coil
Fig 9-1
Induction type Ground Over Current Relay[OCR] 50/51N
DCG/DOG type
DCG/DOG형 지락과전류 계전기는 소세력 유도원판형으로서 주로 변류기
의 잔류회로에 사용되며 지락 및 단락사고 보호용으로 사용된다.
DCG/DOG type ground over current relay is induction rotary disk
type that is operated in remained circuit current of current
transformer.
Specification
Time
Characteristics
Very
Inverse
Rating
Type
Model No
A
Hz
Tap
Range
(A)
IIT Unit
(A)
Burden
(VA)
Operating Burden
ICS
ICS+IIT
ICS Unit
(DC A)
Weight
(Kg)
12
2.5
20
1.0
3.0
12
2.5
20
0.5/2.0
0.1/1.0
4.0
NonDrawout
DCG-B
CI 5
Drawout
DCG-B
CI D5
NonDrawout
DOG-B
CI 5
6.5
1.6
7
1.0
3.0
Drawout
DOG-B
CI D5
6.5
1.6
7
0.5/2.0
0.1/1.0
4.0
*0.5-2.5:0.5-0.6-0.8-1.0-1.5-2.0-2.5
1
60
0.5/2.5
10-40
*10-40:10-20-30-40
Time & curve characteristics
�Very inverse(For distribution)
�Very inverse(For receiving)
DCG-B
DOG-B
DEESYS TOTAL PRODUCTS GUIDE
193
Induction type Ground Over Current Relay[OCR] 50/51N
Internal connection diagram(ICS current type)
�Drawout type
�Non drawout type
External connection diagram
(fig 13)
194
DEESYS TOTAL PRODUCTS GUIDE
Induction type Over, Under, Ground Voltage Relay[59] [27] [64]
DOV/DUV type
DOV, DUV형 전압계전기는 교류회로의 이상전압을 검출하여 송배전선과
기기의 손상을 방지하는 단상 유도 원판형 전압계전기입니다.
DOV, DUV type voltage relay is induction rotary disk type
and protects the power and distribution line & equipments
from abnormal voltage of AC circuit.
Features
1. JEC-174B규격에 적용 제작 되었습니다.
2. 주파수 및 주위 온도 변화에 따른 오차폭이 작습니다.
3. D형은 내부인출의 구조로 되어 있어 외부에서의 보수 및 시험이
가능합니다.
1. It is applied JEC-174B standard
2. According to variable frequency and temperature, the error
of relay is very little
3. D type relay is drawout type and it's maintanence and
testing is very easy in outside.
Specification
�OVR, OVGR
Item
Operating value
Resetting vlaue
Operating value
Self temperature
rising
characteristics
Temperature
characteristics
Overload withstand
Vibration
characteristics
Shock characteristics
Insulation
characteristics
Withstand voltage
Contact capacity
�UVR
DOV type over voltage relay(OVR, OVGR)
±5%of setting tap
above 90% of operating value in minimum tap (OVGR;80%)
Min voltage tap at lever #10
Input
120%
130%
150%
Operating time(SEC)
26.6 ± 20%
17.7 ± 18%
9.84 ± 15%
Refer to characteristics wave of tested operating time(Fig14)
At min tap Lever#1 The operating erro between
normal condition and self temperature
rising condition will be ±5% of setting tap value
1. operting value:Min TAP.Lever #1
-10℃, 50℃ Error ±10%
2. operating time:MinTAP, Lever #10
Input
120%
130%
150%
Operating time(SEC)
26.6 ± 30%
17.7 ± 37%
9.84 ± 32%
(Applied JEC174B)
DUV type under voltage relay(UVR)
±5% of setting tap
below 110% of operating value in maximum tap
Max. voltage tap at lever #10
Input
80%
0%
Operating time(SEC)
20.7 ± 20%
7.4 ± 18%
Refer to characteristics wave of tested operating time(Fig15)
The operating error will be ±5% of setting tap
value
1. operting value:Min TAP.Lever #1
-10℃, 50℃ Error ± 7%
2. operating time:MinTAP, Lever #10
Input
80%
0%
Operating time(SEC)
20.7 ± 30%
7.4 ± 15%
At min tap, 1.15 times 3 hours of rating voltage
In case of 10 minutes of vibration to each direction front and back, left and right, above and below
in frequency 16.7㎐ with 0.4㎜ in condition of min tap, lever #1 110% of DOV type relay setting values 90% of DUV
type relay should be good
In case of impacting 30g weight to all partsuf relay, all parts of relay should be good
All circuit to case : over 10㏁/500V Megger
circuit to circuit : over 10㏁/500V Megger
contact to contact : over 10㏁/500V Megger
All circuit to case : AC 2000V/1 minute
circuit to circuit : AC 1000V/1 minute
contact to contact : AC 1000V/1 minute
Main contact : AC 110V 5A
AC 110V 10A
ICS contact : AC 110V 10A
AC 110V 5A
DEESYS TOTAL PRODUCTS GUIDE
195
Induction type Over, Under, Ground Voltage Relay[59] [27] [64]
Over voltage relay(OVR)
Rating
Model No
NON-DRAWOUT
DOV
DRAWOUT
DOV
V
Hz
C1
110
C2
220
CD1
110
CD2
220
60
60
Tap Range
Burden
Operating Burden
(V)
(VA)
MIn(VA)
Max(VA)
110-115-120-125-130-140-150
2.0
1.6
1.6
220-230-240-250-260-280-300
2.0
1.6
1.6
110-115-120-125-130-140-150
2.0
1.6
1.6
220-230-240-250-260-280-300
2.0
1.6
1.6
ICS Unit
Weight
(DC A)
(㎏)
1.0
2.7
0.5/2.0
0.1/1.0
3.5
Under voltage relay(UVR)
Rating
Model No
V
NON-DRAWOUT
DOV
C16
110
C26
220
DRAWOUT
DOV
CD16
110
CD26
220
Hz
60
60
Tap Range
Burden
(V)
(VA)
MIn(VA)
Operating Burden
Max(VA)
60-65-70-75-80-85-90
6.0
1.6
1.6
160-165-170-175-180-185-190
4.0
1.6
1.6
ICS Unit
Weight
(DC A)
(㎏)
1.0
2.7
60-65-70-75-80-85-90
6.0
1.6
1.6
0.5/2.0
160-165-170-175-180-185-190
4.0
1.6
1.6
0.1/1.0
Tap Range
Burden
(V)
(VA)
MIn(VA)
Max(VA)
20-25-30-35-40-45-50
35
0.8
0.8
35-40-45-50-55-60-65
40
0.8
0.8
20-25-30-35-40-45-50
35
0.8
0.8
0.5/2.0
35-40-45-50-55-60-65
40
0.8
0.8
0.1/1.0
3.5
Over voltage ground relay(OVGR)
Rating
Model No
V
NON-DRAWOUT
DVG
C1
110
C9
190
DRAWOUT
DVG
CD1
110
CD9
190
Hz
60
60
Operating time characteristics curves
196
DEESYS TOTAL PRODUCTS GUIDE
Operating Burden
ICS Unit
Weight
(DC A)
(㎏)
1.0
2.7
3.5
Induction type Over, Under, Ground Voltage Relay[59] [27] [64]
Internal connection diagram
�Drawout type
�Non draw out type
External connection diagram
DEESYS TOTAL PRODUCTS GUIDE
197
Induction type Directional[Selective] Ground Relay [67]
DSG type
DSG형 방향지락 계전기는 비접지 계통의 고압배전 및 수전단의 지락
보호용으로 사용되며 보호구간내에 cable과 대지간 충전전류가 클 경
우(예:cable이 길때) 에 적용됩니다. 모선(Main)에서 나와있는 다수의
회선중 사고 회선만 선택 판별하여 차단시켜 정전사고 파급을 최소화
할수 있습니다.
※ 접지 변압기 (GPT:3’ry 190 or 110V)및 영상 변류기
※ (ZCT:200/1.5mA) 조합하여 사용하십시오.
본 catalog 191page 참고
※ 본 계전기는 고감도형으로 배전반의 진동과 충격에 의해 오동작
할 수 있습니다. 따라서 진동, 충격이 발생 할 수 있는 장소에서
는 DVG형 OVGR과 조합하여 사용하십시오.
DSG type directional ground relay will be used for ground
fault protection of high voltage distribution and receiving line
in non-grounding system.
In case of discharging much current between cable and
earth in portection area, this relay will be applied. This relay
will select the fault line among many feeder lines of main bus
and shut down the fault line. And then the fault will be
minimum
�Ground transformer (GPT 3ry 190V or 110V) and zero phase
current transformer(ZCT:200/1.5㎃)should be used for
coordination.
�This relay may be misoperated by vibration and impact of
switchgear because it is very precious.
�In condition of being used in place of happening vibration
and impact, it should be used with over of DVG type.
Specification
�SGR
Type
Model No
Drawout
DSG
Drawout
Non-
DSG
Rating
Zero Phase
Zero Phase
Voltage(V)
1’
ry current
CD 1
110
CD 9
190
C 1
110
C9
190
Operating Current
150㎃
200(㎃)
Burden
34
36
Voltage:190V, Current:200㎃
34
Phase angle:LEAD37。
36
ICS Unit
(DCA)
Weight
(Kg)
0.5/2.0
4.5
1.0
3.5
Phase angle characteristics
※ 유도형 SGR 계전기에 사용되는 ZCT는 반듯이 ZT
형을 사용하십시요.(영상변류기 200mA/1.5mA)
198
DEESYS TOTAL PRODUCTS GUIDE
Induction type Directional[Selective] Ground Relay [67]
Internal connection diagram (ICS current Type)
�Drawout type
�Non draw out type
Connection diagram
Connection diagram
DEESYS TOTAL PRODUCTS GUIDE
199
How to Drawout
Name of parts
How to drawout
A,B) release the cover handle of.
C) Take over the dwawout pin located in each side of case.
D) Take out drawout socket.
200
DEESYS TOTAL PRODUCTS GUIDE
E) take out the relay unit with drawout pin smoothly
F) The relay unit will be seperated from the case
※ for assembling the relay, please reverse the process
Dimension
Dimension
�Induction protective relay
Cutting Size : 154 x 184mm
DEESYS TOTAL PRODUCTS GUIDE
201
KS C 1303
JIs C 1102
Panel Board Meter
■Panel Board Meter
■Panel Board Factor Meter [cosφ
]
■Panel Board Meter [DIN Type]
■Panel Board Frequency Meter(Vo)
■Panel Board Ampermeter
■Panel Board Maximum Demend Meter
■Panel Board Voltmeter
■3Phase Square Type Selction Meter[A,V]
■Panel Board Wattmeter
■Digital Paner Board Meter
■Panel Board varmeter
판넬용
지지전기계기(각형, 광각형)
DEESYS TOTAL PRODUCTS GUIDE
203
KS C 1303
Panel Board Meter
Characteristics
● 주위환경에 대해 높은 신뢰성이 있습니다.
● 판넬에 취부가 용이하도록 설계하였습니다.
● 계기는 PIVOT 형으로 광각형은 80X80mm , 110x110mm, 각형은
80 x 80mm, 100x 84mm가 있습니다.
● 외부 자계의 영향을 받지 않습니다.
● 광각형 메타 전면 카바를 광각의 효율을 배가시키기 위하여 카바
돌출부를 특수하게 제작 명판 눈금 표시사항 및 지침 상태를 선명
하게 볼수 있도록 제작되었습니다.
● 계기의 외함 조립 부분을 볼트인써트화하여 기존계기보다 견고히
제작 장수명화 하였습니다.
● 단자에 보호커버를 설치하여 안전사고에 만전을 기했습니다.
� High reliability for surrounding environments
� Suitable designation to be installed on the panel.
� It in pivot type. and the size of wide angle type
is 80×80mm.
110×110mm and the size of square type is 80×80mm.
100×84mm
� No influence for magnetic force of outstanding.
� This meter in manufactured specially the front cover to
increase effect of the wide angle and if in very easy to
find out indicating and locating of the needle due to
manufacturing specially the top of cover
� As assembling the case with incerting some bolts. if in
longer life than the other meter
Ordering procedure
W : 광각형
(Wide Angle Type)
S : 각형
(Square type)
8:80mm×80mm
11:110mm×110mm
8:80mm×80mm
10:100mm×84mm
*7:72mm×72mm
*4:48mm×48mm
A: Ampere
V: Volt
W: Watt
P: Power Factor(cosφ
)
F: Frequency (Hz)
R: Reactive power (var)
*DIN SIZE
Double Scale 눈금경우 외측이 흑색 내측 눈금이 적색으로 표시됩니다.
204
DEESYS TOTAL PRODUCTS GUIDE
A: AC
D: DE
1: 1P 2W
2: 1P 3W
3: 3P 3W
4: 3P 4W
U: Unbalance
B: Balance
T: Transducer (INT type)
M: Meter Relay
Panel Board Meter
Type
division
equipment
Amperemeter &
Voltmeters
DC
W8/S8 Type
Model
Class
Model
W8-AD
1.0%
W11-AD
W8-VD
1.5%
W11-VD
2.5%
S4.7-AD,VD
Moving Coil type
S8-AD
S8-VD
Operating method
class
1.0 or 1.5%
S10-AD
Moving Coil Type
1.5%
S10-VD
W8-AA
Rectifier Type
W8-VA
Amperemeter &
Voltmeters
W11/S10 Type
Operating method
S8-AA
Moving lron Type
1.0%
W11-AA
1.5%
W11-AA
S4.7-AA
2.5%
S10-AA
Rectifier Type
1.0 or 1.5%
Moving Coil Type
1.5%
Rectifier Type
1.5%
S4-VA
S8-VA
Rectifier Type
2.5%
S7-VA
S10-VA
AC
W8-W
Watt Meters(W)
Transducer Type
S8-W
W8-R
Var Meters(var)
Power Factor
(cosφ
) Meters
Frequency
Meters
W8-F
W11-W
2.5%
S10-W
1.5%
W11-R
2.5%
S10-R
Transducer Type
S8-R
W8-P
1.0%,1.5%
S8-P
S8-F
Transducer Type
5.0%
Transducer Type
1.0%
1.5%
1.0%,1.5%
Transducer Type
W1-P
1.5%
3.0%,5.0%
Transducer Type
S10-P
W11-F
5.0%
Transducer Type
S10-F
※
1.0%,1.5%
Transducer Type
1.0%
EXT Transducer Type /
INT Transducer Type
Standard specification
Scale
Type
W8/S8 Type
Scale Length(㎜)
W11/S10 Type
122/68
176/80
Number of Division
24~52
Angle of Deflection
250。
/ 90。
meterial : Case/Cover
ABS Resin/Poly cabonate Resin
colour : Case
Munsell n1.5 (black), Munsell 7.5(blue-gray)
Name Plate
White
Position of Use
Vertical(⊥)
Standard Pointer
“W”Type Standard
Ambient Temperture
“S”
Type Standard
0℃~ 40℃
Full scale formats of“W”type
Full Scale
1
1.2
1.3
1.4
1.5
2
2.4
2.5
3
3.8
4
4.5
4.8
5
6
5.2
7.5
8
9
31.2
1.6
Divisions
50
24
26
28
30
40
48
50
30
38
40
45
48
50
30
52
37.5
40 45
31.2
32
※ Actural full scale in the value of 10n times of table value.
Full scale formats of“S”type
Full Scale
1
1.2
1.5
2
2.4
2.5
3
4
4.5
5
6
7
7.5
Divisions
20
24
30
20
24
25
30
20
22.5
25
30
35
37.5
※1
7.5
8
15
40
※2
8
16
※3
9
45
※ Actural full scale in the value of 10n times of table value.
※ Remark ※1.2 in applicated for S8 type
※ Remark ※3 is applicated only for type S10
� The standard scale of power factor meter (cos�)
� The standard scale of frequency meter(Hz) is indicated 45~55 and 55~66.
DEESYS TOTAL PRODUCTS GUIDE
205
Panel Board Meter[DIN type]
S7 type
S4 type
Specification
Type
Size
S4-AA
S4-VA
48X48mm
Rating
Freq(Hz)
AC 5A
50/60
Moving lron
1.5VA
0.15
AC 150,300V
50/60
Rectfier
0.7VA
0.15
S4-AD
DC50mV,1mA
S7-AA
AC 5A
50/60
Rectifier
AC150,300V
50/60
Rectifier
S7-VA
72X72mm
S7-AD
S7-F
-
Principle
Class
Moving Coil
1.5
Burden
Weight(Kg)
DC 1mA,50mA
0.15
1.5VA
0.22
0.7VA
0.18
DC50mV, 1mA
-
Moving Coil
DC 1mA, 50mV
0.18
45~70Hz
-
Transducer
2.0VA
0.3
※ 주문시 Hz 선택
특징
Features
1. Motor 회로에 사용시 기동전류를 감안하여 정격 전류치의
150~300%에 해당하는 초과눈금 계기를 사용하십시오.
2. 선로전압(측정대상 전압)이 300V를 초과 할시는 계기용 PT를 조합
하여 사용하십시오.
3. Panel 에 취부하기가 편리합니다.
■ S7형은“ㄷ”
형 Band를 이용 Nut로 조여 취부합니다.
■ S4형은 판 Spring (SUS)이 부착되어 있어 CUT부위에 밀어 넣
으면 간단히 취부됩니다.
Dimension
206
DEESYS TOTAL PRODUCTS GUIDE
1. Select the 150~330% over scale meter of rating current
due to starting current of motor if it is used in motor circuit.
2. Combine the P.T for meter if the voltage of circuit
(Measuring voltafe) is over 300V
3. It is very easy to install the meter on panel
■ In case of S7 type. it can be installed by ㄷ type band.
■ In case of S4 type. if can be installed easing by pushing
on the cut hole with plate spring (SUS)
Panel Board Ampere Meter
“W”type
“S”type
Specification
Type
W8-AA
W8-AD
W11-AA
W11-AD
S8-AA
S8-AD
S10-AA
S10-AD
Size
80X80mm
110X110mm
80X80mm
100X84mm
Rating
Freq(Hz)
VA
5A
50/60
1.5
50mV
-
50mV Drop
5A
50/60
1.5
50mV
-
50mV Drop
5A
50/60
1.5
50mV
-
50mV Drop
5A
50/60
1.5
50mV
-
50mV Drop
Class
Weight(Kg)
1.0 or 1.5
0.40
1.0 or 1.5
0.52
2.5
0.25
1.5
0.27
※ 주문시 Hz 선택
특징
Characteristics
●AC Amperemeter
1. 전류가 5A를 초과할 경우에는 정격 2차 전류가 5A(1A) 인 계기
용 변류기(C.T)를 조합하여 사용하십시오.
2. 회로전압이 500V를 초과하고 전류가 5A 이하인 회로의 경우에
도 확실한 절연을 위해 계기용 변류기를 조합하여 사용하십시오.
3. 전동기 사용시 전류계의 Full Scale를 Motor의 기동전류를 감안
하여 정격전류치의 150~500%에 해당하는 초과눈금 계기를 사
용하십시오. (초과 눈금의 오차는 ±10%입니다.)
●DC Amperemeter
1. 30A 이하인 전류에서는 자체 Meter에 분류기(Shunt)가 내장되
어 있어 필요없으나 30A 이상의 전류에서는 외부에
Shunt(50mV)를 연결하여 사용하십시오.
2. Shunt 결선시 마이너스(-)측에 설치하십시오.
■ AC Amperemeter
1. Combine C.T of rating 2ry current 5A(1A) for meter if
current of case it in over 5A
2. Combine P.T & C.T for meter in order to insulate the
circuit if voltage of circuit over 500V and current of
circuit is below 5A.
3. Select 150~500% over scale meter of rating current
due to starting current of motor if it in for motor circuit.
■ DC Amperemeter
1. In case of below 30A current. the shunt installed in the
meter. But in case of over 30A current. the shunt in not
installed in the meter. please connect the shunt (50mA)
outside.
2. When you connect the shunt. connect the shunt on the
minus side.
External connection diagram
■ AC Ammeter
■ DC Ammeter
DEESYS TOTAL PRODUCTS GUIDE
207
Panel Board Volt Meter
“W”type
“S”type
Specification
Type
W8-VA
W8-VD
W11-VA
W11-VD
S8-VA
S8-VD
S10-VA
S10-VD
Size
80X80mm
110X110mm
80X80mm
100X84mm
Rating
Freq(Hz)
VA
150, 300V
50/60
0.5
150, 300V
-
1KΩ/V
150, 300V
50/60
0.5
150, 300V
-
1KΩ/V
150, 300V
50/60
5.0(0.5)
150, 300V
-
1KΩ/V
150, 300V
50/60
5.0(0.5)
150, 300V
-
1KΩ/V
※ VA: AC, VD: DC, W:Wide Angle Types, S: Square Type
※ The value of ( ) in for rectifier type
Class
Weight(Kg)
1.0 or 1.5
0.33
1.0 or 1.5
0.45
2.5
0.18
1.5
0.20
※ 주문시 Hz 선택
Characteristics
●AC Voltmeter
1. 입력전압이 AC 300V이상의 회로에는 150V전압계를 P.T와 조
합하여 사용하십시오.(600V 전압계는 주문에 의함)
예) meter scale 0~9.000V. Input range 0~150V
P.T ratio 6.600/110V
■ AC Meter
1. Combine P.T with 150V meter if input voltage in over
AC 300V circuit.
EX) meter scale 0~9000V. input range 0~150V
P.T ratio 6.600/110V
●DC Voltmeter
1. 입력전압이 DC 750V 이상의 경우에는 외부 배율기를 부착 사용
하십시오.
2. 배율기는 (+)측에 결선 하십시오.
3. DC Voltmeter의 전류감도는 1mA(1KΩ/V)입니다.
■ DC Meter
1. Connect the multiplier outside in case of over DC 750V
of input voltage.
2. Connect the multiplier on pluse side.
3. The current sensitivity of DC voltmeter in 1mA (1KΪ/V)
Ex) Choose of Meter
ex1) 3P 3W (In case of 6.6KV line)
full scale value (V):9KV
P.T ratio:6.6KV/110V
9KV
MAX. input range=
=150V
6.6KV/110V
ex) 3P 4W (In case of 22.9KV line)
full scale value (V):31.2KV
P.T ratio:22.9KV/110V
31.2KV
MAX. input range=
=150V
22.9KV/110V
External connection diagram
■ DC Voltmeter
208
DEESYS TOTAL PRODUCTS GUIDE
■ AC Voltmeter
Panel Board Watt Meter
“W”type
“S”type
Specification
Type
Size
Circuit
W8-W2
(wide angle)
W8-W3
80×80㎜
W8-W1
Rated
VA
Remark
Weight
Hz
Class
-
60
1.5
0.65
-
60
1.5
0.75
EXT.
T/D
V
A
V
A
V
A
1P2W
110,220
5
0.5
0.5
-
1P3W
110
5
0.5
0.5
-
(㎏)
REF
3P3W
110,220
5
0.5
0.5
B
U
60
1.5
0.75
3P4W
190/ √
3, 380/ √
3
5
0.5
0.5
B
U
60
1.5
0.85
W8-W4U
3P4W
190/ √
3, 380/ √
3
5
0.5
0.5
U
U
60
1.5
0.90
W11-W1
1P2W
110,220
5
0.5
0.5
-
-
60
1.5
0.70
W11-W2
1P3W
110
5
0.5
0.5
-
-
60
1.5
0.85
EXT.
W11-W3
3P3W
110, 220
5
0.5
0.5
B
U
60
1.5
0.85
T/D
W8-W4
W11-W4
(wide angle)
3P4W
190/ √
3, 380/ √
3
5
0.5
0.5
B
U
60
1.5
0.95
W11-W4U
110×110㎜
3P4W
190/ √
3, 380/ √
3
5
0.5
0.5
U
U
60
1.5
1.00
W11-W1T
1P2W
110, 220
5
0.5
0.5
-
-
60
1.5
0.60
W11-W2T
1P3W
110
5
0.5
0.5
-
-
60
1.5
0.85
INT.
W11-W3T
3P3W
110, 220
5
0.5
0.5
B
U
60
1.5
0.85
T/D
W11-W4T
3P4W
190/ √
3, 380/ √
3
5
0.5
0.5
B
U
60
1.5
0.90
W11-W4UT
3P4W
190/ √
3, 380/ √
3
5
0.5
0.5
U
U
60
1.5
0.90
S8-W1
1P2W
110,220
5
0.5
0.5
-
-
60
1.5
0.55
S8-W2
(Square type)
1P3W
110
5
0.5
0.5
-
-
60
1.5
0.65
EXT.
S8-W3
80×80㎜
3P3W
110,220
5
0.5
0.5
B
U
60
1.5
0.65
T/D
S8-W4
3P4W
190/ √
3, 380/ √
3
5
0.5
0.5
B
U
60
1.5
0.75
S8-W4U
3P4W
190/ √
3, 380/ √
3
5
0.5
0.5
U
U
60
1.5
0.85
S10-W1
1P2W
110,220
5
0.5
0.5
-
-
60
1.5
0.57
S10-W2
(Square type)
1P3W
110
5
0.5
0.5
-
-
60
1.5
0.67
EXT.
S10-W3
100×84㎜
T/D
3P3W
110, 220
5
0.5
0.5
B
U
60
1.5
0.67
S10-W4
3P4W
190/ √
3, 380/ √
3
5
0.5
0.5
B
U
60
1.5
0.77
S10-W4U
3P4W
190/ √
3, 380/ √
3
5
0.5
0.5
U
U
60
1.5
0.87
※U:Unbalance, T:Int. Transduce, W:Watt.
※EXT.T/D:Installation the Transducer outside, INT.T/D:Installation the transducer inside
※The specification of rating current 1A is based on ordering
� EXT. Watt meter
※ 주문시 Hz 선택
�EXT. T/D
DEESYS TOTAL PRODUCTS GUIDE
209
Panel Board Watt Meter
Standard full scale table(Watt meters)
Phase Wire
1P2W
1P3W
P.T.ratio(V)
110
110
220
380
/110
440
/110
3300
/110
6600
/110
22000
/110
22900
/110
0.6㎾
1.0㎾
2.0㎾
1.158㎾
1.0㎾
1.0㎾
1.0㎾
1.0㎾
0.961㎾
1.0㎾
2.0㎾
2.0㎾
4.0㎾
1.666㎾
1.666㎾
0.6
1
2
4
4
30
60
200
200
1400
2
4
4
100
200
C.T.ratio
Calibrating
watts
5/5
3P3W
3P4W
154㎾ 208/ 3 380/√
√ /190/√33
/110
380 11400/ √
3 22900/ √
3
/√
3 /190/√
3
/190/√
3
10/5
1.2
2
4
8
8
60
120
400
400
2800
4
8
8
200
400
15/5
1.8
3
6
12
12
90
180
600
600
4200
6
12
12
300
600
20/5
2.4
4
8
16
16
120
240
800
800
5600
8
16
16
400
800
25/5
3.0
5
10
20
20
150
300
1000
1000
7000
10
20
20
500
1000
30/5
3.6
6
12
24
24
180
360
1200
1200
8400
12
24
24
600
1200
40/5
4.8
8
16
32
32
240
480
1600
1600
11.2㎿
16
32
32
800
1600
50/5
6.0
10
20
40
40
300
600
2000
2000
14.0
20
40
40
1000
2000
60/5
7.2
12
24
48
48
360
720
2400
2400
16.8
24
48
48
1200
2400
3000
75/5
9.0
15
30
60
60
450
900
3000
3000
21.0
30
60
60
1500
80/5
9.6
16
32
64
64
480
960
3200
3200
2204
32
64
64
1600
3200
100/5
12.0
20
40
80
80
600
1200
4000
4000
28.0
40
80
80
2000
4000
120/5
14.4
24
48
96
96
720
1440
4800
4800
33.6
48
95
95
2400
4800
150/5
18.0
30
60
120
120
900
1800
6000
6000
42.0
60
120
120
3000
6000
200/5
24.0
40
80
160
160
1200
2400
8000
8000
56.0
80
160
160
4000
8000
250/5
30.0
50
100
200
200
1500
3000
10㎿
10㎿
70.0
100
200
200
5000
10㎿
300/5
36.0
60
120
240
240
1800
3600
12
12
84.0
120
240
240
6000
12
400/5
48.0
80
160
320
320
2400
4800
16
16
112.0
160
320
320
8000
16
500/5
60.0
100
200
400
400
3000
6000
20
20
140
200
400
400
10㎿
20
600/5
72.0
120
240
480
480
3600
7200
24
24
168
240
480
480
12
24
750/5
90.0
150
300
600
600
4500
9000
30
30
210
300
600
600
15
30
800/5
96.0
160
320
640
640
4800
9600
32
32
224
320
640
640
16
32
1000/5
120.0
200
400
800
800
6000
12㎿
40
40
280
400
800
800
20
40
1200/5
144.0
240
480
960
960
7200
14.4
48
48
336
480
960
960
24
48
1500/5
180.0
300
600
1200
1200
9000
18.0
60
600
420
600
1200
1200
30
60
2000/5
240.0
400
800
1600
1600
12㎿
24.0
80
80
560
800
1600
1600
40
80
2500/5
300.0
500
1000
2000
2000
15
30.0
100
100
700
1000
2000
2000
50
100
Characteristics
1. 정격을 초과하여 사용할 시에는 AC 110V, 5A 의 정격을 초과하여
사용시 PT, CT는 조합하여 사용하십시오.
2. 동작전압범위는 정격전압의 ±10% 이내입니다.
3. 최대 눈금은 위의 Standard Full Scale Table을 참조하여 사용하
십시오.
4. Watt Meter Transducer는 내부(INT.) 또는 외부(EXT.)형 2종류가
있습니다.
/√
3 )으로 표시합니다.
5. 3상 4선의 경우 상전압 (Vι
MAX. scale value
6. 교 정 전 력 =
PT ratio × CT ratio
ex) 3P 3W
full scale wattmeter : 600KW
P.T ratio : 3300V/110V
210
600KW
(3300/110)X(100/5)
DEESYS TOTAL PRODUCTS GUIDE
ex1) 3P 4W
full scale wattmeter : 2000KW
P.T ratio : 22900V
√
3
C.T ratio : 100A/5A
calibrating watts =
1. Combine AC 110V P.T & AC 5A CT in case of over rating
value.
2. Allowance of operating voltage is ± 10% of rating voltage.
3. For max scale. refer to the above Standard Full Scale
Table.
4. Watt Meter Transducer is internal type and external type.
5. In case of 3�4W voltage in phase voltage(Vι/ √
3)
MAX. scale value
6. Calibrating Watt =
PT ratio × CT ratio
= 1.0KW
190V
√
3
C.T ratio : 50A/5A
2000KW
calibrating watts =
22900V
190V
(
√
3
=
)
√
3
= 1.666KW
X (50/5A)
Panel Board Var Meter
“W”type
“S”type
Specification
Type
Size
Circuit
Rated
V
VA
A
V
Remark
A
V
A
Hz
Class
Weight
(㎏)
REF
W8-R1
1P2W
110,220
5
0.5
0.5
-
-
60
1.0/1.5
0.65
W8-R2
1P3W
110
5
0.5
0.5
-
-
60
1.0/1.5
0.75
EXT.
T/D
W8-R3
80×80㎜
W8-R4
3P3W
110,220
5
0.5
0.5
B
U
60
1.0/1.5
0.75
3P4W
190/ √
3,380/ √
3
5
0.5
0.5
B
U
60
1.0/1.5
0.85
W8-R4U
3P4W
190/ √
3,380/ √
3
5
0.5
0.5
U
U
60
1.0/1.5
0.90
W11-R1
1P2W
110,220
5
0.5
0.5
-
-
60
1.0/1.5
0.70
W11-R2
1P3W
110
5
0.5
0.5
-
-
60
1.0/1.5
0.85
EXT.
W11-R3
3P3W
110,220
5
0.5
0.5
B
U
60
1.0/1.5
0.85
T/D
W11-R4
3P4W
190/ √
3,380/ √
3
5
0.5
0.5
B
U
60
1.0/1.5
0.95
3P4W
190/ √
3,380/ √
3
5
0.5
0.5
U
U
60
1.0/1.5
1.00
W11-R1T
1P2W
110,220
5
0.5
0.5
-
-
60
1.0/1.5
0.60
W11-R2T
1P3W
110
5
0.5
0.5
-
-
60
1.0/1.5
0.85
INT.
W11-R3T
3P3W
110,220
5
0.5
0.5
B
U
60
1.0/1.5
0.85
T/D
W11-R4T
3P4W
190/ √
3,380/ √
3
5
0.5
0.5
B
U
60
1.0/1.5
0.90
W11-R4UT
3P4W
190/ √
3,380/ √
3
5
0.5
0.5
U
U
60
1.5
0.90
S8-R1
1P2W
110,220
5
0.5
0.5
-
-
60
2.5
0.55
S8-R2
1P3W
110
5
0.5
0.5
-
-
60
2.5
0.65
EXT.
3P3W
110,220
5
0.5
0.5
B
U
60
2.5
0.65
T/D
S8-R4
3P4W
190/ √
3,380/ √
3
5
0.5
0.5
B
U
60
2.5
0.75
S8-R4U
3P4W
190/ √
3,380/ √
3
5
0.5
0.5
U
U
60
2.5
0.85
S10-R1
1P2W
110,220
5
0.5
0.5
-
-
60
1.5
0.57
S10-R2
1P3W
110
5
0.5
0.5
-
-
60
1.5
0.67
EXT.
T/D
W11-R4U
S8-R3
110×110㎜
80×80㎜
S10-R3
3P3W
110,220
5
0.5
0.5
B
U
60
1.5
0.67
S10-R4
100×84㎜
3P4W
190/ √
3,380/ √
3
5
0.5
0.5
B
U
60
1.5
0.77
S10-R4U
3P4W
190/ √
3,380/ √
3
5
0.5
0.5
U
U
60
1.5
0.87
※ U: Unbalance, T: Int.Transducer, R: VAR ※EXT.T/D: 트랜스듀서 외부설치용, INT.T/D: 트랜스듀서 내장형
※ The specification of rating current 1A is based on ordering
※ 주문시 Hz선택
example scale
※The standard scale in lag scale
※set the var meter to lead in left side and to lag in right side from point if the var meter in used for the power factor
DEESYS TOTAL PRODUCTS GUIDE
211
Panel Board Var Meter
Standard full scale table(1/2 var meters)
Phase Wire
1P2W
1P3W
P.T.ratio(V)
110
110
Calibrating
watts
3P 4W
220
380
/110
440
/110
3300
/110
6600
/110
22000
/110
22900
/110
0.5Kvar 1.0Kvar
0.5Kvar 0.48Kvar
154㎸ 208//√
3 380/√
3
/110
/190/√
3
380 11400/√
3 22900/ √
3
/√
3 /190/√
3
/190/ √
3
0.579Kvar
0.5Kvar
0.5Kvar
0.5Kvar
0.5Kvar
1.0Kvar
1.0Kvar
2.0Kvar
0.833Kvar
5/5
0.3
0.5
1
2
2
15
30
100
100
700
1
2
2
20
100
10/5
0.6
1
2
4
4
30
60
200
200
1400
2
4
4
100
200
C.T.ratio
0.3Kvar
3P 3W
0.833Kvar
15/5
0.9
1.5
3
6
6
45
90
300
300
2100
3
6
6
150
300
20/5
1.2
2
4
8
8
60
120
400
400
2800
4
8
8
200
400
25/5
1.5
2.5
5
10
10
75
150
500
500
3500
5
10
10
250
500
30/5
1.8
3
6
12
12
90
180
600
600
4200
6
12
12
300
600
40/5
2.4
4
8
16
16
120
240
800
800
5600
8
16
16
400
800
50/5
3.0
5
10
20
20
150
300
1000
1000
7000
10
20
20
500
1000
60/5
3.6
6
12
24
24
180
360
1200
1200
8000
12
24
24
600
1200
75/5
4.5
7.5
15
30
30
225
450
1500
1500
105Mvar
15
30
30
750
1500
80/5
4.8
8
16
32
32
240
480
1600
1600
11.2
16
32
32
800
1600
100/5
6.0
10
20
40
40
300
600
2000
2000
14.0
20
40
40
1000
2000
120/5
7.2
12
24
48
48
360
720
2400
2400
16.3
24
48
48
1200
2400
150/5
9.0
15
30
60
60
450
900
3000
3000
21.0
30
60
60
1500
3000
200/5
12.0
20
40
80
80
600
1200
4000
4000
28.0
40
80
80
2000
4000
250/5
15.0
25
50
100
100
750
1500
5000
5000
35.0
50
100
100
2500
5000
300/5
18.0
30
60
120
120
900
1800
6000
6000
42.0
60
120
120
3000
6000
400/5
24.0
40
80
160
160
1200
2400
8000
8000
56.0
80
160
160
4000
8000
10Mvar
500/5
30.0
50
100
200
200
1500
3000
10Mvar
10Mvar
70
100
200
200
5000
600/5
36.0
60
120
240
240
1800
3600
12
12
84
120
240
240
6000
12
750/5
45.0
75
150
300
300
2250
4500
15
15
105
150
300
300
7500
15
800/5
48.0
80
160
320
320
2400
4800
16
16
112
160
320
320
8000
16
1000/5
60.0
100
200
800
800
3000
6000
20
20
140
200
400
400
10Mvar
20
1200/5
72.0
120
240
480
480
3600
7200
24
24
168
240
480
480
12
24
1500/5
90.0
150
300
600
600
4500
9000
30
30
210
400
600
600
150
30
2000/5
120.0
200
400
800
800
6000
12Mvar
40
40
280
400
800
800
20
40
2500/5
150.0
250
500
1000
1000
7500
15
50
50
350
500
1000
1000
25
50
Characteristics
1. 정격을 초과하여 사용할 시에는 AC 110V, 5A의 PT, CT를 조합하
여 사용하십시오.
2. 동작전압범위는 정격전압의 ± 10% 이내입니다.
3. 최대 눈금은 위의 Standard Full scale Table 을 참조하여 사용하
십시오.
4. Var meter Transducer는 내부(INT.) 또는 외부(EXT.)형 2종류가
있습니다.
5. 3상 4선의 경우 상전압( √
3 )으로 표시합니다.
6. 최대 눈금은 전부하용량의 1/2, 1/3, 1/4 로 선택하여 사용하십시오.
MAX. scale value
6. 교 정 전 력 =
PT ratio × CT ratio
ex) 3P 3W
full scale varmeter : 300KVar
P.T ratio : 3300V/110V
C.T ratio : 100A/5A
calibrating Var =
212
300KVar
(3300/110)X(100/5)
DEESYS TOTAL PRODUCTS GUIDE
= 0.5KVar
1. Combine AC 110V P,T & AC 5A C.T in case of over rating
value.
2. Allowance of operating voltage is ± 10% of rating voltage.
3. For max scale. refer to the above standard full scale table.
4. Var meter Transducer is internal type and external type.
5. In case of 3�4W. the voltage in phase voltage (Vι/√
3 )
6. Select 1/2 or 1/3 or 1/4 value of total load capacity for max
scale.
MAX. scale value
7. Calibrating Watt =
PT ratio × CT ratio
ex1) 3P 4W
full scale Var meter : 1000KVar
190V
P.T ratio : 22900V
√
√
3
3
C.T ratio : 50A/5A
1000KVar
calibrating Var =
22900V
190V
( √
) X (50/5A)
√
3
3
= 0.833KVar
Watt Meter, Var Meter
External connection diagram
�EXT. T/D type
�INT. T/D type
DEESYS TOTAL PRODUCTS GUIDE
213
Panel Board Power Factor Meter [COS ]
“W”type
“S”type
Specification
Type
Size
Circuit
Rated
VA
V
A
V
A
Remark
Hz
Class
Weight
(㎏)
0.65
REF
W8-P1
1P2W
110,220
5
0.5
0.5
-
50/60
3.0/5.0
W8-P2
1P3W
110
5
0.5
0.5
-
50/60
3.0/5.0
0.75
W8-P3B
3P3W
110,220
5
0.5
0.5
B
50/60
3.0/5.0
0.75
EXT.
T/D
W8-P3U
80×80㎜
3P3W
110,220
5
0.5
0.5
U
50/60
3.0/5.0
0.85
3P4W
190/ 3,380/ 3
5
0.5
0.5
B
50/60
3.0/5.0
0.90
W8-P4U
3P4W
190/√
3,380/ √
3
5
0.5
0.5
U
50/60
3.0/5.0
0.90
W11-P1
1P2W
110,220
5
0.5
0.5
-
50/60
3.0/5.0
0.70
W11-P2
1P3W
110
5
0.5
0.5
-
50/60
3.0/5.0
0.85
W11-P3B
3P3W
110,220
5
0.5
0.5
B
50/60
3.0/5.0
0.85
EXT.
W11-P3U
3P3W
110,220
5
0.5
0.5
U
50/60
3.0/5.0
0.95
T/D
W11-P4B
3P4W
190/√
3,380/ √
3
5
0.5
0.5
B
50/60
3.0/5.0
1.00
W8-P4B
3P4W
190/√
3,380/ √
3
5
0.5
0.5
U
50/60
3.0/5.0
1.00
W11-P1T
1P2W
110,220
5
0.5
0.5
-
50/60
3.0/5.0
0.60
W11-P2T
1P3W
110
5
0.5
0.5
-
50/60
3.0/5.0
0.85
W11-P3BT
3P3W
110,220
5
0.5
0.5
B
50/60
3.0/5.0
0.85
INT.
W11-P3UT
3P3W
110,220
5
0.5
0.5
U
50/60
3.0/5.0
0.90
T/D
W11-P4BT
3P4W
190/√
3,380/ √
3
5
0.5
0.5
B
50/60
5.0
0.90
W11-P4UT
3P4W
190/√
3,380/ √
3
5
0.5
0.5
U
50/60
5.0
0.90
S8-P1
1P2W
110,220
5
0.5
0.5
-
50/60
5.0
0.55
0.65
W11-P4U
110×110㎜
S8-P2
1P3W
110
5
0.5
0.5
-
50/60
5.0
3P3W
110,220
5
0.5
0.5
B
50/60
5.0
0.75
EXT.
S8-P3U
3P3W
110,220
5
0.5
0.5
U
50/60
5.0
0.85
T/D
S8-P4B
3P4W
190/√
3,380/ √
3
5
0.5
0.5
B
50/60
5.0
0.85
S8-P4U
3P4W
190/√
3,380/ √
3
5
0.5
0.5
U
50/60
5.0
0.57
S10-P1
1P2W
110,220
5
0.5
0.5
-
50/60
5.0
0.67
S8-P3B
80×80㎜
S10-P2
S10-P3B
100×84㎜
1P3W
110
5
0.5
0.5
-
50/60
5.0
0.67
3P3W
110,220
5
0.5
0.5
B
50/60
5.0
0.77
EXT.
T/D
S10-P3U
3P3W
110,220
5
0.5
0.5
U
50/60
5.0
0.87
S10-P4B
3P4W
190/√
3,380/ √
3
5
0.5
0.5
B
50/60
5.0
0.87
S10-P4U
3P4W
190/√
3,380/ √
3
5
0.5
0.5
U
50/60
5.0
0.87
※ U:Unbalance, T:Int. Transduce, P:Power Factor.
※ EXT.T/D:External Transducer, INT.T/D:Internal Transducer
※ Order made is rating current 1A of meter
※ 주문시 Hz 선택
214
DEESYS TOTAL PRODUCTS GUIDE
Panel Board Power Factor Meter[COS ]
Feature
1. 정격을 초과하여 사용할 시에는 AC 110V, 5A의 PT, CT를 조합하
여 사용하십시오.
2. 동작전압범위는 정격전압의 ±10%이내입니다.
3. Power Factor meter, Transducer는 내부(INT.) 외부 (EXT.) 형
2종류가 있고 Balance형과 Unblance형으로 구분합니다.
4. 3상 4선의 경우 상전압(Vι
/√
3 )으로 표시합니다.
5. 2차 정격전류 5A의 10%인 소부하의 경우는 역률의 정상지시를 기
대할수 없으며 정격전류의 1/3 이상이 되어야 정확한 오차가 보증
됩니다.
6. 역률계의 Standard scale의 LEAD 0.5~1.0 ~ 0.5 LAG입니다.
1. Combine AC 110V. PT & AC 5A C.T in case of over rating
value
2. Allowance of operating voltage is ± 10% of rating voltage.
3. Power Factor meter. Transducer can be classified 2type
(internal and external) and it can be classified 2 type
(Balance and unbalance)
4. In case of 3�4W, voltage is phase voltage (Vι
/√
3)
5. On over 1/3 value of rating current. it is certified the error
correctly because it is not expected normal indication of
power factor in case of 10% load of rating 2ry current 5A.
6. The standard scale of power factor meter is Lead
0.5~1.0~0.5 lag
External connection diagram
�EXT. T/D type
�INT. T/D type
DEESYS TOTAL PRODUCTS GUIDE
215
Panel Board Frequency Meter
“W”type
“S”type
Specification
Type
Size
Rated Voltage (V)
VA
Class
Weight(Kg)
1.0
0.33
110.220
2.0
1.0
0.45
W8-F
80X80mm
W11-F
110X110mm
S8-F
80X80mm
1.0
0.10
S10-F
100X84mm
1.0
0.20
※F : Frequency
Characteristics
1. 주파수의 Standard full scale은 45Hz~55Hz, 55Hz~65Hz 2종
류가 있습니다.
2. 정격전압을 초과할 경우는 외부 P.T를 조합하여 사용하십시오.
3. 동작전압의 범위는 AC 110V: 80~120V, AC220V: 160~240V입
니다.
4. 주파수 METER의 Pointer는 Needle type입니다.
External connection diagram
216
DEESYS TOTAL PRODUCTS GUIDE
1. Standard full scale of frequency meter in 2 types :
45HZ~55HZ and 55HZ~65HZ
2. Combine P.T in outside in case of over the rating voltage.
3. Allowance of operating voltage in 80~120V for AC 110V
and 160~240V for AC 220V
4. Pointer of power factor meter in needle type.
Panel Board Maximum Demand Meter [V0]
특징
이 Vo 메타는 기계식과 전자식을 겸한 영상전압지시계이며, 현재의
값은 기계식 아나로그 값으로 지시합니다. Vo 값이 변동할 때 마다
Peak를 EEPROM에 기억 하게하고 그 값은 메터 밑 부분에 있는 3
digital FND Display에 나타납니다. 본 전자형은 관성에 의한 오차가
없으므로 보다 정확히 그 Peak치를 확인할 수 있습니다.
Feature
The Vo meter is a electronic type for demand Vo. which is
displayed by 3 digit FND window on the lower part of the
meter with mechanical type indicatior for real time Vo value.
Comparing with mechanical type. the Electronic Vo meter no
slip error against inertia moment of indicating needle set.
Application
적용
이 Vo메타는 1선 지락시 접지 전류량이 작아 전류요소로 접지 상태를
파악 할 수 없는 장소에 전원측 PT의 2차측을 Open-Delta 결선하여
이 메타에 연결, 사용합니다.
사용법
The Vo meter is application for detecting zero sequence
voltage on the distribution line which has small ground
current. As soon as one phase is grounded by fault. zero
phase sequence voltage is generated, For the purpose, the
meter would be connected with Open-Delta circuit of 3 phase
PT secondary.
Description
1. 아래의 결선도에서와 같이 결선합니다.
2. 외장형 재충전용 밧데리를 메터에 연결합니다.
3. 3상 전원을 살립니다.
4. 선로에 영상 전압이 발생하면 광각형 지시계기에 현재의 영상 전압
을 지시합니다. 이 값은 현재의 값이므로 선로의 상태 변경에 따라
변합니다.
5. 영상 전압의 크기가 최대값이 되면 그 값은 3digit Display에 나타
나며 EPROM에 저장 됩니다. 최대값이 되면 갱신 될 때 마다
Display 값은 상향 지시 합니다.
6. 표시된 최대치는 Display 오른 쪽에 있는 Reset Button 을 누르면
영구히 지워 집니다.
7. 영상전압이 10V 미만에서는 최대치를 표시하지 않습니다.
1. To connect a meter as shown below
2. To connect the meter with external rechargeable battery
3. To enerzise source PT
4. The wide range analog indicator will indicate real time Vo
voltage. If any on the line. The indicating value will move
according to real time line situation,
5. The demand value on the Display with 3 digit FND located
lower part of the front plate of the meter, is shown a fixed
peak vaule. The value is stored in a EEPROM in the meter.
Whenever new peak vaule is generated, the vaule is
renewed instead of the old data.
6. The Display is errassed by pressing reset button on the
right side of the Display.
7. Demand display is designed to be indicated to be
indicated for higher than 10Volt.
사양
Item
Model
Rating
(AC)
Full Scall
Accuracy
(%)
Aux.Power
(AC)
Freq.
(Hz)
Burden
(VA)
Weight
(Kg)
Vo Meter
W11 DVA
110/190
150/259
1.5 at FS
110V/190V
60
0.5
1.0
External connection diagram
Dimension for External Power supply Box
Dimension for Meter
DEESYS TOTAL PRODUCTS GUIDE
217
Panel Board Maximum Demand Meter [A0]
특징
이 Ao메타는 기계식과 전자식을 겸한 영상전류지시계이며, 현재의 값
은 기계식 아나로그 값으로 지시합니다. Ao값이 변동할 때마다 Peak
치를 EEPROM에 기억 하게하고 그 값은 메터 밑 부분에 있는 3 digit
FND Display에 나타납니다. 이 전자형은 관성에 의한 오차가 없으므
로 보다 정확히 그 Peak치를 확인할 수 있습니다.
Feature
The Ao meter is a electronic type for demand Ao. which is
displayed by 3digit FND window on the lower part of the
meter with mechanical type indicatior for real time Ao value.
Comparing with mechanical type, the Electronic Ao meter no
slip error against inertia moment of indicating needle set.
Application
적용
이 Io메타는 계통사고 또는 비정상시 발생하는 영상전류를 측정하는
메타로, 직접 접지 또는 저항접지 계통에 적용하며 ZCT 또는 3 CT의
중성선에 연결하여 사용합니다.
사용법
The lo meter is applied for detecting zero sequence current
on the distribution live which is ground solidly or with
resistance. As soon as one phase is grounded by fault. zero
phase sequence current is generated. For the purpose. the
meter would be connected with a ZCT or neutral line of 3 CT
connection.
Description
1. 아래의 결선도에서와 같이 결선 합니다.
2. 외장형 재충전용 밧데리를 메터에 연결합니다.
3. 3상 전원을 투입시킵니다.
4. 선로에 영상 전류가 발생하면 광각형 지시계기에 현재의 영상 전류
를 지시합니다. 이 값은 현재의 값이므로 선로의 상태 변화에 따라
항상 변합니다.
5. 영상 전류의 크기가 최대값이 되면 그 값은 3 Digit Display에 타
나나며 EEPROM에 저장 됩니다. 최대값이 되면 갱신 될 때 마다
Display 값은 갱신된 값을 지시합니다.
6. 표시된 최대치는 Display 오른쪽에 있는 Reset Button을 누르면
영구히 지워집니다.
1. To connect a meter as shown below.
2. To Connect the meter with external rechargeable battery
3. To be flow unbalanced current at the relay terminal as the
below diagram.
4. The wide range analog indicator will indicate real time lo
current. The indicating value will move according to real
time unbalanced line current.
5. The demand value on the Display with 3 digit FND located
lower part of the front plate of the meter, is shown a fixed
peak value. The value is stored in a EEPROM in the meter.
Whenever new peak value is generated. the value is
renewed instead of the old data.
6. The Display is errassed by pressing reset button on the
right side of the Display.
사양
Item
Model
Rating
(A)
Full Scall
(A)
Accuracy
(%)
Aux.Power
(AC)
Freq.
(Hz)
Burden
(VA)
Weight
(Kg)
Ao Meter
W11 DAA
1 or 5
1 or 5
1.5 at FS
110V/190V
60
0.5
1.0
※주문시 ㎐ 선택
External connection diagram
Dimension for Meter
218
DEESYS TOTAL PRODUCTS GUIDE
Dimension for External Power supply Box
Panel Board Meter
Dimension
UNIT : m/m
�Wide angle type (80 x 80mm)
�Wide angle type (110 x 110mm)
�Square type (80 x 80mm)
�Square type (100 x 84mm)
DEESYS TOTAL PRODUCTS GUIDE
219
Panel Board Meter
Dimension
UNIT : m/m
�INT. T/D (watt,var, unbalance type P.F meter, Demand meter)
�INT. T/D (balance type P.F meter)
�W11 type meter relay(110×110m)
220
DEESYS TOTAL PRODUCTS GUIDE
3상 절환형 각형 지시전기계기 [교류전압 전류계]
KSC-1303 JIS C 1102
Model
특징
∙ 단상 3선 또는 3상3선식 회로에서 각상의 상태를 전면부에서 직접
절환하여 전압, 전류를 볼 수 있는 계기입니다.
∙ AS, VS 스위치 가 필요 없으므로 공간 활용 및 배선 작업이 간편
하고 스위치로 인한 문제발생 요인을 제거하였습니다.
∙ 판넬 취부가 용이하도록 설계되어있습니다.
∙ 주위 환경에 대해 높은 신뢰성을 가지고 있습니다.
∙ 전류가 5A 초과시에는 변류기를 조합하여 사용하십시오.
∙ 회로 전압이 300V를 초과 사용시에는 VT를 사용 하십시오.
S8 - S V A
AC
Voltage
Phase Selection
Square Type(80mm)
Specification
Part Name
3Phase Selection type panel Board Meter(V,A)
Item
Volt Meter(V)
Ampere Meter(A)
Type
S8-SVA
S8-SAA
Accuracy
±2.5%
±2.5%
Rating
AC 150V, 300V
AC 5A or 1A
Input burden
0.5VA
1.5VA
Frequency
동작원리
AC 50/60㎐
Rectifier(정류형)
Moving lron type(가동철편형)
스위치 내구성
정격전류 인가하여 스위치 절체시 10,000회
절연저항
회전기회로와 외함간 500V Megger 100㏁ 이상
내전압
전기회로와 외함간 AC 2000V/MIN
재질
Cover:Poly cabonate(투명)
중량
Case:내열성 ABS(흑색)
0.3kg
※ 기타 계기에 대한 모든 적용 규격은 당사의 제품인 S8-VA, S8-AA와 같습니다.
※ 주문시 Hz 선택
DEESYS TOTAL PRODUCTS GUIDE
221
KSC-1303 JIS C 1102
3상 절환형 각형 지시전기계기[교류전압 전류계]
Wiring
Dimension
222
DEESYS TOTAL PRODUCTS GUIDE
Digital Panel Meter
General Specification
Digital Panel Meter 96×48.
Insulation
Temperature
� Insulation resistance at DC500V 100MΪ
� Withstand voltage 2KV for 1 minuts between all terminals
� Lightning impulse voltage 1.2/50μ
s 4.5kV
Display and Rating
�
�
�
�
�
�
�
Display range : 1999 4digit-LED 7 segment
Digit Height : 14.22mm
Color: Red
Aux. power : AC 110/220V
Frequency : 50/60Hz
Outside dim. : 96×48×112mm
Response time : less than 500ms
� Operating temperature : 0~ 50℃
� Storage temperature : -20 ~ +70℃
Standard operating condition
�
�
�
�
Temperature 0~50℃
Humidity
5~85%
Aux. supply ±10%
Power harmonic sine wave 10%
Example of Application
Direct type
With TD type(Analog입력)
Communication type
DEESYS TOTAL PRODUCTS GUIDE
223
Digital Panel Meter [96 48mm]
Specification
Commercial type Panel Board Meter 96 X 48mm - DIN std. Part Name
Digital Panel Meter
Front view
Type
Connection
Input
Input burden
Aux. power
AC-A,V
DC-A,V
Hz
CT or VT
Direct. others
VT
A:0.1~10A
A : 1㎃~10A
AC 50~300V
V;1~500V
V : 50㎷~350
V40~70㎑
0.3VA이하
A : 0.2V drop
0.3VA이하
V : 10㏁
AC110/220V±15%, 50/60㎐ 3VA 이하
Aux. power burden
3VA 이하
Display resolution
1.999/0.001, 19.99/0.01, 199.9/0.1, 1999/1 step
Respons time
1 sec 이하
Accuracy
±0.5% + 1digit
Display range
1999 4 digit-LED 7 segment
Display color
Red
Terminal withstand
Current : for 5sec 20×In
capability
Voltage : for 5sec 1.5×Vn
Temperature
Operating temperature 0~50℃
RH<95%
Storage temperature -20~+70℃
Mounting
Flush mounted type
Insulation resistance
DC 500V Megger 100㏁ More-between all terminals
Withstand voltage
2㎸ for 1 minuts - between all terminals
Lightning impulse
withstand voltage
Vibration
Shock
Weight
224
DEESYS TOTAL PRODUCTS GUIDE
1.2/50㎲ 4.5㎸
Vibration frequency:16.7㎐ Double amplitude:0.4㎜ Direction:horizontal, vertical, transerse
Shock acceleration : 50G Shock application Direction : horizontal, vertical, transverse
Shock times : 3 times
350g
Digital Panel Meter [96 48mm]
Ordering Code
D
D : Direct(직가)
A : analog(입력)
Digital Meter
9:W96mmXH48mm
AA : AC Ammeter(A)
AV : AC Voltmeter(V)
DA : DC Ammeter(A)
DV : DC Voltmeter(V)
WT : Watt(W)
VR : var(var)
PF : PowerFactor(cosφ
)
HZ : Frequency(㎐)
(50,60㎐선정)
WH : kWhr meter
VH : kVarh meter
01 : Ampere-(19.99A,199.99A, 1999A중 선택)
02 : Volt-AC0~500V(500V이상의 경우는 보조 PT사용)
03 : DC 1㎃~10A(F.S지정)
04 : DC 50㎃~350V(F.S지정)
05 : DC 4~20㎃(With TD-F.S는 주문에 의함)
06 : DC 4~20㎃(With TD-F.S는 Program 방식)
Digital Panel Meter 96X48mm
Ammeter는 직접 Line에 연결하여 사용하는 type과 계장용 Transducer와 조합하여 사
용되는 type RS-485를 이용한 통신방식으로 나누어지며 전면에서 사용조건에 맞도록
Program으로 설정이 가능합니다.
CT의 정격은 1 또는 5A 이며 True rms 방식을 채택 하였습니다.
AC Ammeter
Ordering Procedure
Model
Display
Connection
Accuracy
D9AA-D01
D9AA-A05
Aux.Power
19.99A, 199.9A, 1999A선택(Input 5A)
Direct(직가)
0.5% or 1 digit
AC110/220V,50/60㎐
1999,9999(4~20㎃)
WithT/D-FS주문사양
0.5% or 1 digit
AC110/220V,50/60㎐
Model
Display
Connection
Accuracy
Aux.Power
D9AV-D02
19.99A,199.9A,1999A선택(Input Max.500V)
Direct
0.5% or 1 digit
AC110/220V,50/60㎐
D9AV-A05
1999,9999V(4~20㎃)
WithT/D-FS주문사양
0.5% or 1 digit
AC110/220V,50/60㎐
AC Voltmeter
Ordering Procedure
DEESYS TOTAL PRODUCTS GUIDE
225
Digital Panel Meter [96 48mm]
DC Ammeter
Ordering Procedure
Model
Display
Connection
Accuracy
Aux.Power
D9DA-D03
19.99A,199.9A,1999A선택(Input 1㎃~10A)
D9DA-A05
1999,9999A(4~20㎃)
Direct(직가)
0.5% or 1 digit
AC110/220V,50/60㎐
WithT/D-FS주문사양
0.5% or 1 digit
AC110/220V,50/60㎐
Model
Display
Connection
Accuracy
Aux.Power
D9DV-D04
D9DV-A05
19.99A,199.9A,1999A선택(50㎷~350V)
Direct(직가)
0.5% or 1 digit
AC110/220V,50/60㎐
1999,9999A(4~20㎃)
WithT/D-FS주문사양
0.5% or 1 digit
AC110/220V,50/60㎐
DC Voltmeter
Ordering Procedure
Watt, var, Power Factor-meter
Ordering Procedure
Item
Watt
Model
Display
D9WT-A05
1999,9999㎾(4~20㎃)
D9WT-A06
D9WT-A05
Var
D9WT-A06
0~999.9㎾(4~20㎃)
Program setting
(cos∅)
D9PF-A05
D9PF-A06
0~999.9kvar(4~20㎃)
226
DEESYS TOTAL PRODUCTS GUIDE
Aux.Power
WithT/D
0.5% or 1 digit
AC110/220V,50/60㎐
0.5% or 1 digit
AC110/220V,50/60H
0.5% or 1 digit
AC110/220V,50/60㎐
계장신호
WithT/D
계장신호
4㎃(-0.5)~12㎃(1)~20㎃(0.5)
4~20㎃
WithT/D
4㎃(-0.5)~12㎃(1)~20㎃(0.5)
계장신호
4~20㎃ Program set.
P.F의 극성 표시는“-”
만 표시됩니다.
Accuracy
1999,9999kvar(4~20㎃)
Program setting
PF
Connection
Digital Panel Meter [96 48mm]
Hz meter
Ordering Procedure
Model
D9HZ-D02
Display
Connection
50㎐:40~60㎐
Direct
60㎐:50~70㎐(AC110)
(직결 Max.300V)
50㎐:40~60㎐
D9HZ-D05
WithT/D-FS주문사양
60㎐:50~70㎐(4~20㎃)
Accuracy
Aux.Power
0.5% or 1 digit
AC110/220V,50/60㎐
0.5% or 1 digit
AC110/220V,50/60㎐
kWhr, kVarh meter
Ordering Procedure
Model
Display
Connection
Aux.Power
D9WH-A08
999999 count
WithT/D-계장신호(dry contact)
AC110/220V
Dimension
Terminal connection
Wiring
Ampere
Volt
DEESYS TOTAL PRODUCTS GUIDE
227
Current and Voltage
Transformer
■Round Type Current Transformer [1.15kV]
■Winding Type Current Transformer [1.15kV]
■Square Type Current Transformer [1.15kV]
■Voltage Type Transformer [0.72kV]
■Busbar Type Current Transformer [3.45-7.2kV]
■Square WindowType Current Transformer
[3.45-7.2kV]
■Voltage Transformer [3.45-7.2kV]
■Ground Type Voltage Transformer
[3.45-7.2kV]
■Round Type Zero PhaseCurrent Transformer
[3.45-7.2kV]
■Epoxy Resin Insulator [0.6kV]
■Epoxy Resin Insulator [7.2, 12kV]
■Epoxy Resin Insulator [24, 36kV]
■Shunt [Voltage Drop 50mV]
■Current Limit Resister [CLR]
CT, VT (저압, 고압,)
절연애자 (0.6kV, 7.2kV, 12kV, 24kV, 36kV)
Round Type Current Transfomer [1.15kV]
KSC-1706
DR-1, DR-2, DR-3, DR-18
∙Resin : ABS Non-flamable(case)
∙Mold : Polyester
∙Cable through type
∙Mounting parts to be changeable at 90。
direction
∙For metering application
∙For indor
∙Color : Brown
∙케이블 관통형
∙취부방향 90。회전가능
∙일반 계기용
∙옥내용
∙케이스 ABS 난연성
●정격 Ampere turn이란?
정격 AT는 정격 1차전류“A”
에 1차도체의 관통회수 ”
T”를 곱한 값
을 나타냅니다.
따라서 1차도체를 달리하면 여러 가지의 정격 1차전류를 얻을수 있
습니다.
[예] 정격 AT가 200AT 인 경우
관통수 1T
정격 1차 전류 200A
의 회로에 사용할수
관통수 2T
정격 1차 전류 100A
있습니다.
관통수 4T
정격 1차 전류 50A
●Specification
Type
Rated
(AT)
Burden
(VA)
Class
(%)
5
1.0
Over
Frequen
Current
-cy
Strength
(Hz)
(times)
Weight
(kg)
75
100
DR-18
120
150
200
100
●What is rating ampere turn?
The rating A.T is the value of rating 1ry current(A) a
multiplies the turn of
1ry conductor.
According to the method how the turn of 1ry
conductor is changed. It is able to change rating
1ry current.
ex) In case of rating AT : 200 AT
The turn of cable 1T :rating 1ry current 200A
The turn of cable 2T :rating 1ry current 100A
The turn of cable 4T :rating 1ry current 50A
Refer to page 231 for the turn and cross area of 1’
ry
conductor according to rating 1’
ry current.
120
150
160
DR-1
0.55
5
1.0
180
or
200
3.0
240
250
5 or 15
300
40In
50/60
240
250
DR-2
15
1.0
300
0.75
400
500
15 or 40
600
500
●Dimension
600
230
Type
A
B
∅C
∅D
E
F
G
DR-18
84
48
18
64
65
80
50
DR-1
95
55
27
70
75
94
40
DR-2
108
65
40
87
75
94
40
1200
DR-3
134
77
60
114
75
94
40
1500
DEESYS TOTAL PRODUCTS GUIDE
750
DR-3
800
1000
15 or40
1.0
1.10
Round Type Current Transfomer [1.15kV]
KSC-1706
●DR CT 1차 도체 관통회수에 따른 전류비와 1차도체 단면적
다음 표는 정격 1차 전류와 1차 도체 관통회수 및 관통가능한 600V
비닐 전선(600V Ⅳ 전선)의 최대공칭 단면적을 기재하였습니다.
이 표의 값은 주위온도 40℃에서 전선의 허용 전류를 표시하였습니다.
Rated
AT
75
100
150
160
180
200
250
300
5VA
15VA
DR-1 / DR-18
DR-2
1ry
current
(A)
turns
(T)
5
15
25
75
5
10
20
25
50
100
15
25
30
50
75
100
10
20
40
80
160
10
20
30
60
90
180
20
25
40
50
100
200
25
50
125
250
50
60
75
100
150
300
15
5
3
1
20
10
5
4
2
1
10
6
5
3
2
1
16
8
4
2
1
18
9
6
3
2
1
10
8
5
4
2
1
10
5
2
1
6
5
4
3
2
1
1ry
cable
(mm2)
(
Rated
AT
)
8
14
50
)
8
14
14
22
200
8
14
14
38
50
200
8
14
38
50
200
8
14
22
50
60
200
8
14
22
38
50
200
8
14
50
200
14
14
22
38
50
200
240
(
250
300
400
500
600
●Current ratio and across area of 1ry conductor
According to turn of DR. CT 1ry conductor Follwing table
is discribed the trun rating 1ry current, 1ry conductor and
the cross area of 600V vinyl wire(6000.I Wire)
The allownace current of wire is the value at amboent
temperaure 40℃ discribed.
40VA
DR-3
1ry
current
(A)
turns
(T)
1ry
cable
(mm2)
15
20
30
60
120
240
25
50
125
250
30
50
75
100
150
300
40
50
100
200
400
50
100
125
250
500
70
100
150
200
300
600
16
12
8
4
2
1
10
5
2
1
10
6
4
3
2
1
10
8
4
2
1
10
5
4
2
1
8
6
4
3
2
1
5.5
14
22
80
125
500
14
60
125
500
22
38
80
80
125
500
14
22
80
200
500
14
60
80
125
500
22
60
80
100
125
500
Rated
AT
500
600
750
800
1000
1200
1500
1ry
current
(A)
turns
(T)
50
100
125
250
500
75
100
150
200
300
600
75
150
250
750
80
100
200
400
800
100
200
250
500
1000
100
200
300
400
600
1200
150
300
500
750
1500
10
5
4
2
1
8
6
4
3
2
1
10
5
3
1
10
8
4
2
1
10
5
4
2
1
12
6
4
3
2
1
10
5
3
2
1
1ry
cable
(mm2)
38
125
125
250
500
60
60
125
150
250
500
38
125
250
500
38
50
125
250
500
38
125
125
250
500
38
125
125
( )
80×3(
250×3(
38
125
250
80×3(
250×3(
)
)
)
)
●DR CT의 내경과 관통전선의 외경과의 관계
(ex)In case of DR-1type CT and 3 trun of 38㎟ outer cross lengh of 38㎟ will 11.5
The error 120 & 100AT is 0.3 class and then inner cross lengh of DP-50F CT
is 27mm and the CTcan be used
㎟
DEESYS TOTAL PRODUCTS GUIDE
231
Winding Type Current Transfomer [1.15kV]
DRW-15, DRW-40, DRB-1, DRB-2, DRBD-1, DRBD-2
∙권선형
∙일반계기용
∙보통전력계량용
∙케이스 ABS 난연성
∙Winding type
∙Color : Brown
∙For metering
∙Resin : ABS Non-flamable(case)
∙For watt hour meter
∙Mold : Polyester
∙Changeable 90。at mounting direction
●Single ratio C.T
DRW C.T
Type
Primary
(A)
5~30
40~150
DRB-1 200~300
400~500
DRW-40
5~30
40~150
DRB-2 200~300
400~500
SeconBurden
dary
(VA)
(A)
Class
(%)
DRW-15
5 or 1
5 or 1
15
40
1.0
over curr. Frequdimen- Weight
strenght ency
Remark
sion
(kg)
(times)
(Hz)
Fig 1
0.70 Terminal Type
40in
1.0
40in
50/60
50/60
Type
Primary
(A)
10~150
5~75
DRBD-1 200~300
100~150
400~500
200~250
10~150
5~75
200~300
DRBD-2 100~150
400~500
200~250
Fig1.5~30A(DRW C.T)
SeconBurden
dary
(VA)
(A)
5 or 1
Class
(%)
Primary
curreent
DRW-15
Fig 1
1.0
Terminal Type
Fig 2
1.2
Busbar Type
5 or 15
Remark
0.92
1.0
40in
50/60
Fig 2
5 or 1 15 or 40
Busbar Type
1.35
Fig2. 200~500A(DRB C.T)
Type
Dimension
A
B
D
80
100
90
100
118
102
5~30
DEESYS TOTAL PRODUCTS GUIDE
Primary
current(A)
Dimension
A
40~150
80
(20~75)
DRB-1 200~300
80
DRBD-1 (100~150)
400~500
(200~250) 80
40~150
100
(20~75)
DRB-2 200~300
100
DRBD-2 (100~150)
400~500
(200~250) 100
※(
232
Busbar Type
over curr. Frequdimen- Weight
strenght ency
sion
(kg)
(times)
(Hz)
Unit : mm
DRW-40
0.85
●Double ratio C.T
DRB C.T
Type
Fig 2
B
C
D
E
F
G
H(∅)
100
60
125
100
25
3.2
6
100
60
135
105
30
6
10
100
60
155
115
30
6
12
118
70
135
110
25
3.2
6
118
70
145
115
30
6
10
118
70
165
130
40
6
12
)안의 전류값은 DRBD(Double Ratio)type 일때 적용
Square Type Current Transfomer [1.15kV]Busbar취부용
DS-1, DS-2, DS-3, DS-4, DS-5, DS-6
DSD-1, DSD-2, DSD-3, DSD-4, DSD-5, DSD-6
∙부스바 관통형
∙일반계기용
∙옥내용
∙케이스 ABS 난연성
∙Busbar through type
∙Color : Brown
∙For metering
∙Resin : ABS Non-flamable(case)
∙For indoor
∙Mold : Polyester
●Single ratio C.T
Type
DS-1
DS-2
DS-3
DS-4
DS-5
DS-6
Primary
(A)
100~150
200~300
300
400
500~600
600~1000
750~2000
1000~4000
2500~8000
Secondary
(A)
5 or 1
Burden
(VA)
Class
(%)
5
5 or 15
40
15 or 40
40
40
3.0
over curr.
strenght
(times)
Frequency
(Hz)
Weight
(kg)
1.3
40in
50/60
over curr.
strenght
(times)
Frequency
(Hz)
1.0
40
1.5
1.5
1.6
1.9
4.8
●Double ratio C.T
Type
DSD-1
DSD-2
Primary
(A)
Secondary
(A)
Burden
(VA)
200~100
5
300~150
5
400~200
5
Class
(%)
3.0
Weight
(kg)
1.3
500~250
1.5
600~300
DSD-3
DSD-4
800~400
1000~500
1200~600
2000~1000
15
5 or 1
(생산의뢰)
1.5
1.0
40in
50/60
1.6
40
2000~1000
DSD-5
2400~1200
3000~1500
1.9
40
4000~2000
DSD-6
Unit : mm
4.8
●Double C.T Connection diagram
Dimension
Type
DS-1, DSD-1
6000~3000
A
B
C
D
44
110
80
10
DS-2, DSD-2
65
115
65
11
DS-3, DSD-3
85
135
70
13
DS-4, DSD-4
105
155
85
22
DS-5, DSD-5
130
212
126
41
DS-6, DSD-6
160
260
180
75
DS CT is designed how to install the busbar is very
easy being used the installing metal. Busbar.
DEESYS TOTAL PRODUCTS GUIDE
233
Square Type Current Transfomer [1.15kV]Panel취부용
DS-1, DS-2, DS-3, DS-4, DS-5, DS-6
DSD-1, DSD-2, DSD-3, DSD-4, DSD-5, DSD-6
∙부스바 관통형
∙일반계기용
∙옥내용
∙케이스 ABS 난연성
∙Busbar through type
∙Color : Brown
∙For metering
∙Resin : ABS Non-flamable(case)
∙For indoor
∙Mold : Polyester
∙취부가 견고하므로 진동이 많은 곳에 사용하시기 바랍니다.
●Single ratio C.T
Type
DS-1
DS-2
DS-3
DS-4
DS-5
DS-6
Primary
(A)
100
150~200
250~300
300
400
500~600
750~1000
1200~2000
2500~4000
3000~8000
Secondary
(A)
5 or 1
Burden
(VA)
Class
(%)
5
5 or 15
15
40
15 or 40
40
40
3.0
over curr.
strenght
(times)
Frequency
(Hz)
Weight
(kg)
1.3
1.0
40in
50/60
over curr.
strenght
(times)
Frequency
(Hz)
40
1.5
1.5
1.6
1.9
4.8
●Double ratio C.T
Type
DSD-1
Primary
(A)
Secondary
(A)
200~100
Burden
(VA)
5
300~150
Class
(%)
3.0
Weight
(kg)
1.3
400~200
DSD-2
500~250
1.5
600~300
DSD-3
DSD-4
15
800~400
1000~500
1200~600
1.5
5 or 1
40in
1.0
2000~1000
50/60
1.6
2000~1000
DSD-5
2400~1200
3000~1500
40
1.9
4000~2000
DSD-6
234
DEESYS TOTAL PRODUCTS GUIDE
6000~3000
4.8
Voltage Transformer and Grounding Voltage Transformer [0.72kV]
∙단상
∙계기용 및 계전기용
∙옥내용
∙케이스 ABS 난연성
∙Single phase
∙Color : Brown
∙metering & relaying
∙Resin : ABS Non-flamable(case
∙For indoor
∙Mold : Epoxy
●Specification
Name
Type
Rated voltage(V)
1’ry
2’ry
3’ry
Burden(VA)
2’ry
2’ry
3’ry
DP-50
DP-50F
V.T
DP-100
50
2.5
220
380
DP-100F
DP-200
Frequ Voltage
Weight
-ency Factor
3’ry (Hz) (IEC-186) (kg)
Accuracy Class
110
or
190
1.2Vn
cont
100
3.2
440
-
-
200
5.8
DP-200F
DGP-100
1.0
※ 주의 : 3차 권선의 open terminal 간의 부담이
정격 부단보다 많이 작게되면 잔류전압이
발생되어 계전기의 오동작 원인이 될 수도
있습니다.
사용부담을 정격 부담의 100~70%가 되도록하여 주
시기 바랍니다.
※ Note : It the burden of 3ry winding open
terinal is less than rating burden.
It may be the reason of relay
malfunction due to remaining
voltage.
Please select the pit that applieable burden
of PT will be 100~70% of rating burden.
50/60
50
3.2
DGP-100F
DGP-200
220 3 190/ 3
100
DGP-200F
GPT
DGP-100T
DGP-100TF
DGP-200T
DGP-200TF
380 3
or
440 3 110/ 3
5.8
100
190/3
or
110/3
50
3P
3.0C
1.2Vn
cont
1.9Vn
30s
3.2
200
100
3.0C
5.8
●Dimension
Model
A
B
C
D
E
DP-50
100
102
30
75
77
DP-100/DGP-100
118
112
33
75
73
DP-200/DGP-200
166
126
37
82
142
DEESYS TOTAL PRODUCTS GUIDE
235
Busbar Type Current Transformer [3.45-7.2kV]
∙계기용 ∙For metering
∙계전기용∙For protective relay
Dimension
∙Color : Brown
∙Resin : Lupoy Non-flamable (case)
∙Mold : Epoxy
Specification
Type
Specificaton
Standard
KS C-1706
Max. Voltage
3.45kV/7.2KV
Rated Burden
15, 40VA
Accuracy Class
1.0/10P10
Frequency
50/60HZ
Rating
Model
AHB-1
AHB-1R ※
Primary(A)
Secondary(A)
Class(%)
Burden(VA)
Over Current
1.0
40
-
1.0/10P10
15
n〉
10
Over curr.strength
Weight(kg)
40 times
4.0
5~300
5
Primary(A)
A
B
C
D
E
F
5~300
187
100
110
35
66
4
Dimension
Model
AHB-1
AHB-1R ※
*R: For Protective Relay
236
DEESYS TOTAL PRODUCTS GUIDE
Square Window Type Current Transformer [3.45-7.2kV]
∙계기용
∙계전기용
∙부스바관통형
∙For metering
∙For protective relay
∙Bus bar through
Dimension
∙Color : Brown
∙Resin : Lupoy Non-flamable(case)
∙Mold : Epoxy
Unit: mm
Model
A
B
C
D
E
AHS-1/AHSD-1
146
145
92.5
10
65
AHS-2/AHSD-2
186
155
97.5
20
105
Specification (Single Ratio)
Type
Specificaton
Standard
KS C-1706
Max. Voltage
3.45kV/7.2KV
Rated Burden
15, 40VA
Accuracy Class
1.0/10P10
Frequency
50/60HZ
Rating (Single Ratio)
Model
1ry current(A)
AHS-1
300~600
AHS-2
750~2000
AHS-1R
※
AHS-2R ※
400~600
750~2000
2ry current(A)
Class(%)
Burden(VA)
Over Current consrant Over curr.strength
5 or 1
1.0
5 or 1
1.0/10P10
2ry current(A)
Class(%)
Burden(VA)
1.0
40
-
5.0
1.0
40
-
5.0
1.0/10P10
15
n〉
10, n〉
5
1.0/10P10
15
n〉
10, n〉
5
40
-
40
-
15
n〉
10
15
n〉
10
40 times
Weight(kg)
5.0
*R: For Protective Relay
Rating (Double Ratio)
Model
AHSD-1
AHSD-2
AHSD-1R※
AHSD-2R※
1ry current(A)
400~600
200~300
800~2000
5 or 1
400~1000
400~600
200~300
800~2000
400~1000
5 or 1
Over Current consrant Over curr.strength
40 times
Weight(kg)
5.0
5.0
*R: For Protective Relay
DEESYS TOTAL PRODUCTS GUIDE
237
Voltage Transformer [3.45-7.2kV]
Dimension
∙계기용 ∙For metering
∙계전기용
∙For protective
∙Color : Brown
∙Resin : Lupoy Non-flamable (case)
∙Mold : Epoxy
Type
A
B
C
D
E
F
AHP-1
125
160
223
107
55
87
138
160
223
107
55
98
AHP-2
AHP-3
Specification
Type
Specificaton
Standard
KS C-1706
Max. Voltage
3.45kV/7.2kV
PRI. Voltage
3,300 or 6,600V
Accuracy Class
1.0/ 3.0
Frequency
50/60HZ
Secondary Voltage
110V
Rating(Single ratio)
238
Model
1ry current(A)
2ry current(A)
Class(%)
Burden(VA)
Weight(kg)
AHP-1
3300~6600
110
1.0
50
8
AHP-2
3300~6600
110
1.0
100
10
AHP-3
3300~6600
110
3.0
200
10
DEESYS TOTAL PRODUCTS GUIDE
Ground VoltageTransformer [3.45-7.2kV]
Dimension
∙계기용 ∙For metering
∙계전기용
∙For protective
∙Color : Brown
∙Resin : Lupoy Non-flamable (case)
∙Mold : Epoxy
Type
A
B
C
D
E
F
AHGP-2
125
160
223
107
55
87
AHGP-3
138
160
223
107
55
98
Specification
Type
Specificaton
Standard
KS C-1706
Max. Voltage
3.45kV/7.2KV
PRI. Voltage
3,300/ 6,600V
Accuracy Class
1.0/3G
Frequency
50/60HZ
Secondary, third Voltage
110/3. 190/3
Rating(Single ratio)
Model
AHGP-2
AHGP-3
1ry Voltage(V)
2ry Voltage(V)
3ry Voltage(V)
3300/√3 or
190/√3
190/ 3
6600/√3
110/√3
110/ 3
3300/√3 or
190/√3
190/ 3
6600/√3
110/√3
110/ 3
Class(%)
Burden(VA)
Weight(kg)
2ry
3ry
2ry
3ry
1.0
3G
50
100
8
1.0
3G
100
200
10
※ 주의 : 3차 권선의 open단자간의 사용부담이 정격 부담보다 작게되면 잔류전압이 발생되어 계전기의 오동작 원이이 될 수도 있습니다.
사용부담을 정격부담의 100~70%가 되도록하여 주시기 바랍니다.
※ Note : It the burden of 3ry winding open terminal is less than rating burden. It may be the reason of realy malfunction due to remaining voltage
please select the pit applieable burden of P.T will be 100~70% of rating burden.
DEESYS TOTAL PRODUCTS GUIDE
239
Round Type Zero Phase Sequence Current Transformer [3.45-7.2kV]
∙케이블 관통형
∙방향성 계전기용
∙옥내용
∙Cable through type
∙Color : Brown
∙For SGR protective relay(induction)∙Resin : ABS Non-flamable(case)
∙For indoor type
∙Mold : Polyester
Dimension
Type
A
B
C
D
ZT-1
177
70
175
95
ZT-2
220
110
220
120
Specification
Type
Specificaton
Standard
KS C-1706
Rated Impedance
10Ω(P.F : 0.5LAG)
Accuracy Class
“L”CLASS
Frequency
50/60HZ
Rating(Single ratio)
240
Model
Rated current(A)
Zero phase 1ry(mA)
Zero phase 2ry(mA)
error(mA)
burden(Ω)
ZT-1
5~300
200
1.5
1.5 (1.0-2.0)
10(PF : 0.5LAG)
ZT-2
400~1200
200
1.5
1.5 (1.0-2.0)
10(PF : 0.5LAG)
DEESYS TOTAL PRODUCTS GUIDE
Epoxy Resin Insulators [0.6kV]
∙분전반, 배전반 제어반 등의 절연을 위하여 사용되는 EPOXY 수지로 된 절연지지
애자로 저압회로에 사용됩니다.
unit: mm
LGD-2010
LGD-266
LGD-260
LGD-C30
LGD-3030
30
2-M6 DP7
Rating
LGD-2010
LGD-266
LGD-260
LGD-C30
LGD-3030
Rated Voltage
(kv)
0.6
0.6
0.6
-
0.6
Power Frequency Withstand Voltage
(kv)
-
-
-
-
-
Impulse Withstand Voltage
(kv)
-
-
-
-
-
Power Frequncy Flashover Voltage
(kv)
-
-
-
-
-
Impulse flashover Voltage
(kv)
-
-
-
-
-
Tensile Strength
(kg)
-
-
-
-
-
-
60
Contents
Type
Bending Strength
(kg)
-
30
30
Net Weight
(kg)
-
0.03
0.03
-
0.05
Leakage Distance
(mm)
-
26
26
-
30
Insulation Level
-
-
-
-
-
Remark
-
-
-
-
-
DEESYS TOTAL PRODUCTS GUIDE
241
Epoxy Resin Insulators [0.6kV]
∙분전반, 배전반 제어반 등의 절연을 위하여 사용되는 EPOXY 수지로 된 절연지지 애자로 저압회로에 사용됩니다.
unit: mm
LGD-4040
LGD-5040
LGD-5050
LGD-6040
LGD-6070
2-M10 DP14
Rating
Contents
Type
LGD-4040
LGD-5040
LGD-5050
LGD-6040
LGD-6070
0.6
0.6
Rated Voltage
(kv)
0.6
0.6
0.6
Power Frequency Withstand Voltage
(kv)
-
-
-
-
-
Impulse Withstand Voltage
(kv)
-
-
-
-
-
Power Frequncy Flashover Voltage
(kv)
-
-
-
-
-
Impulse flashover Voltage
(kv)
-
-
-
-
-
Tensile Strength
(kg)
600
500
1200
500
1200
Bending Strength
(kg)
60
60
200
60
360
Net Weight
(kg)
0.14
0.13
0.17
0.18
0.55
Leakage Distance
(mm)
40
57
58
60
65
Insulation Level
-
-
-
-
-
Remark
-
-
-
-
-
242
DEESYS TOTAL PRODUCTS GUIDE
Epoxy Resin Insulators [7.2kV]
∙분전반, 배전반 제어반 등의 절연을 위하여 사용되는 EPOXY 수지로 된 절연지지 애자로 고압회로에 사용됩니다.
∙전기적, 기계적 내구성이 우수합니다.
unit: mm
LGD-8030
LGD-8055
LGD-8075
LGD-8085
Rating
Contents
Type
LGD-8030
LGD-8055
LGD-8075
LGD-8085
7.2
Rated Voltage
(kv)
7.2
7.2
7.2
Power Frequency Withstand Voltage
(kv)
22
22
22
22
Impulse Withstand Voltage
(kv)
60
60
60
60
Power Frequncy Flashover Voltage
(kv)
50
50
55
55
Impulse flashover Voltage
(kv)
80
80
90
90
Tensile Strength
(kg)
210
600
1200
2000
Bending Strength
(kg)
60
180
360
720
Net Weight
(kg)
0.25
0.39
0.77
0.95
Leakage Distance
(mm)
110
110
122
127
6A
6A
6A
6A
EIB6A2
EID6A2
EIF6A2
EIH6A2
Insulation Level
Remark
DEESYS TOTAL PRODUCTS GUIDE
243
Epoxy Resin Insulators [7.2kV]
∙분전반, 배전반 제어반 등의 절연을 위하여 사용되는 EPOXY 수지로 된 절연지지 애자로 고압회로에 사용됩니다.
∙전기적, 기계적 내구성이 우수합니다.
unit: mm
LGD-9075
LGD-9085
Rating
Contents
Type
LGD-9075
LGD-9085
Rated Voltage
(kv)
7.2
7.2
Power Frequency Withstand Voltage
(kv)
22
22
Impulse Withstand Voltage
(kv)
60
60
Power Frequncy Flashover Voltage
(kv)
55
55
Impulse flashover Voltage
(kv)
90
90
Tensile Strength
(kg)
1200
2000
Bending Strength
(kg)
360
720
Net Weight
(kg)
0.78
0.88
Leakage Distance
(mm)
132
137
6A
6A
-
-
Insulation Level
Remark
244
DEESYS TOTAL PRODUCTS GUIDE
Epoxy Resin Insulators [12kV]
∙분전반, 배전반 제어반 등의 절연을 위하여 사용되는 EPOXY 수지로 된 절연지지 애자로 고압회로에 사용됩니다.
∙전기적, 기계적 내구성이 우수합니다.
unit: mm
LGD-11090
LGD-14586
LGD-145100
※액상
Rating
Contents
Type
LGD-11090
LGD-14586
LGD-145100
Rated Voltage
(kv)
12
12
12
Power Frequency Withstand Voltage
(kv)
28
36
36
Impulse Withstand Voltage
(kv)
75
95
95
Power Frequncy Flashover Voltage
(kv)
70
80
80
Impulse Flashover Voltage
(kv)
120
125
125
Tensile Strength
(kg)
2000
2000
3000
Bending Strength
(kg)
900
600
1400
Net Weight
(kg)
1.59
1.58
1.72
Leakage Distance
(mm)
Insulation Level
Remark
170
192
225
10B
10A
10A
EIJ10B2
EIJ10B2
-
DEESYS TOTAL PRODUCTS GUIDE
245
Epoxy Resin Insulators [24kV]
∙분전반, 배전반 제어반 등의 절연을 위하여 사용되는 EPOXY 수지로 된 절연지지 애자로 특고압회로에 사용됩니다.
∙전기적, 기계적 내구성이 우수합니다.
unit: mm
LGD-21090
LGD-22075
LGD-22090
Rating
Contents
Type
LGD-21090
LGD-22075
LGD-22090
Rated Voltage
(kv)
24
24
24
Power Frequency Withstand Voltage
(kv)
50
50
50
Impulse Withstand Voltage
(kv)
125
125
125
Power Frequncy Flashover Voltage
(kv)
115
115
115
Impulse flashover Voltage
(kv)
170
170
170
Tensile Strength
(kg)
2000
1500
2000
Bending Strength
(kg)
600
240
600
Net Weight
(kg)
2.12
1.49
2.22
Leakage Distance
(mm)
Insulation Level
Remark
246
DEESYS TOTAL PRODUCTS GUIDE
330
340
340
20B
20B
20B
EIG20B4
EIE20B2
EIG20B2
Epoxy Resin Insulators [24kV, 36kV]
∙분전반, 배전반 제어반 등의 절연을 위하여 사용되는 EPOXY 수지로 된 절연지지 애자로 고압회로에 사용됩니다.
∙전기적, 기계적 내구성이 우수합니다.
unit: mm
LGD-280100
LGD-310115
Rating
Contents
Type
LGD-280100
LGD-310115
Rated Voltage
(kv)
24
36
Power Frequency Withstand Voltage
(kv)
60
70
Impulse Withstand Voltage
(kv)
150
170
Power Frequncy Flashover Voltage
(kv)
140
150
Impulse flashover Voltage
(kv)
150
170
Tensile Strength
(kg)
2000
2000
Bending Strength
(kg)
600
600
Net Weight
(kg)
4.3
5.2
Leakage Distance
(mm)
Insulation Level
Remark
396
485
20A
30B
EIG20A2
EIG30B2
DEESYS TOTAL PRODUCTS GUIDE
247
Shunt [Voltage Drop 50mV]
Accuracy class : 1.0%
2’
ry drop voltage : DC 50mV
DC 100mV용 적용시 당사와 Dimension을 협의하십시요.
Dimension
Division
A
B
C
D
E
F
H
Type
130
26
75
103
150
17
13
DST-1
120~200
139
30
75
103
160
24
17
DST-2
220~300
139
30
75
103
160
24
17
DST-3
Rating(DC A)
10~100
● DST-4~7(400~750A)
● DST-10~30(1000~3000A)
Dimension
Division
TYPE
Rating(DC A)
A
DST-4
DST-5
DST-6
DST-7
DST-10
DST-12
DST-15
DST-20
DST-25
DST-30
400
500
600
750
1000
1200
1500
2000
2500
3000
40
50
50
60
70
80
90
100
100
100
● DST-40(4000A)
248
● DST-50(5000A)
TYPE
DST-40
DST-50
Rating(A)
4000
5000
DEESYS TOTAL PRODUCTS GUIDE
Current Limit Resistor [CLR]
한류저항은 GPT 3차측, a, f간에 접속되어 사고시 1차측 중성선에 흐르는 전류(lg)를 조정하여
(통상 380mA) 유효 전류를 발생시켜 지락계전기 및 영상전압계를 동직시킵니다. 또한 GPT 3차
측(OPEN DELTA)에 발생하는 제3고조파 및 이상전위 발생을 억제시켜 줍니다.
Current limit resistor(CLR) will make the grounding relay and zero voltage meter
operate due to the current which in a djusted primary neutral side current when
fault. And it will be connected with 3ry side of GPT between terminal “a” and
terminal “f” and then it restrains the 3ry harm once voltage and abnormal potential.
Specification
MODEL
1ry voltage
of GPT(KV)
3ry voltage
of GPT(V)
Resistance
value(Ω)
DCR-1
3.3
110
16
DCR-2
3.3
190
50
DCR-3
6.6
110
8
DCR-4
6.6
190
25
DCR-5
3.3, 6.6
110, 190
by order
capacity
● How to calculate the resistor value
(3300V, 6600V급에만 적용)
Ig=
E1
√3
×
1
n2
×
9
R
400W
Ig=
E1
√3
×
1
n2
×
9
Ig
※ Remark : 1. If max 3ry voltage of GPT is on CLR during 1 minute over, the
E1=
E2=
√3
190
3
V
R=25(Ω)
Ig=
R=
CLR may be fired.
6.600V
6.600V
√3
6.600V
√3
×
×
1
2
60
1
602
×
9
25
= 0.38(A)
9
×
= 25(Ω)
0.38
2. In case og low voltage G.P.T. Please adjust the value of CLR
to 100~70% loading value of rating burden on GPT 3ry open
Ig : Ground Fault Current
terminal.
E1 : GPT 1ry voltage
n : Voltage Ratio = Winding Ratio
※ 비고 : 1. GPT의 최고전압이 1분이상 인가되면 CLR이 소손될 우려가 있습니다.
R : Limting Resister(Ϊ )
2. 저압 GPT인 경우 3차 정격부담의 70~100%가 되도록 CLR 저항값을 조정
해서 사용하시기 바랍니다.
※ Remark : In case of low voltage GPT, the above formula
can not be used
※ 비고 : 저압 GPT의 경우는 상기식을 적용할 수 없습니다.
Dimension
Unit : mm
DEESYS TOTAL PRODUCTS GUIDE
249
Digital Electric& Electronics System (Formerly Known as DAIYUN Electronics Co., Ltd.)
HEADOFFICE & FACTORY
(R/D CENTER) ���-��� 경기도 김포시 대곶면 대능리 257-18
#257-18, Daenung-Ri, Daegod-Myeon, Kimpo-City, Gyunggi-Do, KOREA
TEL: 031-987-8771, 996-5661~5 FAX: 031-987-9197, 996-5564
A/S PART
TEL: 031-987-2420
http://www.deesys.com